Plan Review Details - Permit 09050021
Plan Review Stops For Permit 09050021
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-05-07 Cont ID  
Sent By jnguyen Date 2009-05-07 Time 09:28 Rev Time 0.00
Received By jnguyen Date 2009-05-07 Time 08:01 Sent To  
Notes
2009-05-07 09:15:50I TOOK A LOOK AT THE SITE PLANS DOWNSTAIRS WITH DEWEY.
 SINCE THIS PERMIT RELATED TO ELECTRICAL WORK FOR
 UNDERGROUND LIGHTING & PARKING LIGHT POLES, I ISSUED IT
 THE UNOFFICIAL & TEMPORARY ADDRESS OF 120 CLEARWATER DR
 (AS IT WON'T BE AN ACTUAL STRUCTURE RECEIVING MAIL THAT
 NEEDS TO BE VISIBLY LABELED). UNDER THIS PCN#
 74434321270010000, I CREATED THE SEQUENTIAL UNIT RECORD
 0002 - @ 120 CLEARWATER DR (@ MEANING THE ROUGH
 LOCATION). PLEASE MOVE & ATTACH THIS PERMIT TO THAT
 PARTICULAR RECORD IN COMMUNITYPLUS (AS I DO NOT HAVE
 AUTHORIZATION). ALSO, SOMEONE NEEDS TO MAKE THE
 ADJUSTMENT ON THE ORIGINAL PERMIT APPLICATION FROM 150
 TO 120 CLEARWATER DR, AS I WAS ONLY PROVIDED WITH A
 COPY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-07-03 Cont ID  
Sent By dpalmer Date 2009-07-03 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2009-07-03 Time 16:36 Sent To PC
Notes
2009-07-03 16:37:07REDLINED PLANS, GATES AND FENCE ARE NOT INCLUDED.
 SEPARATE PERMITS REQUIRED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-06-22 Cont ID  
Sent By dpalmer Date 2009-06-22 Time 14:59 Rev Time 0.00
Received By dpalmer Date 2009-06-22 Time 14:59 Sent To PC
Notes
2009-06-22 14:59:28 
 ** DENIED REVISIONS **
  
 1) NOTE: PLANS STILL SHOWS SYSTEMS FROM TWO SEPARATE
 LEGAL PROPERTIES AND OWNERS CROSSING ONTO ONE LOCATION.
 NONE OF THESE ITEMS WERE ON PREVIOUS PLANS.
 THE PLANS NOW INDICATE GATES WITH CONTROLS TO TRI-RAIL
 STATION. THIS WOULD ALSO HAVE ELECTRICAL EQUIPMENT WITH
 POWER FROM TWO SOURCES.
 PLEASE ALSO SEE 250 FOR SYSTEMS REQUIRED TO BE BONDED.
 250.90,250.92,250.94, ETC
 ARE THE GATES ALSO FED FROM THE LIGHTING CIRCUIT?
  
 2) NOTE: PLEASE KNOW THAT ANY ACCESS GATES AND FENCING
 SHALL BE UNDER SEPARATE PERMITS. PLEASE BE SURE TO
 CONTACT THE FIRE MARSHAL FOR ANY MINIMUM WIDTHS FOR
 FIRE VEHICLE EQUIPMENT. THESE WERE NOT ON PREVIOUS
 PLANS WHICH WERE RED LINED FOR UNDERGROUND CONDUITS
 ONLY.
 PLEASE BE SURE TO SUBMIT THE GATE OPERATOR SPEC SHEETS
 WHEN SUBMITTING FOR PERMIT. 110.3.
  
 3) NOTE: PLEASE CLARIFY THE CONDUCTORS TO THE SERVICE
 AND MAIN.
 RISER NOTES 3-#1 AND #8 G. IS THIS THE NEUTRAL/GROUNDED
 CONDUCTOR?
 NO EQUIPMENT GROUNDING BEFORE FIRST MEANS OF
 DISCONNECT. PLEASE SEE THAT THE RISER DOES NOT INDICATE
 LOCATION IN WHICH THE MINI-ZONE TRANSFORMER WILL BE
 GROUNDED PER 250.50,250.66,250.20,250.30
  
 4) NOTE: THE PANEL SCHEDULE FOR H AND RISER DOES NOT
 INDICATE THE CONDUCTORS FROM THE PANEL TO THE MINI-ZONE
 PANEL UNIT.
 310.16, 240.4
  
 5) NOTE: PLEASE SEE 450.3 AS THE MAXIMUM OVER CURRENT
 PROTECTION TO THE TRANSFORMER SHALL BE 125%.
 ( SEE NOTE #5) AS NOTED ON TABLE.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 TRANSFORMER. PLEASE BE SURE THE SPECS INDICATE A
 LISTING FROM A RECOGNIZED NRTL.
 110.3,90.7
  
 6) NOTE: PLEASE BE SURE THE ADOPTED RELEVANT CODES ARE
 STATED ON PLANS. THE PLANS STATE THE 2008 SFBC ( SOUTH
 FLORIDA BUILDING CODE). THE STATE OF FLORIDA IS UNDER
 THE FLORIDA BUILDING CODE PER FS 553.73. THIS WAS
 BEGINNING IN 2002.
  
 PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING CODES
 BASED ON THE PERMIT APPLICATION DATE.
 2007 FBC W/ 2009 REVISIONS.
 2005 NFPA-70 (NEC).
  
 7) NOTE: PLEASE REVISE THE COLOR CODING ON THE PLANS
 FOR THE 277/480V SYSTEM TO BROWN, PURPLE, AND YELLOW.
 THIS AHJ HAD LOCAL TECHNICAL AMENDMENTS FOR SEVERAL
 DECADES FOR COLOR CODING OF ELECTRICAL SYSTEMS AS THE
 NEC DID NOT PROVIDE COLOR CODING. THE NEC DOES USE THE
 COLOR OF ORANGE FOR OPEN DELTA HIGH LEG SYSTEM
 IDENTIFICATION. THE SYSTEM AS SHOWN ON PLANS IS NOT A
 HIGH-LEG SYSTEM. IN KEEPING WITH THE IDENTIFICATION OF
 OTHER SYSTEMS IN THIS JURISDICTION PLEASE ADJUST.
 90.4
 * CALL FOR QUESTIONS
  
 8) NOTE: PLEASE BE SURE THE ADDRESS FOR THE PROJECT IS
 LOCATED ON PLANS.
 THE ADDRESS WAS REDLINED ON PREVIOUS PLANS. 120
 CLEARWATER PK.
 FAC 61G15-23.002, FBC 106.5 FOR RECORD PLANS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-05-13 Cont ID  
Sent By dpalmer Date 2009-05-13 Time 11:19 Rev Time 0.00
Received By dpalmer Date 2009-05-13 Time 11:19 Sent To PC
Notes
2009-05-13 11:22:09PLANS ARE FOR UNDERGROUND ONLY. THE ELECTRICAL SERVICE
 WILL BE DONE UNDER SEPARATE PERMIT FOR SERVICE.
 PLANS REDLINED FOR UNDERGROND ONLY AND FOR CORRECTED
 ADDRESS OF 120 CLEARWATER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-06 Cont ID  
Sent By dpalmer Date 2009-05-06 Time 16:22 Rev Time 0.00
Received By dpalmer Date 2009-05-06 Time 16:23 Sent To PC
Notes
2009-05-06 16:23:03**DENIED PLANS**
  
  
  
 1) NOTE: PLANS WILL BE ROUTED TO ADDRESSING REVIEWER.
 THIS LOCATION AND PARKING LOT AREA NEEDS TO BE UNDER A
 SEPARATE ADDRESS FROM THE OTHER APPLIED BUS-STOP
 LOCATIONS.
 AN ADDRESS EXTENSION WILL BE DETERMINED. ONCE THIS IS
 DONE PLEASE BE SURE TO REVISE PLANS ACCORDINGLY.
 FAC 61G15-23.002
  
 2) NOTE: PLANS INDICATE THE ELECTRICAL BEING FED FROM A
 SEPARATE PROPERTY WHICH IS A COMPLETELY SEPARATE LEGAL
 OWNER AND SEPARATE LEGAL PROPERTY. THIS IS NOT
 PERMITTED. PLEASE CONTACT YOUR LOCAL LEGAL
 REPRESENTATIVE ALONG WITH THE CITY ATTORNEY FOR
 SPECIFIC LEGAL QUESTIONS.
  
 A SEPARATE ELECTRICAL SERVICE SUCH AS METER ON A
 FREE-STANDING RACK OR BEING FROM EXISTING PALM BEACH
 COUNTY ELECTRICAL ON THE SAME PROPERTY MAY BE AN
 OPTION.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH
 GROUND FOR ALL LIGHTING FIXTURES/POLES, SERVICE,
 FEEDERS, CONDUCTORS, OVER CURRENT PROTECTION ETC.
 CONTINUOUS
 215.5,230.70,230.71, 220,240, 310.16,ETC
  
 3) NOTE: PLEASE REVISE TITLE BLOCKS FOR ENGINEERING
 FIRM TO COORDINATE WITH DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. (DBPR). THE STATE WEBSITE
 LISTS ALL ADDRESSING ASSOCIATED WITH AECOM USA INC
 LOCATED IN NEW YORK.
 PLEASE REVISE.
 61G15-23.002, FS 471.023
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-01 Cont ID  
Sent By kstevens Date 2009-07-01 Time 10:38 Rev Time 0.00
Received By kstevens Date 2009-07-01 Time 10:38 Sent To  
Notes
2009-07-01 10:38:28TO DVP'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-11 Cont ID  
Sent By rregueir Date 2009-06-11 Time 13:53 Rev Time 0.00
Received By rregueir Date 2009-06-11 Time 13:53 Sent To E
Notes
2009-06-11 13:53:33TO DVP DESK