Plan Review Details - Permit 09040446
Plan Review Stops For Permit 09040446
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-07 Cont ID  
Sent By jwitmer Date 2009-05-07 Time 10:02 Rev Time 4.22
Received By jwitmer Date 2009-05-07 Time 08:48 Sent To  
Notes
2009-05-07 10:22:54BUILDING PLAN REVIEW
 PERMIT: 09040446
 ADD: 2013 DOCK ST.
 CONT: ABALON CONSTRUCTION
 TEL: (561)722-3890
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009. THREE UNIT STRUCTURE WILL BE
 REVIEWED UNDER THE 2007 FLORIDA BUILDING CODE, 2007
 FLORIDA EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS.
  
 1C) 2007 FBC 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. THE PLANS DO NOT
 INDICATE WHAT WALLS ARE ORIGINAL OR NEW CONSTRUCTION,
 PLEASE IDENTIFY. IN UNITS 2 & 3 THERE IS NO INFORMATION
 IF THERE IS NEW WORK, DISCUSSION WITH CORAL KEY DESIGN
 INDICATES THERE TO BE NO NEW WORK BUT THE FRONT
 ELEVATION INDICATES NEW WINDOWS IN UNIT TWO WHERE THE
 HEADERS ARE BEING REPLACED. PLEASE CORRELATE PLANS FOR
 CONSISTENCY.
  
 1D) CORAL KEY DESIGN CAN ONLY DESIGN A ONE & TWO FAMILY
 RESIDENCE AND NOT COMMERCIAL WORK. THE P.E. OF RECORD
 FOR THIS PROJECT H. JOHN GRIFFIN SHOULD ONLY HAVE HIS
 NAME IN THE TITLE-BLOCK.
 1E)THE STATED DOLLAR VALUE FOR THE SCOPE OF WORK
 INDICATED IN THE PLAN DOCUMENT IS TOO LOW. PLEASE
 UPDATE VALUE TO INCLUDE LABOR AND MATERIAL TO REFLECT A
 FAIR MARKET VALUE.
  
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) UNIT# 1, BEDROOM# 2 INDICATES THE WINDOW TO BE
 RELOCATED. FL EXIST. BLDG. CODE 701.2 ALTERATION LEVEL
 1 COMPLIANCE. IN ADDITION TO THE REQUIREMENTS OF THIS
 CHAPTER, ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 6. 606.4 REPLACEMENT OF WINDOWS AND DOORS. THE
 REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS, SKYLIGHTS,
 OPERATIVE AND INOPERATIVE WINDOWS SHALL BE DESIGNED AND
 CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF THE FLORIDA
 BUILDING CODE, BUILDING . PLEASE NOTE THE RELOCATED
 WINDOW WILL NEED DOCUMENTATION THAT IT MEETS THE
 CURRENT WIND PRESSURES. THE OTHER ISSUE IS TO IDENTIFY
 THROUGH-OUT THE BUILDING WHICH WINDOWS ARE GOING TO BE
 REPLACED.
  
 3) SHEET# 2 INDICATES PROPOSED STUCCO, OUR RECORDS
 INDICATE THIS TO BE A WOOD FRAME STRUCTURE WITH WOOD
 SIDING. PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 APPLICATION OF STUCCO. 2510.1 GENERAL. EXTERIOR AND
 INTERIOR CEMENT PLASTER AND LATHING SHALL BE DONE WITH
 THE APPROPRIATE MATERIALS.
  
