Plan Review Details - Permit 09050371
Plan Review Stops For Permit 09050371
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-09-24 Cont ID  
Sent By dwise Date 2009-09-24 Time 13:02 Rev Time 0.00
Received By dwise Date 2009-09-24 Time 13:01 Sent To  
Notes
2009-09-24 13:02:26STOREFRONT DOOR AND WINDOW SCHEDULES AND PRODUCT
 APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-08 Cont ID  
Sent By dwise Date 2009-07-08 Time 21:55 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 21:55 Sent To FIRE
Notes
2009-07-08 21:57:14APPROVED WITH PROVISOS:
 1. SUBMIT PRODUCT APPROVALS FOR IMPACT RESISTANT
 STOREFRONT, DOORS, AND EXTERIOR COMPONENTS AND CLADDING
 WHICH HAVE BEEN "ACCEPTED" FOR USE BY THE DESIGN
 PROFESSIONAL FOR REVIEW AND ACCEPTANCE BY THE CITY
 PRIOR TO INSTALLATION IN THE BUILDING.
 2. SUBMIT REVISED X-RAY SHIELDING SPECIFICATIONS WHICH
 BEAR THE STAMP OF APPROVAL FROM THE DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE PROJECT FOR REVIEW PRIOR TO
 INSTALLATION IN THE BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-28 Cont ID  
Sent By dwise Date 2009-05-28 Time 20:30 Rev Time 0.00
Received By dwise Date 2009-05-28 Time 18:00 Sent To  
Notes
2009-05-28 20:28:131.SHEET A-1. PLEASE PROVIDE AN EXISTING FLOOR OR DEMO
 PLAN IN ORDER TO CLARIFY THE EXTERIOR ENVELOPE OPENINGS
 THAT ARE BEING REMOVED AND CREATED AS A RESULT OF THIS
 PROJECT.
 2.SHEET A-1. PLEASE PROVIDE ANY AND ALL REVISED
 EXTERIOR ELEVATIONS.
 3. SHEET A-1. PLEASE CLARIFY NOTE RELATED TO "IMPACT"
 FILM IS APPLICABLE ONLY TO EXISTING EXTERIOR GLAZING.
 IT SHOULD ALSO BE NOTED THAT THERE IS NO FILM CURRENTLY
 IN EXISTENCE WHICH SATISFIES THE APPLICABLE CODE
 REQUIREMENTS FOR GLAZING PROTECTION IN THE WINDBORNE
 DEBRIS REGION.
 4. SHEET A-1 PLEASE PROVIDE DESIGN PRESSURES FOR ALL
 EXTERIOR COMPONENTS AND CLADDING (I.E., DOORS AND
 WINDOWS) THAT ARE BEING PROPOSED AS A RESULT OF THIS
 PROJECT.
 5. INFORMATIONAL ONLY: THE APPLICANT WILL BE REQUIRED
 TO PROVIDE PRODUCT APPROVALS FOR VARIOUS COMPONENTS OF
 THIS PROJECT FOR REVIEW AND APPROVAL BY THE
 CONSTRUCTION SERVICES DEPARTMENT BEFORE THEY ARE
 INSTALLED AT THE SITE. THESE COMPONENTS INCLUDE (BUT
 ARE NOT LIMITED TO) DOOR AND STORE FRONT PRODUCT
 APPROVALS, X-RAY EQUIPMENT, X-RAY SHIELDING, AND
 PERMANENTLY WIRED EQUIPMENT. ALL OF THESE SUBMITTALS
 MUST BEAR THE APPROVAL OF THE APPLICABLE DESIGN
 PROFESSIONAL AT THE TIME OF SUBMITTAL.
 6. INFORMATIONAL ONLY: SEPERATE APPLICATION, REVIEW,
 ACCEPTANCE AND PERMITTING SHALL BE REQUIRED FOR WORK
 RELATED TO FIRE ALARMS, FIRE SPRINKLERS, GREASE TRAPS,
 GAS, GENERATORS, FENCES, SITE LIGHTING, SITE
 LANDSCAPING, AND SITE IRRIGATION (IF ANY) WHICH MAY BE
 PROPOSED IN CONJUNCTION WITH THIS PROJECT.
 7. INFORMATIONAL ONLY: IT APPEARS THAT THE APPLICANT
 PROPOSES TO PLACE A GENERATOR AND SLAB OVER TWO
 ABANDONED GREASE TRAPS. THE EXISTING GREASE TRAPS SHALL
 BE ABANDONED PURSUANT TO STATE DEPARTMENT OF HEALTH
 REGULATIONS, AND MAY NOT BE DEEMED SUITABLE AS A
 FOUNDATION FOR THE GENERATOR SLAB BY THE CONSTRUCTION
 SERVICES DEPARTMENT.
  
