Plan Review Details - Permit 09050396
Plan Review Stops For Permit 09050396
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-08 Cont ID  
Sent By jgomez Date 2009-06-08 Time 09:11 Rev Time 0.00
Received By jgomez Date 2009-06-08 Time 09:11 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-22 Cont ID  
Sent By jgomez Date 2009-05-22 Time 08:51 Rev Time 0.00
Received By jgomez Date 2009-05-22 Time 08:51 Sent To PC
Notes
2009-05-22 09:15:06RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE.
  
 1- REVISE INSTALLATION SCHEDULE ANCHOR SPACING FOR
 OPENINGS 1, 3, 4, 5, 6, 7 AND 9 TO MATCH THE CALCULATED
 DESIGN PRESSURES. CALCULATED DESIGN PRESSURES ARE
 -57.2. THEREFORE ANCHOR SPACING FOR -57 CAN'T BE USED.
 NEED TO USE HIGHER DESIGN PRESSURES ANCHOR SPACING.
  
 2- CLARIFY IF SUBSTRATE TO RECEIVE SHUTTERS IS POURED
 CONCRETE ON TOP AND BOTTOM. TYPICALLY THERE IS A
 PRECAST CONCRETE LINTEL OR POURED CONCRETE BEAM ON TOP,
 BUT WINDOW SILL MAY NOT BE POURED CONCRETE. PROVIDE
 PROOF THAT WINDOW SILL HAS MIN. 3,320 PSI CONCRETE
 STRENGTH AS REQUIRED BY THE PRODUCT APPROVAL OR USE THE
 CONCRETE BLOCK ANCHOR SPACING TO VERIFY COMPLIANCE WITH
 THE PRODUCT APPROVAL AND CALCULATED DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE.
 REVISE ANCHOR SPACING AS REQUIRED.
  
 3- REVISE LENGTH OF TAPCON. 1-3/4" TAPCON DOESN'T
 PROVIDE THE MIN. REQUIRED EMBEDMENT OF 1-3/4" ON
 CONCRETE INSTALLATIONS.
 NOTE: MINIMUM EMBEDMENT EXCLUDES STUCCO OR ANY OTHER
 FINISH. ALSO, MINIMUM EMBEDEMNT REQUIRED FOR CONCRETE
 BLOCK INSTALLATION IS 1-1/4" EXCLUDING STUCCO ALSO.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-08 Cont ID  
Sent By jgomez Date 2009-06-08 Time 09:15 Rev Time 0.00
Received By jgomez Date 2009-06-04 Time 15:13 Sent To  
Notes
2009-06-05 15:13:43GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-22 Cont ID  
Sent By jgomez Date 2009-05-22 Time 09:33 Rev Time 0.00
Received By jgomez Date 2009-05-19 Time 12:07 Sent To  
Notes
2009-05-20 12:07:42UNDER 5000 BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved