Plan Review Details - Permit 09050076
Plan Review Stops For Permit 09050076
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-08-05 Cont ID  
Sent By shill Date 2009-08-05 Time 08:37 Rev Time 0.00
Received By shill Date 2009-08-05 Time 08:37 Sent To  
Notes
2009-08-05 08:38:43PASSED W/REDLINE/PROVISO
  
 FABRIC SHIELD, OPENINGS >60" REQUIRE 10" ANCHOR SPACING
 SEE OPENING #3
  
 SPANS ON INSTALLATION SCHEDULE INCORRECT BUT ANCHOR
 SPACING COMPLIANT (SEE ATTACHED, DREW SKETCH FOR
 CONTRACTOR TO DEMONSTRATE)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 22:20 Rev Time 0.00
Received By shill Date 2009-07-22 Time 22:20 Sent To  
Notes
2009-07-22 22:25:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE EVIDENCE THAT THIS PROPERTY IS
 GREATER THAN 1500' FROM THE INTERCOASTAL. THE
 CONTRACTOR PROVIDED A STATEMENT THAT THE PROPERTY IS
 GREATER THAN 1500', AND THE PERMIT WAS ISSUED BASED ON
 THAT STATEMENT. HOWEVER, MEASUREMENTS PROVIDED BY OUR
 GIS SHOWS THAT THIS PROPERTY IS APPROXIMATELY 1400'
 FROM THE INTERCOASTAL. ON WHAT INFORMATION DID THE
 CONTRACTOR BASE THAT STATEMENT? PLEASE PROVIDE EVIDENCE
 OF EXPOSURE B CONDITIONS OR REVISE INSTALLATION
 SCHEDULE FOR EXPOSURE C.
  
 2. OPENING 3 STATES THAT IT WILL BE INSTALLED
 HORIZONTALLY, THE HORIZONTAL DIMENSION (WXH) IS 95",
 BUT THE SPAN IS 40"? INFORMATION IS NOT CONSISTENT.
 THIS COMMENT APPLIES TO OTHER OPENINGS.
  
 3. SEE OPENINGS 1 AND 2, HOW CAN THE SPAN BE THE SAME
 AS THE OPENING SIZE WITH A WALL MOUNT AND A .75 EDGE
 DISTANCE? PLEASE EITHER EXPLAIN OR REVISE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-21 Cont ID  
Sent By lmartine Date 2009-05-21 Time 15:26 Rev Time 0.00
Received By lmartine Date 2009-05-21 Time 15:26 Sent To  
Notes
2009-05-21 15:26:44PASSED PER SAMANTHA

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-06 Cont ID  
Sent By shill Date 2009-05-06 Time 11:24 Rev Time 0.00
Received By shill Date 2009-05-06 Time 11:21 Sent To  
Notes
2009-05-06 11:21:51****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. OPENING 3, SPAN OF 101" REQUIRES USE OF 9' CHART (P
 2 OF FABRIC PRODUCT APPROVAL), 10" SPACING REQUIRED,
 INSTALLATION SCHEDULE PROPOSES 18". PLEASE REVISE AND
 CHECK ALL.
  
 2. PLEASE CONFIRM EXPOSURE B CONDITIONS. NOTE THAT THE
 DEFINITION OF EXPOSURE B HAS CHANGED; THIS PROPERTY
 MUST BE >1500' FROM INTRACOASTAL. SEE FBC1609, FBC R301
 (AND GLITCH AMENDMENTS 2009).
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-05-05 Cont ID  
Sent By mmiller Date 2009-05-05 Time 15:20 Rev Time 0.00
Received By mmiller Date 2009-05-05 Time 15:20 Sent To  
Notes
2009-05-05 15:21:02OK PER JILLIAN PAPA MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-22 Cont ID  
Sent By lmartine Date 2009-07-22 Time 16:23 Rev Time 0.00
Received By lmartine Date 2009-07-22 Time 16:22 Sent To  
Notes
2009-07-22 16:24:02GAVE TO SAM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-06 Cont ID  
Sent By shill Date 2009-05-06 Time 11:29 Rev Time 0.00
Received By shill Date 2009-05-06 Time 11:29 Sent To  
Notes
***NONE***