 PLEASE FEEL FREE TO CONTACT ME DURING NORMAL BUSINESS
 HOURS IF YOU HAVE ANY QUESTIONS ABOUT THIS REVIEW. I
 MAY BE REACHED AT 561-805-6650 OR BY EMAIL AT
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-08 Cont ID  
Sent By dwise Date 2009-07-08 Time 21:32 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 21:32 Sent To  
Notes
2009-07-08 21:35:31APPROVED WITH PROVISO: PURSANT TO PRIOR REQUEST, IT
 STILL APPEARS THAT INADEQUATE ESSENTIAL ELECTRICAL
 SYSTEM TASK LIGHTING HAS BEEN PROVIDED IN THE EXAM
 ROOMS TO PROVIDE FOR THE ORDERLY CESSATION OF
 PROCEDURES IN THE EVENT OF A POWER FAILURE AT THE
 FACILITY. ALTHOUGH SOME EMERGENCY TASK LIGHTING HAS
 BEEN PROVIDED, A SIGNIFICANT NUMBER OF EXAM ROOMS HAVE
 BEEN OMMITED. PLEASE PROVIDE A REVISION WHICH SATISFIES
 THE REQUIREMENTS OF NEC SECTION 517.33. NOTE: BATTERY
 BACKUP EMERGENCY LIGHTS MAY BE UTILIZED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-28 Cont ID  
Sent By dwise Date 2009-05-28 Time 21:07 Rev Time 0.00
Received By dwise Date 2009-05-28 Time 21:07 Sent To FIRE
Notes
2009-05-28 21:12:101. ESSENTIAL ELECTRICAL SYSTEM TASK LIGHTING DOES NOT
 APPEAR TO BE INSTALLED IN ALL EXAM AND PROCEDURE AREAS
 PURSUANT TO THE REQUIREMENTS OF 517.33.
 2. THE X RAY DISCONNECTING MEANS APPEARS TO BE LOCATED
 IN A DIFFERENT ROOM THAN THE X RAY CONTROL PANEL AND IS
 THEREFORE NOT READILY ACCESSIBLE PURSUANT TO 517.72 (B)
 3. SHEET E-1 NOTE 8(B) NON-METALLIC CONDUIT MAY NOT BE
 RUN UNDERGROUND TO SERVE ANY PATIENT CARE AREAS
 PURSUANT TO 517.13.(A) AND (B).
 4. ALL RECEPTACLES IN PATIENT CARE AREAS SHALL BE
 DESIGNATED AS HOSPITAL GRADE PURSUANT TO 517.18(B),
 5. SHEET E-3.1. NOTE D. PLEASE ENSURE THAT RECEPTACLES
 IDENTIFIED AS BEING NECESSARY FOR THE ESSENTIAL
 ELECTRICAL SYSTEM MANDATED FOR THIS FACILITY PURSUANT
 TO 517.25 ARE PROVIDED IN EACH AREA SO DESIGNATED. IT
 APPEARS THAT ONLY CERTAIN EXAMINATION AND PROCEDURE
 ROOMS ARE APPROPRIATELY CIRCUITED. PLEASE CLARIFY.
 6. INFORMATIONAL ONLY: SEPARATE APPLICATIONS AND
 PERMITS ARE REQUIRED FOR THE PROPOSED GENERATOR AND
 FIRE ALARM SYSTEM.
 PLEASE FEEL FREE TO CONTACT ME DURING NORMAL BUSINESS
 HOURS IF YOU HAVE ANY QUESTIONS ABOUT THIS REVIEW. I
 MAY BE REACHED AT 561-805-6650 OR BY EMAIL AT
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-13 Cont ID  
Sent By mawillia Date 2009-07-13 Time 14:50 Rev Time 0.00
Received By mawillia Date 2009-07-13 Time 14:08 Sent To  
Notes
2009-07-13 14:50:28*****APPROVED*****
  
