Plan Review Details - Permit 09050151
Plan Review Stops For Permit 09050151
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-22 Cont ID  
Sent By rmcdouga Date 2009-06-22 Time 14:59 Rev Time 0.00
Received By rmcdouga Date 2009-06-22 Time 14:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-16 Cont ID  
Sent By btrobaug Date 2009-06-16 Time 8:05 Rev Time 0.00
Received By rmcdouga Date 2009-06-16 Time 08:05 Sent To  
Notes
2009-06-16 08:21:352007 FBC
 INSTALL GENERATOR
  
 DENIED BY BUILDING
  
 1) THE ENGINEERING CALCULATIONS AND PAD ANCHORING
 DRAWINGS FROM HILLMAN ENGINEERING INC. ARE REQUIRED TO
 HAVE THE ENGINEERS ORIGINAL SIGNATURE AND RAISED SEAL.
 FS 471.025
  
 2) THE CALCULATIONS FOR WIND LOAD REFERENCE THE 2004
 FLORIDA BUILDING CODE AND ASCE 7-02. THE 2007 FLORIDA
 BUILDING CODE WENT INTO EFFECT ON MARCH 1,2009 AND ASCE
 7-05 IS THE DESIGN STANDARD REFERENCED. PLEASE UP DATE
 ENGINEERING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-05-28 Cont ID  
Sent By mcruz Date 2009-05-28 Time 14:11 Rev Time 0.00
Received By btrobaug Date 2009-05-27 Time 10:32 Sent To M
Notes
2009-05-27 10:49:20 
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-06-12 Cont ID  
Sent By kstevens Date 2009-06-12 Time 15:01 Rev Time 0.00
Received By kstevens Date 2009-06-12 Time 15:01 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-06-10 Cont ID  
Sent By kstevens Date 2009-06-10 Time 09:36 Rev Time 0.00
Received By kstevens Date 2009-06-10 Time 09:36 Sent To  
Notes
2009-06-10 09:56:16DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. -- SHOW THE GAS PIPING FROM THE METER TO
 THE TEE FOR THE GENERATOR. INDICATE MATERIAL FROM THE
 METER TO THE TEE FOR THE GENERATOR AND THE PIPE SIZE.
  
 2. TYPE OF GAS, (LP OR NATURAL).
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-16 Cont ID  
Sent By rmcdouga Date 2009-06-16 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2009-05-07 Time 15:01 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-06-16 Cont ID  
Sent By btrobaug Date 2009-06-16 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2009-06-16 Time 08:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-05-28 Cont ID  
Sent By rmcdouga Date 2009-06-16 Time 08:07 Rev Time 0.00
Received By mcruz Date 2009-05-18 Time 15:19 Sent To E
Notes
***NONE***