 2510.3 INSTALLATION. INSTALLATION OF THESE MATERIALS
 SHALL BE IN COMPLIANCE WITH ASTM C 926 AND ASTM C 1063.
 1405.3 FLASHING. FLASHING SHALL BE INSTALLED IN SUCH A
 MANNER SO AS TO PREVENT MOISTURE FROM ENTERING THE WALL
 OR TO REDIRECT IT TO THE EXTERIOR. FLASHING SHALL BE
 INSTALLED AT THE PERIMETERS OF EXTERIOR DOOR AND WINDOW
 ASSEMBLIES, PENETRATIONS AND TERMINATIONS OF EXTERIOR
 WALL ASSEMBLIES
 1404.2 WATER-RESISTIVE BARRIER. EXTERIOR WALLS OF FRAME
 CONSTRUCTION RECEIVING A VENEER SHALL BE PROVIDED WITH
 A WATER-RESISTIVE BARRIER. THE WATER-RESISTIVE BARRIER
 SHALL BE A MINIMUM OF ONE LAYER OF NO. 15 ASPHALT FELT,
 COMPLYING WITH ASTM D 226 FOR TYPE 1 FELT OR OTHER
 APPROVED MATERIALS, SHALL BE ATTACHED TO THE SHEATHING,
 WITH FLASHING AS DESCRIBED IN SECTION 1405.3, IN SUCH A
 MANNER AS TO PROVIDE A CONTINUOUS WATER-RESISTIVE
 BARRIER BEHIND THE EXTERIOR WALL VENEER.
  
 1404.2.1 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED
 TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL BE
 TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER AND
 THE WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE
 PROVIDED BETWEEN THE WATER RESISTIVE BARRIER AND THE
 CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE
 FOLLOWING:
  
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER OR
  
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP, OR
  
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-01 Cont ID  
Sent By btrobaug Date 2009-05-01 Time 11:02 Rev Time 0.00
Received By btrobaug Date 2009-05-01 Time 08:29 Sent To  
Notes
2009-05-01 09:58:16 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A), 230.70 GENERAL.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS.
 THE AHJ HAS DETERMINED THAT "NEAREST POINT OF ENTRANCE"
 SHALL BE NO FARTHER THAN 8' OF UNPROTECTED CONDUCTORS.
 INDICATE COMPLIANCE WITH THIS ARTICLE ON THE PLAN.
 225.32 LOCATION. THE DISCONNECTING MEANS SHALL BE
 INSTALLED EITHER INSIDE OR OUTSIDE OF THE BUILDING OR
 STRUCTURE SERVED OR WHERE THE CONDUCTORS PASS THROUGH
 THE BUILDING OR STRUCTURE. THE DISCONNECTING MEANS
 SHALL BE AT A READILY ACCESSIBLE LOCATION NEAREST THE
 POINT OF ENTRANCE OF THE CONDUCTOR
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. SUBMIT
 THIS INFORMATION ON THE PLANS.
  
 3} PER 230.2 ONE BUILDING SHALL BE SUPPLIED BY ONE
 SERVICE. IT CAN HAVE UP TO SIX METERS, BUT ONLY ONE
 SERVICE. REDRAW THE RISER DIAGRAM TO SHOW COMPLIANCE
 WITH THESE ARTICLES. SHEET #4.
  
 4} NOTES ON THE RISER DIAGRAM INDICATE THE GEC SYSTEM
 ATTACHING TO "FOUNDATION REBAR", NOTE HOW THIS WILL BE
 ACCOMPLISHED GIVEN THE BUILDING IS EXISTING.
  
 5} IF THE LAUNDRY ROOM IS COMMON ELEMENT AREA THAT AREA
 MUST CONTAIN ONLY WIRING FROM THE HOUSE PANEL PER
 210.25 COMMON AREA BRANCH CIRCUITS
 BRANCH CIRCUITS IN DWELLING UNITS SHALL SUPPLY ONLY
 LOADS WITHIN THAT DWELLING UNIT OR LOADS ASSOCIATED
 ONLY WITH THAT DWELLING UNIT. BRANCH CIRCUITS REQUIRED
 FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, SIGNAL,
 COMMUNICATIONS, OR OTHER NEEDS FOR PUBLIC OR COMMON
 AREAS OF A TWO-FAMILY OR MULTIFAMILY DWELLING SHALL NOT
 BE SUPPLIED FROM EQUIPMENT THAT SUPPLIES AN INDIVIDUAL
 DWELLING UNIT.*** NOTE ON PLANS WILL SUFFICE.
  
