Plan Review Details - Permit 09040291
Plan Review Stops For Permit 09040291
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2009-09-10 Cont ID  
Sent By jwitmer Date 2009-09-10 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2009-09-10 Time 08:51 Sent To  
Notes
2009-09-10 08:52:09REVISION SUBMITTED 9-01-09 WAS A CONTRACTOR MISTAKE, IT
 SHOULD OF BEEN A DIFFERENT PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-15 Cont ID  
Sent By jwitmer Date 2009-07-15 Time 16:44 Rev Time 0.33
Received By jwitmer Date 2009-07-15 Time 16:44 Sent To  
Notes
2009-07-15 16:45:36NEW: A120.1 & A210.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-04 Cont ID  
Sent By jwitmer Date 2009-06-04 Time 16:40 Rev Time 1.00
Received By jwitmer Date 2009-06-04 Time 16:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-22 Cont ID  
Sent By jwitmer Date 2009-04-22 Time 11:44 Rev Time 2.22
Received By jwitmer Date 2009-04-22 Time 10:22 Sent To  
Notes
2009-04-22 13:47:53BUILDING PLAN REVIEW
 PERMIT: 09040291
 ADD: 4 HARVARD CIRCLE
 CONT: FISHER CONTRACTING CORP
 TEL: (561)691-4716
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
  
 * WEST PALM BEACH AMENDMENTS
  
 APRIL 22/2009
 1ST REVIEW
 ACTION: DENIED
  
 1A) : WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 20097 SUPPLEMENTS.PLEASE REVISE COVER
 SHEET AND A120.1.
  
 2) SHEET A120.1 INDICATES (3) NEW OFFICES, THE NEW
 DOORS FAIL TO PROVIDE 18" ON THE PULL SIDE OF THE LATCH
 PLEASE REVIEW 11-4. 13.6.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
  
 3) NEW HANDICAPPED RESTROOM SHOWN ON A120.1 DOES NOT
 INDICATE ON SHEET A130.1 THAT THIS RESTROOM IS A
 HANDICAPPED RESTROOM, PLEASE INDICATE AS SUCH. SHEET
 A110.1 INDICATES THE REMOVAL OF SINK AND CABINET
 INACTING DISPROPORTIONATE COST SECTION 11-4.1.6 (2)(A)
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM.
  
 3A) SHEET A120.1 INDICATES THE REQUIRED FLOOR SPACE FOR
 THE LAV AND WATER CLOSET. THE PLANS CLEARLY INDICATE
 THE DOOR SWINGING INTO THE REQUIRED CLEAR FLOOR SPACE.
 1-4.22.2 DOORS.(1) ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH SECTION 11-4.13. DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 3B) SHEET A500.1 INDICATES THE E3 DOOR THAT LEADS TO
 THE NEW HANDICAPPED RESTROOM TO BE A 32 INCH DOOR
 CREATING A 30 INCH OPENING.
 11-4.13.5 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE
 A MINIMUM CLEAR WIDTH OF 32" WITH THE DOOR OPEN
 90-DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND
 OPPOSITE STOP.
 NOTE THIS IS WHERE THE DISPROPORTIONATE COST REQUIRING
 A HANDICAPPED RESTROOM AND THE REMOVAL OF THE LAV AND
 CABINET CREATE THE REQUIREMENT FOR THE WIDER DOOR. ALSO
 NOTE THE LARGER DOOR WOULD ALSO SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR THE LAV AND WATER CLOSET.
  
 4) SHEET A130.1 DOOR# 2 TO THE RECEPTION AREA INDICATES
 A NEW GLASS SIDE LIGHT, THE DOOR SCHEDULE NOR IS IT
 PICKED UP WITH THE DETAIL 4/ A130.1 THIS REQUIRES
 SAFETY GLAZING. 2406.3(6).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-07-05 Cont ID  
Sent By dpalmer Date 2009-07-05 Time 15:54 Rev Time 0.00
Received By dpalmer Date 2009-07-05 Time 15:54 Sent To  
Notes
2009-07-05 15:55:46LOW VOLTAGE, PHONE/DATA TO BE UNDER SEPARATE PERMIT.
 MAY REFERENCE THESE PLANS FOR TURN AROUND PERMIT FOR
 THE SCOPE OF WORK.
  
