Plan Review Details - Permit 09050198
Plan Review Stops For Permit 09050198
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-14 Cont ID  
Sent By jwitmer Date 2009-07-14 Time 13:17 Rev Time 0.55
Received By jwitmer Date 2009-07-14 Time 13:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-29 Cont ID  
Sent By jwitmer Date 2009-05-29 Time 13:12 Rev Time 0.77
Received By jwitmer Date 2009-05-29 Time 13:12 Sent To  
Notes
2009-05-29 13:57:24BUILDING PLAN REVIEW
 PERMIT: 09050198
 ADD: 1617 N FLAGLER DR, SUITE UP02
 CONT: EMPIRE DEVELOPMENT SYSTEMS
 TEL: (954)464-9168
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009, 2007 EXISTING BUILDING CODE WITH
 2009 SUPPLEMENTS, THIS REMODEL IS CONSIDERED A LEVEL
 TWO RECONFIGURATION OF WALLS AND SSYTEMS. 2007 EXISTING
 BUILDING CODE 404.1 SCOPE. LEVEL 2 ALTERATIONS INCLUDE
 THE RECONFIGURATION OF SPACE, THE ADDITION OR
 ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION
 OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT. PLEASE UPDATE PLANS.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5,
 TABLE 503, CHAPTER 6, & TABLE 601.
  
 3) SHEET 3.1 CEILING DETAIL INDICATES THE USE OF HI-HAT
 FURRING BUT FAILS TO INDICATE ATTACHMENT TO THE
 CONCRETE DECK ABOVESIZE OF FASTENER NOR THE SPACING OF
 FASTENER.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 4) ALL NEW WORK MUST COMPLY WITH THE FLORIDA BUILDING
 CODE, BUILDING, PLEASE REVIEW REQUIREMENTS FOR FLOOR
 SOUND INSULATION. 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-08-19 Cont ID  
Sent By dpalmer Date 2009-08-19 Time 09:35 Rev Time 0.00
Received By dpalmer Date 2009-08-19 Time 09:35 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-03 Cont ID  
Sent By dpalmer Date 2009-07-03 Time 08:24 Rev Time 0.00
Received By dpalmer Date 2009-07-03 Time 08:24 Sent To  
Notes
2009-07-03 08:25:09 
 ** DENIED 2ND REVIEW **
  
 1) NOTE: PLANS SUBMITTED DO NOT CONTAIN ANY DESIGN
 PROFESSIONAL SIGNED, DATED OR SEALED ON ELECTRICAL
 PLANS. PLEASE SEE 481.229, 471.003. PLANS ARE FOR A
 COMMERCIAL HIGH-RISE MUST MEET THESE SECTIONS.
  
 2) NOTE: PLEASE SEE BEDRM #2 WHICH STILL HAS MISSING
 RECEPTACLE REQUIRED PER 210.52 FOR 2FT OR MORE OF WALL
 SPACE.
  
 3) NOTE: PREVIOUS NOTES WITH RESPECT TO THE REQUIRED
 CIRCUITING AND SMALL APPLIANCE CIRCUITS FOR KITCHEN,
 DINING AND AREAS OF THE LIKE. THE PLANS NOW INDICATE
 ONLY ONE SMALL APPLIANCE CIRCUIT FOR THE ENTIRE
 KITCHEN. TWO ARE REQUIRED AT A MINIMUM. AT THE TIME
 THIS BUILDING WAS CONSTRUCTED THESE UNITS HAD TWO SMALL
 APPLIANCE CIRCUITS AT A MINIMUM NOW ONLY SHOWS ONE IN
 KITCHEN.
 210.52B1, 210.11C1, 220.52
  
 4) NOTE: PANEL SCHEDULE STILL INDICATES TWO WATER
 HEATERS HOWEVER NONE ARE SHOWN ON PLANS. PLEASE KNOW
 THAT ALL CONTINUOUS LOADS SHALL BE BASED AT 125%.
 422.13
 WHEN SHOWING THESE ITEMS ON PLANS, PLEASE BE SURE TO
 INCLUDE THE NEW OR EXISTING DISCONNECTS PER 422.30,31
 ETC
  