 THE COMMENTS FORMO THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS LS-1, A-1, A-3, A-4, E-2.1,
 E-2.2, E-4.1, E-4.2, E-8, FS-1, FS-2.1, FS-2.2, AND
 FS-3 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-02 Cont ID  
Sent By mawillia Date 2009-06-02 Time 16:13 Rev Time 0.00
Received By mawillia Date 2009-06-02 Time 15:13 Sent To  
Notes
2009-06-02 16:13:20*****DENIED*****
  
 1. PROVIDE A POINT OF COMPASS FOR THE FLOOR PLAN SO AS
 IT RELATES TO PALM BEACH LAKES BOULEVARD.
  
 2.. ON SHEET A-4, INDICATE FIRE-RATED DOORS. BE ADVISED
 THAT FIRE-RATED DOORS AND ASSEMBLIES SHALL COMPLY WITH
 NFPA 80 - 1999 EDITION.
  
 3. ON SHEET E-8, FIRE ALARM NOTES, AMEND NOTE #7 TO
 INDICATE THAT: DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.
  
 4. ON SHEET FS-1, UNDER FIRE SPRINKLER NOTES
 -COMPLIANCE, CODE EDITIONS AS FOLLOWS: NFPA 13 - 2002,
 NFPA 13R - 2002, NFPA 14 - 2003, NFPA 20 - 2003, AND
 NFPA 25 - 2002 SHALL BE REFERENCED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EASCH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-11-19 Cont ID  
Sent By kstevens Date 2009-11-19 Time 08:59 Rev Time 0.00
Received By kstevens Date 2009-11-19 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-11-02 Cont ID  
Sent By lmartine Date 2009-10-29 Time 16:07 Rev Time 0.00
Received By lmartine Date 2009-10-29 Time 16:07 Sent To  
Notes
2009-11-02 16:08:28IN MECHANICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-22 Cont ID  
Sent By kstevens Date 2009-10-22 Time 10:46 Rev Time 0.00
Received By kstevens Date 2009-10-22 Time 10:46 Sent To  
Notes
2009-10-22 10:47:13SENT TO FIRE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 08:15 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 08:15 Sent To P
Notes
2009-11-19 09:09:53SENT TO C-17
2009-07-24 08:15:56PLANS TO DW OFFICE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-02 Cont ID  
Sent By mawillia Date 2009-06-02 Time 15:13 Rev Time 0.00
Received By mawillia Date 2009-05-19 Time 10:42 Sent To  
Notes
2009-05-19 10:43:05TO COMMERCIAL BOX # C2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2009-11-10 Time 15:29 Sent To  
Notes
2009-11-10 15:33:10REVISED M-2.1, M2.2, M5, M7 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-08 Cont ID  
Sent By dwise Date 2009-07-08 Time 21:14 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 21:14 Sent To  
Notes
2009-07-08 21:17:08APPROVED WITH PROVISO: PROVIDE A PRODUCT APPROVAL FOR