  
 PER BUILDIGN OFFICIAL, ANY REVISIONS TO BE SUBMITTED,
 REVIEWED AND STAMPED FOR JOB-SITE INSPECTION BEFORE
 ROUGH.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-06-01 Cont ID  
Sent By dpalmer Date 2009-06-01 Time 17:05 Rev Time 0.00
Received By dpalmer Date 2009-06-01 Time 17:05 Sent To  
Notes
2009-06-01 17:05:52** DENIED 2ND REVIEW**
  
 1) NOTE: PLEASE SEE 13-415.AB.5 UNDER THE FBC 2007 WITH
 2009 REVISIONS.
 THE ADDITIONAL ALLOWANCE PREVIOUSLY PERMITTED FOR
 ACCENT, SCONCE LIGHTING ETC IS NO LONGER UNDER THE NEW
 CODE.
 THE AREAS ARE SPECIFIC TO SPACES. BASED ON THE
 ALLOWANCES UNDER THE NEW CODE, THE AMOUNT SHOWN EXCEEDS
 TABLES.
 THE FIXTURE SCHEDULE NEEDS TO COORDINATE. SEE WALL HUNG
 FIXTURE AS THIS STATES IT IS INCANDESCENT AND SHOWS A
 26W FLUORESCENT BULB. THIS IS NOT POSSIBLE.
 PLEASE BE SURE TO COME UP WITH SOME SORT OF FIXTURE
 MEETING MINIMUM CODE AT THIS TIME. FIXTURES MAY ALWAYS
 BE REVISED ALONG WITH THE TABLE CALCULATIONS AT A LATER
 DATE.
  
  
 ** AS GONE OVER WITH ENGINEER THE MOTION SENSORS WHICH
 ARE SPECIFICALLY STATED ON PLANS TO BE *MOTION ONLY*
 MAY ACTUALLY BE OCCUPANCY SENSORS WHICH ARE DUAL
 TECHNOLOGY.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-06-01 Cont ID  
Sent By dpalmer Date 2009-06-01 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2009-06-01 Time 12:07 Sent To  
Notes
2009-06-01 12:09:25** DENIED**
  
  
 1) NOTE: THE SAME EXACT ELECTRICAL SHEETS WERE
 SUBMITTED BACK INTO THE NEW SETS.
 THE SHEETS ARE DATED 2/23/09. CALLED THE ENGINEER AND
 THERE SHOULD HAVE BEEN NEW SHEETS DATED 5/18/09.
 SAME COMMENTS FROM PREVIOUS REVIEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 BUILDING PLANS EXAMINER II/ ELECTRICAL
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-27 Cont ID  
Sent By dpalmer Date 2009-04-27 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2009-04-27 Time 13:56 Sent To  
Notes
2009-04-27 13:56:17**DENIED PLANS**
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER
 MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007
 FBC WITH 2009 AMENDMENTS. THIS INCLUDES ALL ADOPTED
 CODES AND REFERENCE STANDARDS IN FBC CHAPTER 35
  
 PLEASE SEE FAC 69A-60.003, AND .004 AS THE FOLLOWING
 NFPA REFERENCES WERE ACTUALLY ADOPTED ON DECEMBER 31ST,
 2008
 PLEASE ADJUST AS FOLLOWS.
  
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2006 NFPA-1
 2005 NFPA-70
  
 THESE CODES NEED TO BE REFLECTED ON ELECTRICAL PLANS AS
 WELL AS THE A-SHEETS.
  
 ** PLEASE BE SURE ALL CODE REFERENCES ON PLANS REFLECT
 THE CURRENT ADOPTED CODES.
  
 2) NOTE: PLEASE COMPLETE FIXTURE LEGEND WITH FIXTURES
 SPECIFIC TO INSTALLATION. PLEASE EXPLAIN NOTE ON PLANS
 WHICH STATES * MAXIMUM LIGHTING WILL NOT APPLY IN THIS
 MODEL*.
 IT IS UNCLEAR HOW THE MINIMUM PRESCRIPTIVE FOR NEW
 BEING INSTALLED IS BEING NOTED AS NOT REQUIRED.
 13-415.2.AB.5
  
 3) NOTE: PLEASE EXPLAIN LIGHTING CONTROLS FOR NEW BEING
 INSTALLED. SOME LOCATION ALONG WITH NOTES MENTIONED THE
 USE OF *MOTION SENSORS*. THE MOTION SENSORS ARE NOT
 TYPICAL AND IN EITHER CASE MANY LOCATIONS INDICATE
 THESE DEVICES AND MANY ARE MISSING. AN EXAMPLE IS SOME
 OFFICE ROOMS.
 13-415.1.ABC.1.1, .1.2. (NEW ONLY)
  
 4) NOTE: PLEASE SEE FBC 1006.1.2, LS 101 7.8.1.2.2 AS
 OCCUPANCY SENSORS ARE REQUIRED TO BE FAIL-SAFE ON WHEN
 SELECTED TO CONTROL EGRESS LIGHTING IN EGRESS PATHS.
  