 6} PER 210.8 (A) (6) THE ISLAND RECEPTACLES ARE
 REQUIRED TO BE GFI PROTECTED- KITCHENS ??? WHERE THE
 RECEPTACLES ARE INSTALLED TO SERVE THE COUNTERTOP
 SURFACES
  
 7} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 A SMOKE ALARM IS REQUIRED IN THE HALL OUTSIDE OF
 BEDROOMS #1 AND #2 TO MEET THE INTENT OF THIS
 REQUIREMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-05-04 Cont ID  
Sent By mawillia Date 2009-05-04 Time 15:25 Rev Time 0.00
Received By mawillia Date 2009-05-04 Time 13:41 Sent To  
Notes
2009-05-04 15:22:20*****DENIED*****
  
 1. PROVIDE AN EXISTING FLOOR PLAN FOR THE PROJECT SITE.
 STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241, 2004
 EDITION.
  
 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND
 NFPA 1, UNIFORM FIRE CODE, 2006 EDITION) SHALL BE
 REFERENCED.
  
 3. IF THE PROJECT SCOPE OF WORK IS TO BE DONE IN UNIT
 #1 ONLY OF THE ADDRESSED BUILDING, THE ADDRESS LISTED
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET SHALL
 INCLUDE THE UNIT NUMBER ALSO.
  
 4. PLEASE LIST THE EXISTING AS WELL AS THE NEW OCCUPANT
 LOAD BASED ON THE CHARACTERISTIC OF THE USE OF THE
 SPACE.
  
 5. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALL
 AND CEILING (IN THE BEDROOMS) IN TERMS OF CLASS A,
 CLASS B, OR CLASS C.
  
 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER.
  
 7. ON THE APPROPIATE EXTERIOR ELEVATION, DISPLAY/SHOW
 THE NUMERICAL ADDRESS FOR THIS BUILDING. AS PER WEST
 PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6"
 IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. THE
 INDIVIDUAL DWELLING UNIT NUMBERS SHALL BE NO LESS THAN
 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
 8. ON THE ELECTRICAL PLAN (SHEET 3), SMOKE DETECTORS
 ARE SHOWN AS BEING USED IN THE PROJECT SPACE. UNLESS
 THESE DEVICES ARE TIED INTO A FIRE ALARM SYSTEM FOR THE
 BUILDING, AMEND VERBAGE TO REFLECT THAT SMOKE ALARMS
 (SA), WHICH ALERT THE OCCUPANT OF THE SAID DWELLING
 UNIT ONLY, ARE TO BE USED.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-05-14 Time   Rev Time 0.00
Received By btrobaug Date 2009-04-20 Time 09:03 Sent To  
Notes
2009-05-01 09:05:55 
  
 MOVED TO COM BUILDOUT (BOB) B-16./WRT.
2009-04-22 11:42:21TO RES BOX #21 BZMEPM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-05-11 Cont ID  
Sent By rregueir Date 2009-05-11 Time 17:00 Rev Time 0.00
Received By rregueir Date 2009-05-11 Time 16:08 Sent To  
Notes
2009-05-11 16:57:20REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SHEET 3: NO PROVISIONS ON PLAN FOR BALANCED RETURN
 AIR FROM BEDROOMS. PROVIDE BALANCED RETURN IN
 ACCORDANCE WITH FBC-M 601.4.
  
 2. SHEET 3: ONE OF TWO FLEX DUCTS FROM AHU CLOSET IS
 MISSING DUCT SIZE ON PLANS. PLEASE PROVIDE MISSING
 INFORMATION IN ACCORDANCE WITH FBC-M 603.1.
  
 3. SHEET 3: ELECTRICAL PLAN SHOWS NEW BATHROOM EXHAUST
 FAN. SHOW LOCATION OF BATH EXHAUST DISCHARGE TO
 DEMONSTRATE COMPLIANCE WITH FBC-M 401.4 AND FBC-M
 501.2.
  