 5) NOTE: NOTES ON PLANS MENTION TO WIRE SMOKE ALARMS TO
 EXISTING FIRE ALARM SYSTEM. PLEASE CHECK WITH THE FIRE
 MARSHAL AS UNIT SINGLE STATION DEVICES SHOULD NOT BE
 CONNECTED TO BASE BUILDING. IT MAY BE A TROUBLE SIGNAL
 OF SOME TYPE. PLEASE CHECK WITH FIRE PLAN REVIEW.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-22 Cont ID  
Sent By dpalmer Date 2009-05-22 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2009-05-22 Time 08:47 Sent To  
Notes
2009-05-22 08:47:22**DENIED **
  
 1) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS PER
 MINIMUM CODE REQUIREMENTS.
 PLEASE SEE DINING, BREAKFAST AREAS AND AREA OF THE LIKE
 PER 210.52B1 ARE REQUIRED TO BE ON ONE OR MORE OF THE
 SMALL APPLIANCE CIRCUITS. THE CIRCUIT IN ONE OF THESE
 AREAS IS SHOWN AS CIRCUIT #17 WHICH IS A BEDROOM ARC
 FAULT CIRCUIT WHICH IS NOT PERMITTED.
 ANOTHER WOULD BE THE SMOKE ALARMS. PLEASE ALSO SEE
 210.12 FOR REQUIRED ARC FAULT PROTECTION.
 PLEASE ALSO BE SURE TO SEE OTHER CIRCUITS ON PANEL
 SCHEDULE WHICH DO NOT GO TO ANYTHING. 408.4.
  
 2) NOTE: PLANS APPEAR TO HAVE LIGHT LOCATIONS WHICH ARE
 SWITCHED FROM MORE THAN ONE LOCATION HOWEVER THE
 SWITCHES ARE NOT SHOWN AS 3-WAYS. PLEASE ADJUST. NEC
 300.
 FBC 106.1.1
  
 3) NOTE: PLEASE SEE 422.13 FOR STORAGE TYPE WATER
 HEATERS WHICH REQUIRES LOAD TO BE FIGURED AT 125%.
  
 4) NOTE: PLEASE BE SURE THE PLANS STATE THE FOLLOWING
 CODES AT A MINIMUM.
 2002 NFPA-72
 2007 FBC W/ 2009 REVISIONS
  
 5) NOTE: PLEASE SEE 210.52 FOR RECEPTACLES SPACING.
 THERE ARE SEVERAL LOCATIONS IN WHICH RECEPTACLES ARE
 REQUIRED. SOME NEED TO BE ADDED AND SOME NEED TO BE
 RELOCATED IN ORDER TO BE CODE COMPLIANT.
  
 6) NOTE: PLEASE SEE 210.11C1, AND 220.52 FOR REQUIRED
 LOAD TO BE FIGURED FOR THE ONE OR MORE SMALL APPLIANCE
 CIRCUITS. THIS IS RELEVANT TO THE COMMENT NUMBER ONE
 ABOVE. WHEN YOU HAVE MORE THAN TWO SMALL APPLIANCE
 CIRCUITS FOR DINING ROOMS, AREAS LIKE BREAKFAST AREAS
 AND THE LIKE, EACH ONE REQUIRES 1500 VA FOR EACH.
  
 7) NOTE: PLEASE SEE 210.11C3 FOR RECEPTACLE MISSING
 ALONG KITCHEN COUNTER SPACE. PLEASE ALSO SEE 210.8A6
 FOR REQUIRED GFCI PROTECTION.
  
 * IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-08-12 Cont ID  
Sent By mawillia Date 2009-08-12 Time 13:08 Rev Time 0.00
Received By mawillia Date 2009-08-12 Time 12:26 Sent To E
Notes
2009-08-12 12:27:49*****APPROVED*****
  
 PLAN SHEETS 2.1 AND 4.1 WERE STAMPED, INITIALED, AND
 DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-07-06 Cont ID  
Sent By mawillia Date 2009-07-06 Time 15:09 Rev Time 0.00
Received By mawillia Date 2009-07-06 Time 14:40 Sent To  
Notes
2009-07-06 14:58:21*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; THE APPROPIATE PLAN SHEETS (2.1 & 4.1)
 SHALL BE FIRE-STAMPED WHEN THE OTHER REVIEWERS' AS WELL
 AS THE FOLLOWING COMMENT HAS BEEN SATISFIED: IN
 REFERENCE TO NOTE #3 ON SHEET 4.1, PLEASE BE ADVISED
 THAT SMOKE ALARMS SHALL SOUND ONLY WITHIN AN INDIVIDUAL
 DWELLING UNIT AND SHALL NOT ACTUATE THE BUILDING FIRE
 ALARM SYSTEM (UNLESS OTHERWISE PERMITTED BY WEST PALM
 BEACH FIRE PREVENTION).
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-05-26 Cont ID  
Sent By mawillia Date 2009-05-26 Time 10:38 Rev Time 0.00
Received By mawillia Date 2009-05-26 Time 09:35 Sent To  
Notes
2009-05-26 10:38:18*****DENIED*****
  
  
 1. STRUCTURES UNDERGGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. LIFE SAFETY TO COMPLY WITH NFPA 101 - 2006 EDITION
 WHICH HAS BEEN IN EFFECT SINCE DECEMBER 31ST, 2008.
  
 3. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-10 Cont ID  
Sent By lmartine Date 2009-07-22 Time 13:17 Rev Time 0.00
Received By lmartine Date 2009-07-22 Time 13:18 Sent To  
Notes
2009-08-10 13:17:38GAVE TO BILL T.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-19 Cont ID  
Sent By btrobaug Date 2009-06-19 Time 15:10 Rev Time 0.00
Received By btrobaug Date 2009-06-19 Time 15:10 Sent To  
Notes
2009-06-19 15:11:48 
  
 TO # B-1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-17 Cont ID  
Sent By kstevens Date 2009-06-17 Time 09:10 Rev Time 0.00
Received By kstevens Date 2009-05-11 Time 15:08 Sent To  
Notes
2009-05-13 15:20:13B-21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-13 Cont ID  
Sent By rregueir Date 2009-07-13 Time 15:17 Rev Time 0.00
Received By rregueir Date 2009-07-13 Time 15:17 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-08 Cont ID  
Sent By rregueir Date 2009-06-08 Time 09:35 Rev Time 0.00
Received By rregueir Date 2009-06-08 Time 09:24 Sent To  
Notes
2009-06-08 09:35:41MECH SCOPE OF WORK OK. HOWEVER, PLANS (PROJECT DATA
 TABLE ON PG 2.1) NEED TO BE UPDATED TO REFLECT THE CODE
 IN EFFECT AT TIME OF PERMIT APPLICATION. THE 2007 FBC
 W/ 2009 SUPPLEMENT IS IN EFFECT AS OF MARCH 1, 2009.
 ALSO, THE LEVEL OF ALTERATION AS STATED IN THE PROJECT
 DATA TABLE IS INCORRECT. THE PROPOSED SCOPE OF WORK
 CONSTITUTES A LEVEL 2 ALTERATION AS IT INVOLVES A
 RECONFIGURATION OF SPACE. SEE FBC-EB SECTION 404.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-06-17 Cont ID  
Sent By kstevens Date 2009-06-17 Time 08:58 Rev Time 0.00
Received By kstevens Date 2009-06-17 Time 08:58 Sent To  
Notes
2009-06-17 09:10:27BATHROOM PLUMBING FIXTURE CHANGE OUT ONLY. PLUMBING
 PERMIT REQUIRED.