Plan Review Details - Permit 09040429
Plan Review Stops For Permit 09040429
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-22 Cont ID  
Sent By rmcdouga Date 2009-04-22 Time 15:41 Rev Time 0.00
Received By rmcdouga Date 2009-04-22 Time 15:41 Sent To  
Notes
2009-04-22 16:48:132007 FBC
 SOLAR POOL HEATER
  
 DENIED BY BUILDING
  
 1) SHEET S-2 PROVIDES AN INSTALLATION DETAIL FOR
 ANCHORING THE ROOF PANELS TO THE CONCRETE ROOF TILES.
 PROVIDE A PRODUCT APPROVAL FOR THE ROOF TILES THAT
 ALLOWS THE TILES TO PROVIDE STRUCTURAL ATTACHMENT FOR
 UPLIFT FOR THE SOLAR PANELS. RULE 9B-72
  
 2) PROVIDE SIGNED AND SEALED ENGINEERED CALCULATIONS
 FOR THE SHEAR AND PULLOUT VALUES OF THE TAPCON SCREWS
 IN THE SPECIFIC EXISTING ROOF TILES AT THIS PROJECT.
 SPECIFY THE SIZE OF THE SCREWS, THE LOCATIONS AND
 AMOUNTS OF SCREWS REQUIRED TO PROVIDE ADEQUATE UPLIFT
 RESISTANCE FOR THE SOLAR PANELS. R301.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-04-23 Cont ID  
Sent By btrobaug Date 2009-04-23 Time 16:21 Rev Time 0.00
Received By btrobaug Date 2009-04-23 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-05 Cont ID  
Sent By lmartine Date 2009-04-27 Time 13:20 Rev Time 0.00
Received By lmartine Date 2009-04-22 Time 09:12 Sent To  
Notes
2009-04-22 09:13:16TO "R19"

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-04-22 Cont ID  
Sent By rmcdouga Date 2009-04-22 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2009-04-22 Time 15:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-04-27 Cont ID  
Sent By ajones Date 2009-04-27 Time 16:55 Rev Time 0.00
Received By ajones Date 2009-04-27 Time 16:55 Sent To  
Notes
***NONE***