 THE ROOFTOP EQUIPMENT STANDS AS SPECIFIED BY THE DESIGN
 PROFESSIONAL TO THE FIELD INSPECTOR AT THE TIME OF
 INSPECTION FOR INCLUSION IN THE CITY FILE. NO DEVIATION
 FROM THE SPECIFIED PRODUCT APPROVAL MAY BE ALLOWED WITH
 EXPRESS CONSENT OF BOTH THE DESIGN PROFESSIONAL AND THE
 CITY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-05-28 Cont ID  
Sent By dwise Date 2009-05-28 Time 17:43 Rev Time 0.00
Received By dwise Date 2009-05-28 Time 17:43 Sent To  
Notes
2009-05-28 17:44:491. SHEET M-3. KEY NOTE #4 CALLS FOR SCREEN AT DRYER
 EXHAUST OUTLET. SCREEN SHALL NOT BE INSTALLED AT DRYER
 EXHAUST DUCT TERMINATION IN ACCORDANCE WITH FBC-M
 504.4.
 2. SHEET M-5. OUTSIDE AIR CALCULATIONS REFERENCE ASHRAE
 62.1-2007. THIS IS NOT THE CORRECT REFERENCE STANDARD.
 PLEASE CONFIRM VENTILATION DESIGN IS IN COMPLIANCE WITH
 ASHRAE 62.1-2004 IN ACCORDANCE WITH FBC-M 403.4 AND
 FBC-M CHAPTER 15.
 3. SHEET M-7. PROVIDE AUXILIARY DRAIN PROTECTION. ON
 DOWN-FLOW UNITS AND ALL OTHER COILS THAT DO NOT HAVE A
 SECONDARY DRAIN AND DO NOT HAVE A MEANS TO INSTALL AN
 AUXILIARY DRAIN PAN, A WATER-LEVEL MONITORING DEVICE
 SHALL BE INSTALLED INSIDE THE PRIMARY DRAIN PAN IN
 ACCORDANCE WITH FBC-M 307.2.3.1.
 4. CONDENSING UNIT IS SHOWN ON A PRE-ENGINEERED A/C
 STAND. THIS IS DEFINED AS A STRUCTURAL COMPONENT IN
 ACCORDANCE WIT FAC RULE 9B-72. PROVIDE PRODUCT APPROVAL
 FOR THE STAND TO BE USED WITH INSTALLATION
 INSTRUCTIONS.
 5. SHEET M-7. RTU NOTE #7 CALLS FOR CONDENSATE DRAINS
 TO BE ROUTED TO THE NEAREST FLOOR DRAIN. CONDENSATE
 SHALL NOT DISCHARGE INTO THE SANITARY SEWER SYSTEM IN
 ACCORDANCE WITH CITY ORDINANCE. CONDENSATE PIPING SHALL
 BE DISCHARGED AS SHOWN ON SHEET P-4 IN ACCORDANCE WITH
 FBC-M 307.2.1.
 6. SHEET M-7. EQUIPMENT AND APPLIANCES THAT ARE EXPOSED
 TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES AS DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. PROVIDE MANUFACTURER???S DATA
 OR OTHER SUCH SUPPORTING DOCUMENTATION SHOWING RTUS,
 CONDENSERS AND ROOF CAPS ARE DESIGNED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
  
 PLEASE FEEL FREE TO CONTACT ME DURING NORMAL BUSINESS
 HOURS IF YOU HAVE ANY QUESTIONS ABOUT THIS REVIEW. I
 MAY BE REACHED AT 561-805-6650 OR BY EMAIL AT
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2010-01-13 Cont ID  
Sent By lwagner Date 2010-01-13 Time 12:27 Rev Time 0.00
Received By lwagner Date 2010-01-13 Time 12:17 Sent To  
Notes
2010-01-13 12:27:59REVISION OK

