2009-04-17 17:23:59 | RESIDENTIAL (R3) RE-ROOFING, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 1- NOA 06-0601.08 SUBMITTED DOESN'T CORRESPOND TO |
| FLORIDA PRODUCT APPROVAL FL735-R3 SUBMITTED. SUBMIT NOA |
| ALONE OR PROVIDE NOA THAT IS LISTED ON THE FLORIDA |
| PRODUCT APPROVAL FL 735-R3. |
| |
| 2- CLARIFY IF EXISTING ROOF IS A CONCRETE DECK. NOA |
| SUBMITTED IS FOR CONCRETE DECK APPLICATIONS. |
| |
| 3- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| BE INSTALLED. ALSO, INDICATE WHICH BASE SHEET FASTENING |
| OPTION IS GOING TO BE USED. TO VERIFY THE UPLIFT |
| PRESSURES AS REQUIRED BY SEC. R301 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| ***NOTE: IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR PERIMETER AND CORNER ROOF AREAS AS |
| REQUIRED BY TABLE R301.2(2) OF 2007 FLORIDA RESIDENTIAL |
| CODE AND SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| LIMITATION #7, THEN RAS 117 CALCULATIONS NEED TO BE |
| PROVIDED. ACCORDING TO NOA SUBMITTED RAS 117 |
| CALCULATIONS NEED TO BE SIGNED AND SEALED AS REQUIRED |
| BY GENERAL LIMITATION #7. SEE GENERAL LIMITATION #7 ON |
| LAST PAGE OF NOA SUBMITTED. |
| ON THE OTHER HAND, IF SELECTED ASSEMBLY IS LIMITED BY |
| GENERAL LIMITATION #9, THEN RAS 117 CALCULATIONS CAN'T |
| BE PROVIDED IF THE SELECTED ASSEMBLY DOESN'T MEET THE |
| DESIGN PRESSURES. SEE GENERAL LIMITATION #9 ON LAST |
| PAGE OF NOA SUBMITTED. |
| NOTE: SEE ATTACHED COPY OF CITY POLICY FOR RE-ROOFING |
| PERMITS. |
| |
| 4- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| |