Plan Review Details - Permit 09050228
Plan Review Stops For Permit 09050228
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-19 Cont ID  
Sent By jgomez Date 2009-05-19 Time 15:30 Rev Time 0.00
Received By jgomez Date 2009-05-19 Time 15:30 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-05-14 Cont ID  
Sent By jgomez Date 2009-05-14 Time 11:53 Rev Time 0.00
Received By jgomez Date 2009-05-14 Time 11:53 Sent To PC
Notes
2009-05-14 13:04:03RESIDENTIAL (R3) RE-ROOFING, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- ENGINEER NEEDS TO REVISE RAS 117 CALCULATIONS.
 SELECTED FLAT ROOF ASSEMBLY ON NOA 08-0226.06 CALLS FOR
 THREE ROWS OF NAILS IN THE CENTER OF SHEET FOR ROOF
 ZONE 1. ENGINEER SPECIFIES TWO ROWS OF NAILS FOR ROOF
 ZONE 1. ENGINEER CAN'T REDUCE THE NUMBER OF NAILS.
 REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-12 Cont ID  
Sent By jgomez Date 2009-05-12 Time 17:07 Rev Time 0.00
Received By jgomez Date 2009-05-12 Time 17:07 Sent To PC
Notes
2009-05-12 17:08:44RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- ENGINEER TO REVISE RAS 117 CALCULATIONS:
 A) BUILDING IS LOCATED ON EXPOSURE "C" NOT "B" AS
 REQUIRED BY 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE. REVISE CALCULATED DESIGN PRESSURES
 ACCORDINGLY. SEE SECTIONS R301.2.1.4 THRU R301.2.1.4.2
 OF 2009 REVISIONS.
  
 B) NOA 06-0410.06 FILE IS CLOSED BY MIAMI-DADE COUNTY
 PRODUCT APPROVAL DIVISION. SEE ATTACHED COPY FROM DADE
 COUNTY WEBSITE. NEED TO PROVIDE CURRENT PRODUCT
 APPROVAL.
  
 2- FLAT ROOF PRODUCT APPROVAL FL1654 SUBMITTED ALSO
 REQUIRES CALCULATIONS FOR NAIL ENHANCING DONE BY A
 DESIGN PROFESSIONAL. SEE NOTE #6 OF THE NOTES THAT
 APPLY TO THE SELECTED SYSTEM. SEE ATTACHED COPY FROM
 FLORIDA PRODUCT APPROVAL FL1654-R4.
 **NOTE: USE EITHER THE FLORIDA PRODUCT APPROVAL OR
 CURRENT NOA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-05-12 Cont ID  
Sent By mmiller Date 2009-05-12 Time 11:39 Rev Time 0.00
Received By mmiller Date 2009-05-12 Time 11:39 Sent To  
Notes
2009-05-12 11:39:42APPROVED PER JILLIAN PAPA MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-12 Cont ID  
Sent By jgomez Date 2009-05-12 Time 17:08 Rev Time 0.00
Received By jgomez Date 2009-05-12 Time 17:07 Sent To  
Notes
***NONE***