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-08-11 Cont ID  
Sent By lwagner Date 2009-08-11 Time 10:44 Rev Time 0.00
Received By lwagner Date 2009-08-11 Time 09:53 Sent To  
Notes
2009-08-11 10:45:44GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-07-08 Cont ID  
Sent By dwise Date 2009-07-08 Time 21:06 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 21:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-05-28 Cont ID  
Sent By dwise Date 2009-05-28 Time 17:42 Rev Time 0.00
Received By dwise Date 2009-05-28 Time 17:39 Sent To  
Notes
2009-05-28 17:43:181. SHEET LS-1:YOU MAY NOT SUBSTITUTE WATER COOLERS OR
 BOTTLED WATER DISPENSERS FOR MORE THAN 50% OF THE
 REQUIRED DRINKING FOUNTAINS. 410.1 APPROVAL. DRINKING
 FOUNTAINS SHALL CONFORM TO ASME A112.19.1M, ASME
 A112.19.2M OR ASME A112.19.9M AND WATER COOLERS SHALL
 CONFORM TO ARI 1010. DRINKING FOUNTAINS AND WATER
 COOLERS SHALL CONFORM TO NSF 61, SECTION 9. WHERE WATER
 IS SERVED IN RESTAURANTS, DRINKING FOUNTAINS SHALL NOT
 BE REQUIRED. IN OTHER OCCUPANCIES, WHERE DRINKING
 FOUNTAINS ARE REQUIRED, WATER COOLERS OR BOTTLED WATER
 DISPENSERS SHALL BE PERMITTED TO BE SUBSTITUTED FOR NOT
 MORE THAN 50 PERCENT OF THE REQUIRED DRINKING
 FOUNTAINS.
  
 2. IN ADDITION TO THE REQUIREMENTS LISTED ABOVE IN ITEM
 1 BOTH OF THESE REQUIRED FACILITIES MUST COMPLY WITH
 SECTION 11-4.15:
 11-4.15.1 MINIMUM NUMBER. DRINKING FOUNTAINS OR WATER
 COOLERS REQUIRED TO BE ACCESSIBLE BY SECTION 11-4.1
 SHALL COMPLY WITH SECTION 11-4.15.
 11-4.15.2 SPOUT HEIGHT. SPOUTS SHALL BE NO HIGHER THAN
 36 INCHES (915 MM), MEASURED FROM THE FLOOR OR GROUND
 SURFACES TO THE SPOUT OUTLET [SEE FIGURE 27(A)].
 11-4.15.3 SPOUT LOCATION. THE SPOUTS OF DRINKING
 FOUNTAINS AND WATER COOLERS SHALL BE AT THE FRONT OF
 THE UNIT AND SHALL DIRECT THE WATER FLOW IN A
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO THE
 FRONT OF THE UNIT. THE SPOUT SHALL PROVIDE A FLOW OF
 WATER AT LEAST 4 INCHES (102 MM) HIGH SO AS TO ALLOW
 THE INSERTION OF A CUP OR GLASS UNDER THE FLOW OF
 WATER. ON AN ACCESSIBLE DRINKING FOUNTAIN WITH A ROUND
 OR OVAL BOWL, THE SPOUT MUST BE POSITIONED SO THE FLOW
 OF WATER IS WITHIN 3 INCHES (76 MM) OF THE FRONT EDGE
 OF THE FOUNTAIN.
 11-4.15.4 CONTROLS. CONTROLS SHALL COMPLY WITH SECTION
 11-4.27.4. UNIT CONTROLS SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR THE FRONT EDGE.
 11-4.15.5 CLEARANCES.
 (1) WALL- AND POST-MOUNTED CANTILEVERED UNITS SHALL
 HAVE A CLEAR KNEE SPACE BETWEEN THE BOTTOM OF THE APRON
 AND THE FLOOR OR GROUND AT LEAST 27 INCHES (685 MM)
 HIGH, 30 INCHES (760 MM) WIDE, AND 17 INCHES TO 19
 INCHES (430 MM TO 485 MM) DEEP [SEE FIGURE 27(A) AND
 FIGURE 27(B)]. SUCH UNITS SHALL ALSO HAVE A MINIMUM
 CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) TO ALLOW A PERSON IN A WHEELCHAIR TO APPROACH
 THE UNIT FACING FORWARD.
 (2) FREE-STANDING OR BUILT-IN UNITS NOT HAVING A CLEAR
 SPACE UNDER THEM SHALL HAVE A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) THAT
 ALLOWS A PERSON IN A WHEELCHAIR TO MAKE A PARALLEL
 APPROACH TO THE UNIT [SEE FIGURE 27(C) AND FIGURE
 27(D)]. THIS CLEAR FLOOR SPACE SHALL COMPLY WITH
 SECTION 11-4.2.4.
  