 4. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC-M 307.2.1. ALSO, PROVIDE AUXILIARY
 DRAIN PROTECTION IN ACCORDANCE WITH FBC-M 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-05-05 Cont ID  
Sent By kstevens Date 2009-05-05 Time 15:37 Rev Time 0.00
Received By kstevens Date 2009-05-05 Time 15:37 Sent To  
Notes
2009-05-05 16:20:51DENIED
 REFERENCE:
 FBC-2007 W 2009 SUPPLEMENTS
 FBC-2007 EXISING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. APPLICATIONS FOR PERMIT SUBMITTED ON OR AFTER MARCH
 1, 2009 SHALL BE DESIGNED UNDER THE FBC-2007 CODE
 CYCLE. PLEASE INDICATE ON THE PLANS THE PRESENT CODE
 CYCLE. SECTION 106.1.1.
  
 2. PLEASE INDICATE THE OCCUPANCY ON THE PLANS. SECTION
 106.3.5.1.1(2).
  
 3. A DESIGN PROFESSIONAL OR ON OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THE EXISTING BUILDING
 CODE. SECTION 401.4. PLEASE INDICATE ON PLANS.
  
 4. MORE INFORMATION IS REQUIRED ON THE LAUNDRY ROOM.
 SECTION 106.1.2. IS THE LAUNDRY ROOM FOR UNIT ONE ONLY?
 IF NOT A FLOOR DRAIN IS REQUIRED PER SECTION 412.4 OF
 THE PLUMBING CODE. PLEASE CLARIFY.
  
 5. THE SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. SEE THE RED LINE CORRECTION OF THE SANITARY
 RISER DIAGRAM SUBMITTED AS AN EXAMPLE AS A RISER THAT
 REFLECTS THE FLOOR PLAN. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-05-14 Cont ID  
Sent By lfranco Date 2009-05-14 Time 16:53 Rev Time 0.00
Received By lfranco Date 2009-05-14 Time 16:53 Sent To B
Notes
2009-05-14 17:27:26PLANNING AND ZONING: **** FAILED ****
  
 1. PROVIDE COMMENTS IN WRITING.
  
 2. THIS PROPERTY IS ZONED SINGLE-FAMILY HIGH DENSITY
 ("SF14") - PURSUANT TO THE ZONING AND LAND DEVELOPMENT
 REGULATIONS ("ZLDR"), SECTION 94-74, THE MAXIMUM NUMBER
 OF UNITS ALLOWED IN ONE (1) PRIMARY AND MAY HAVE
 ACCESSORY STRUCTURES THAT ARE REGULATED PURSUANT TO
 SECTION 94-304. ACCESSORY APARTMENTS SHALL BE REGULATED
 PURSUANT TO SECTION 94-303. LOTS LESS THAN THE MINIMUM
 DISTRICT REQUIREMENTS FOR LOT WIDTH AND LOT AREA SHALL
 NOT BE CONSIDERED NONCONFORMING LOTS FOR THE PURPOSE OF
 ALLOWING ACCESSORY STRUCTURES PROVIDED THE STRUCTURE IS
 CONSTRUCTED WITHIN THE REQUIRED DISTRICT SETBACKS.
  
 CLARIFY WHY THERE ARE THREE (3) PROPOSED UNITS WITHIN
 THE BUILDING. THERE IS NO CONNECTION WITH UNIT #1 AND
 THERE IS NO INFORMATION ON WHAT THE OTHER UNITS ENTAIL.
 PROVIDE INFORMATION ACCORDINGLY.
  
 3. PROVIDE A SURVEY SHOWING INFRASTRUCTURE OF THE
 PROPERTY INCLUDING PARKING/DRIVEWAY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 PHONE: (561) 822-1443
 EMAIL: [email protected]
  
  
  
  
  