Plan Review Details - Permit 09040457
Plan Review Stops For Permit 09040457
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-08 Cont ID  
Sent By jgomez Date 2009-05-08 Time 14:36 Rev Time 0.00
Received By jgomez Date 2009-05-08 Time 14:36 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-28 Cont ID  
Sent By rmcdouga Date 2009-04-28 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2009-04-28 Time 10:11 Sent To  
Notes
2009-04-28 10:20:332007 FBC
 RE-ROOF
  
 DENIED BY BUILDING
  
 1) THE ENHANCED FASTENING SPECIFIED FOR THE CORNERS
 (ROOF ZONE 3) IS NOT ADEQUATE. THE ENGINEERING
 SPECIFIES 6"OC AT THE LAP AND TWO ROWS 6"OC IN THE
 FIELD, WHICH DOES NOT MEET THE -89 PSF UPLIFT THAT IS
 REQUIRED. CHECK RAS 117 CALCULATIONS.
  
 2) THE ENGINEERING REFERENCES THE 2004 FBC WITH 2007
 REVISIONS. THE 2007 FBC IS IN EFFECT AS OF MARCH 1,
 2009. ALSO THE 2007 FBC REFERENCES ASCE 7-05. PLEASE
 UPDATE SUBMITTALS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-21 Cont ID  
Sent By rmcdouga Date 2009-04-21 Time 13:13 Rev Time 0.00
Received By rmcdouga Date 2009-04-21 Time 13:13 Sent To  
Notes
2009-04-21 13:53:41****CORRECTIONS****
  
 ROBERT MCDOUGAL, BUILDING PLANS EXAMINER
 561-805-6714 [email protected]
  
 2007 FLORIDA BUILDING CODE &
 CITY OF WEST PALM BEACH AMENDMENTS TO THE 2007FBC
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____ 1.) EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER
 BARRIER REQUIRED FS 553.844(5)(A). PROVIDE INFORMATION
 (PRODUCT APPROVAL OR SPECIFICATIONS) TO SHOW HOW YOU
 WILL COMPLY WITH THIS REQUIREMENT. INFORMATION IS
 AVAILABLE AT WWW.BOAF.NET, HURRICANE MITIGATION.
  
 __X__ 2.) CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION: MEAN ROOF HEIGHT.
  
 ____ 3.) FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC RULE 9B-72. WWW.FLORIDABUILDING.ORG
  
 __X___ 4.) FOR THE FLAT ROOF, INDICATE WHICH ONE OF THE
 APPROVED ASSEMBLIES LISTED IN THE PRODUCT APPROVAL WILL
 BE INSTALLED. ALSO SPECIFY WHICH FASTENER AND DESIGN
 PRESSURE WILL BE USED.
  
 _____ 5.) FOR THE FLAT ROOF, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES. THIS IS TO BE
 SUBMITTED ON COMPANY LETTERHEAD, TWO SETS (NOT WRITTEN
 ON THE RE-SUB SHEET).
  
 ____ 6.) ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING. IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED. FAC RULE 9B-72
  
 __X__ 7.) SEE PRODUCT LIMITATION #7. SIGNED AND SEALED
 CALCULATIONS IN ACCORDANCE WITH RAS 117 PREPARED BY AN
 ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT ARE
 REQUIRED FOR ENHANCED FASTENING.
  
 THE VALUE OF THE PROJECT HAS BEEN ADJUSTED BASED ON
 MARSHALL AND SWIFT VALUATIONS ADDITIONAL FEES OF $13.57
 ARE DUE. FBC 108.3* CITY AMENDMENTS
  
 PROVISO: MECHANICAL EQUIPMENT TO COMPLY WITH FBC EB
 611, FBC 1509.7.
  
  
  
  