 3. SHEET LS-1 THE REQUIRED NUMBER OF FIXTURES HAS BEEN
 INCORRECTLY STATED IN THE FIXTURE TABULATION. 403.3
 NUMBER OF OCCUPANTS OF EACH SEX. THE REQUIRED WATER
 CLOSETS, LAVATORIES, AND SHOWERS OR BATHTUBS SHALL BE
 DISTRIBUTED EQUALLY BETWEEN THE SEXES BASED ON THE
 PERCENTAGE OF EACH SEX ANTICIPATED IN THE OCCUPANT
 LOAD. THE OCCUPANT LOAD SHALL BE COMPOSED OF 50 PERCENT
 OF EACH SEX, UNLESS STATISTICAL DATA APPROVED BY THE
 CODE OFFICIAL INDICATE A DIFFERENT DISTRIBUTION OF THE
 SEXES (SEE ALSO SECTION 403.1.1).THE TOTAL NUMBER OF
 OCCUPANTS IS 167. THE OCCUPANT LOAD FOR EACH SEX IS
 THEREFORE 84. UTILIZING TABLE 403.1 THIS REQUIRES:
 WATER CLOSETS 3 MALE, 3 FEMALE; LAVATORIES 3 MALE, 3
 FEMALE. YOU MAY NOT UNDERSTATE THE REQUIRED NUMBER OF
 FIXTURES EVEN THOUGH YOU HAVE PROPOSED TO CONSTRUCT
 MORE THAN THE MINIMUM REQUIRED.
  
 4. SHEET LS-1 THERE IS A CITED A CODE REFERENCE WHICH
 DOES NOT EXIST OR DOES NOT APPLY TO THIS PROJECT (403.2
 01 FPC EXCEPTION 2), AND CLAIMED AN ALTERNATE EXEMPTION
 (FBC 104.11) TO THE REQUIRED NUMBER OF DRINKING
 FOUNTAINS WHICH DIRECTLY CONTRADICTS SECTION 410.1 OF
 THE PLUMBING CODE.
  
 5. SHEET A-6 DETAIL 1. A FOLDING DOOR IS SHOWN WHICH
 ENCROACHES ON THE REQUIRED CLEAR FLOOR SPACE FOR THE
 WATER CLOSET IN VIOLATION OF 11-4.22.2(1). ALTHOUGH YOU
 HAVE PROVIDED AN ???EXTRA??? TOILET ROOM IN THE
 FACILITY, YOU HAVE CALLED THIS ONE OUT AS AN
 ???EMPLOYEE RESTROOM???. AS, SUCH IT MUST COMPLY WITH
 THE REFERENCED SECTION.
  
 PLEASE FEEL FREE TO CONTACT ME DURING NORMAL BUSINESS
 HOURS IF YOU HAVE ANY QUESTIONS ABOUT THIS REVIEW. I
 MAY BE REACHED AT 561-805-6650 OR BY EMAIL AT
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-07-16 Cont ID  
Sent By eschneid Date 2009-07-16 Time 11:57 Rev Time 0.25
Received By eschneid Date 2009-07-16 Time 11:57 Sent To  
Notes
2009-07-16 11:59:53PASSED W/PROVISOS
  
 1) A PERMIT FOR THE LANDSCAPE AND SITE IMPROVEMENTS
 SHALL BE SUBMITTED PRIOR TO THE INTERIOR BUILDING
 FRAMING INSPECTION.
  
 2) THE LANDSCAPE AND SITE IMPROVEMENTS SHALL BE
 COMPLETED AND A FINAL INSPECTION PASSED PRIOR THE C.O.
 FOR THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 2 Status F Date 2009-07-15 Cont ID  
Sent By eschneid Date 2009-07-15 Time 14:37 Rev Time 0.25
Received By eschneid Date 2009-07-15 Time 14:37 Sent To  
Notes
2009-07-15 14:38:18FAILED
  
 COMMENTS FROM THE MAY 28, 2009 REVIEW HAVE NOT BEEN
 ADDRESSED.
  
