Plan Review Details - Permit 09050066
Plan Review Stops For Permit 09050066
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-12 Cont ID  
Sent By jwitmer Date 2009-06-12 Time 08:15 Rev Time 0.77
Received By jwitmer Date 2009-06-12 Time 07:30 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-15 Cont ID  
Sent By jwitmer Date 2009-05-15 Time 16:00 Rev Time 1.11
Received By jwitmer Date 2009-05-15 Time 15:00 Sent To  
Notes
2009-05-15 16:34:42BUILDING PLAN REVIEW
 PERMIT: 09050066
 ADD: 953 43RD ST
 CONT: GREY CONSTRUCTION
 TEL: (561-312-2766
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS, AND THE 2007
 EXISTING BUILDING CODE WITH 2009 SUPPLEMENTS. PLEASE
 UPDATE PLANS AND ALSO CHOOSE LEVEL OF ALTERATION.
 EXISTING BUILDING CODE. 401.4 A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF
 THIS CODE.
  
 2) PLANS ARE MISSING THE WIND INFORMATION: 2007
 EXISTING BUILDING CODE, 606.4 REPLACEMENT OF WINDOWS
 AND DOORS. THE REPLACEMENT OF GARAGE DOORS, EXTERIOR
 DOORS, SKYLIGHTS, OPERATIVE AND INOPERATIVE WINDOWS
 SHALL BE DESIGNED AND CONSTRUCTED TO COMPLY WITH
 CHAPTER 16 OF THE FLORIDA BUILDING CODE, BUILDING .
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) THE PLAN SUBMITTED FOR WINDOW REPLACEMENT IS NOT
 DRAWN TO SCALE IT CAN NOT BE DETERMINED WHICH WINDOWS
 ARE IN THE END ZONES AND WHICH ARE LOCATED WITH-IN THE
 INTERIOR ZONES, UNABLE TO DETERMINE PRESSURES.
  
 4) THE WINDOW FLOOR PLAN ALSO IS MISSING WINDOW SIZES,
 PLEASE PROVIDE WINDOW SIZES SO WINDOW OPENINGS CAN BE
 REVIEWED FOR THE ASSOCIATED PRESSURES. NOTE: EXISTING
 BUILDING CODE DOES ALLOW FOR A 5% REDUCTION IN CLEAR
 OPENING DIMENSIONS FOR THE REPLACEMENT OF WINDOWS SHALL
 BE ALLOWED.
  
 5) THE PERMIT APPLICATION INDICATES A VALUE OF
 $2,300.00 DOLLARS OF VALUE FOR PLUMBING, ELECTRICAL AND
 REPLACEMENT OF 9 WINDOWS, WHERE AS ON THE WINDOW PLAN
 THE VALUE ALONE FOR THE WINDOWS IS INDICATED AS $365.00
 EACH FOR A TOTAL OF $3,285.99. IT APPEARS THESE TWO
 FIGURESTHE PLUMBING /ELECTRIC AND WINDOWS SHOULD BE
 ADDED TOGETHER.
  
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-06-11 Cont ID  
Sent By dpalmer Date 2009-06-11 Time 08:16 Rev Time 0.00
Received By dpalmer Date 2009-06-11 Time 08:16 Sent To  
Notes
2009-06-11 08:16:13*** PROVISO ***
  
 1) NOTE: PROVIDE RISER DIAGRAM SHOWING NEW PANEL WITH
 ALL CONDUCTORS.
 PLEASE PROVIDE PANEL SCHEDULE FOR NEW PANEL SHOWING
 BREAKER AND CONDUCTOR SIZES.
 408.4, 240.4, 310.16 ETC
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-18 Cont ID  
Sent By dpalmer Date 2009-05-18 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2009-05-18 Time 14:02 Sent To  
Notes
2009-05-18 14:02:42**DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FBC R313 WHICH REQUIRES ALL SMOKE
 DETECTION SYSTEMS TO BE BROUGHT UP TO CURRENT CODES.
 11.5.1, 11.8.3. PLANS STATE SD AND NOTES FOR SMOKE
 DETECTORS.
 SMOKE DETECTORS ARE ONLY DEVICES WHICH DETECT AND DO
 NOT SOUND AN ALARM. IF THIS IS THE CASE PLEASE IDENTIFY
 THE HORN/SIREN DEVICE LOCATIONS. IF THESE ARE INDEED
 SMOKE ALARM DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLEASE ADJUST THE TYPE OF DEVICE IN NOTES AND ON PLANS.
 PLEASE ALSO SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION.
  
 ** PLEASE KEEP IN MIND IF THERE IS ANY GAS APPLIANCES
 OR ATTACHED GARAGE FS 553.885 REQUIRES CARBON MONOXIDE
 DETECTION.
  
  
 2) NOTE: PLANS STATE A NEW SERVICE HOWEVER NO RISER
 DIAGRAM WAS SUBMITTED FOR THE SIZE OF SERVICE,
 CONDUCTORS, GROUNDING , AIC RATINGS, ETC.
 110.9,250.50,310.16,310.15B6 ETC
 PLEASE SEE 2005 NEC
  
 3) NOTE: PLEASE SHOW LOCATION OF PANEL COMPARED TO
 KITCHEN COUNTER SPACE TO VERIFY 110.26
  
 4) NOTE: PLAN STATES TO REPLACE ALL STANDARD
 RECEPTACLES WITH GFI DEVICES. PLEASE EXPLAIN AND SHOW
 LOCATIONS.
 WHY ARE ALL DEVICES BEING CHANGED TO GFICI? 210.8A
  
 5) NOTE: VALUE FOR SCOPE OF WORK IS LOW.
 FBC 108.3
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcdouga Date 2009-06-04 Time 15:46 Sent To  
Notes
2009-06-04 15:47:29TO R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-05-18 Time   Rev Time 0.00
Received By dpalmer Date 2009-05-05 Time 16:49 Sent To  
Notes
2009-05-05 16:57:41TO R13

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-05-11 Cont ID  
Sent By kstevens Date 2009-05-11 Time 16:35 Rev Time 0.00
Received By kstevens Date 2009-05-11 Time 16:35 Sent To  
Notes
2009-05-11 16:36:43REPLACE ELECT. W/H, CHANGE TUB & SHOWER TRIM & REPAIR
 PIPES UNDER KITCHEN SINK.