 1) THE ZONING AND LAND DEVELOPMENT REGULATIONS REQUIRE
 THAT IF RENOVATIONS TO A BUILDING EXCEED 50% OF THE
 VALUE OF THE BUILDING, THEN THE SITE SHALL BE BROUGHT
 INTO CONFORMITY WITH THE CITY'S LANDSCAPE REGULATIONS.
  
 2) THE PALM BEACH COUNTY PROPERTY APPRAISER VALUES THE
 BUILDING AT $753,490. THE VALUE OF THIS PERMIT
 ($600,000) PLUS THE VALUE OF THE INTERIOR DEMOLITION
 PERMIT ($15,000) TOTALS $615,000. THEREFORE, THE
 RENOVATIONS EXCEED 50% OF THE VALUE OF THE BUILDING AND
 THE SITE SHALL BE BROUGHT INTO CONFORMITY WITH ARTICLE
 XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS. A
 LANDSCAPE PLAN, PREPARED BY A FLORIDA REGISTERED
 LANDSCAPE ARCHITECT, IS REQUIRED AS PART OF THIS
 PERMIT, OR AS PART OF A SEPARATE SITE WORK PERMIT,
 PRIOR TO ZONING APPROVING THE RENOVATION PERMIT. ALL
 REQUIRED LANDSCAPE WORK, TO INCLUDE IRRIGATION, SHALL
 BE COMPLETED PRIOR TO THE CERTIFICATE OF OCCUPANCY IS
 ISSUED FOR THE BUILDING RENOVATIONS INCLUDED AS PART OF
 THIS PERMIT.
  
 3) NOTE: THE LANDSCAPE REQUIREMENT CITED ABOVE DOES NOT
 APPLY IF A CURRENT CERTIFIED APPRAISAL OF THE BUILDING
 AT 2007 PALM BEACH LAKES BOULEVARD, SHOWING THE VALUE
 IN EXCESS OF $1,230,000, IS PROVIDED AS PART OF THE
 PERMIT RESUBMITTAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-05-28 Cont ID  
Sent By eschneid Date 2009-05-28 Time 13:59 Rev Time 0.75
Received By eschneid Date 2009-05-28 Time 13:59 Sent To  
Notes
2009-05-28 15:21:06FAILED
  
 THE ZONING AND LAND DEVELOPMENT REGULATIONS REQUIRE
 THAT IF RENOVATIONS TO A BUILDING EXCEED 50% OF THE
 VALUE OF THE BUILDING, THEN THE SITE SHALL BE BROUGHT
 INTO CONFORMITY WITH THE CITY'S LANDSCAPE REGULATIONS.
  
 THE PALM BEACH COUNTY PROPERTY APPRAISER VALUES THE
 BUILDING AT $753,490. THE VALUE OF THIS PERMIT
 ($600,000) PLUS THE VALUE OF THE INTERIOR DEMOLITION
 PERMIT ($15,000) TOTALS $615,000. THEREFORE, THE
 RENOVATIONS EXCEED 50% OF THE VALUE OF THE BUILDING AND
 THE SITE SHALL BE BROUGHT INTO CONFORMITY WITH ARTICLE
 XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS. A
 LANDSCAPE PLAN, PREPARED BY A FLORIDA REGISTERED
 LANDSCAPE ARCHITECT, IS REQUIRED AS PART OF THIS
 PERMIT, OR AS PART OF A SEPARATE SITE WORK PERMIT. ALL
 REQUIRED LANDSCAPE WORK, TO INCLUDE IRRIGATION, SHALL
 BE COMPLETED PRIOR TO THE CERTIFICATE OF OCCUPANCY IS
 ISSUED FOR THE BUILDING RENOVATIONS INCLUDED AS PART OF
 THIS PERMIT.
  
 NOTE: THE LANDSCAPE REQUIREMENT CITED ABOVE DOES NOT
 APPLY IF A CURRENT CERTIFIED APPRAISAL OF THE BUILDING
 AT 2007 PALM BEACH LAKES BOULEVARD, SHOWING THE VALUE
 IN EXCESS OF $1,230,000, IS PROVIDED AS PART OF THE
 PERMIT RESUBMITTAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  