 5) NOTE: PLEASE BE SURE ALL CIRCUITING ON PLANS
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULE AND PLEASE
 BE SURE THE PANEL SCHEDULE IS SPECIFIC TO ROOMS AND
 AREAS IN WHICH THEY FEED. STATING *LTS* OR RECEPTS* IS
 NOT PERMITTED.
 408.4
 AN EXAMPLE WOULD BE CIRCUITS 22 AND 24 HOWEVER THEY ARE
 NOT THE ONLY ONES.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-07-21 Cont ID  
Sent By mawillia Date 2009-07-21 Time 15:27 Rev Time 0.00
Received By mawillia Date 2009-07-21 Time 14:55 Sent To B
Notes
2009-07-21 15:18:09*****APPROVED*****
  
 PLAN SHEETS A110.1, A120.1, A130.1, A180.1, A500.1 AND
 E2 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-06-22 Cont ID  
Sent By mawillia Date 2009-06-22 Time 15:51 Rev Time 0.00
Received By mawillia Date 2009-06-22 Time 15:25 Sent To  
Notes
2009-06-22 15:46:33*****PROVISO*****
  
  
 THE ACTUAL PROJECT SITE ADDRESS, INCLUDING THE SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET. (SUITE NUMBER MISSING FROM SEVERAL PLAN
 SHEETS)
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE ABOVE AS WELL AS THE PLAN EXAMINER(S)' COMMENT HAVE
 BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-23 Cont ID  
Sent By mawillia Date 2009-04-23 Time 09:48 Rev Time 0.00
Received By mawillia Date 2009-04-22 Time 14:29 Sent To  
Notes
2009-04-22 15:46:41*****DENIED*****
  
  
 1. THE 2007 EDITION OF FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION AND
 NFPA 101 - LIFE SAFETY CODE - 2006 EDITION) SHALL BE
 REFERENCED. AMEND APPLICABLE CODES AND CODE ANALYSIS
 DATA ON THE APPROPIATE PLAN SHEETS AS NEEDED.
  
 2. ON THE COVER SHEET UNDER APPLICABLE CODES, AMEND
 NFPA 13 TO REFLECT THE 2002 EDITION (CURRENTLY IN USE).
  
 3. THE ACTUAL PROJECT SITE ADDRESS, INCLUDING THE SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 4. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE FIRE
 SPRINKLER HEADS AND/OR FIRE ALARM DEVICES TO BE
 REMODELED? IF SO, SEPARATE PERMITS AND SHOP DRAWINGS
 WILL BE REQUIRED FOR THIS/THESE SYSTEM(S) AFTER THE
 MAIN PERMIT HAS BEEN ISSUED.
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 10:36 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 10:36 Sent To  
Notes
2009-09-02 10:37:04SENT TO JWITMER.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-24 Cont ID  
Sent By shill Date 2009-06-24 Time 15:35 Rev Time 0.00
Received By shill Date 2009-06-24 Time 15:35 Sent To  
Notes
2009-06-24 15:35:22C10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-05-27 Cont ID  
Sent By kstevens Date 2009-05-27 Time 09:34 Rev Time 0.00
Received By kstevens Date 2009-05-27 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-27 Cont ID  
Sent By kstevens Date 2009-04-30 Time 09:33 Rev Time 0.00
Received By kstevens Date 2009-04-13 Time 15:07 Sent To  
Notes
2009-04-13 15:09:34TO BOB #4

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-06-08 Cont ID  
Sent By rregueir Date 2009-06-08 Time 14:55 Rev Time 0.00
Received By rregueir Date 2009-06-08 Time 14:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-29 Cont ID  
Sent By rregueir Date 2009-04-29 Time 16:00 Rev Time 0.00
Received By rregueir Date 2009-04-29 Time 15:54 Sent To  
Notes
2009-04-29 15:55:41REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 MECHANICAL PLAN STAMPED WITH THE FOLLOWING REDLINED
 NOTE: FLEX DIFFUSER DETAIL REQUIRES SUPPORT TO BE
 MINIMUM 1 1/2 INCHES WIDE IN ACCORDANCE WITH FBC-M
 603.5.6.6.
  
 PLEASE UPDATE THE REFERENCED CODES ON THE FRONT SHEET
 TO SHOW THE CODES IN EFFECT AT TIME OF PERMIT
 APPLICATION. THE 2007 FLORIDA BUILDING CODE W/ 2009
 SUPPLEMENT IS IN EFFECT AS OF MARCH 1, 2009.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-07-13 Cont ID  
Sent By kstevens Date 2009-07-13 Time 10:53 Rev Time 0.00
Received By kstevens Date 2009-07-13 Time 10:53 Sent To  
Notes
2009-07-13 10:53:4711-4-24.4 MAX SINK DEPTH 6-1/2"

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-06-02 Cont ID  
Sent By kstevens Date 2009-06-02 Time 11:48 Rev Time 0.00
Received By kstevens Date 2009-06-02 Time 11:48 Sent To  
Notes
2009-06-02 11:50:13DENIED
 REFERENCE:
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHTS A 120.1 & A 210.1 (DETAILS 8 & 9. PLEASE SHOW
 THE 30" BY 48" CLEAR FLOOR SPACE REQUIRED FOR THE SINK
 ON THE FLOOR PLAN, AND THE KNEE CLEARANCE, (27"), AND
 THE SINK DEPTH, (6-1/2" MAX), AS REQUIRED IN SECTIONS
 11-4.24.3 & 11-4.24.4.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 4. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-30 Cont ID  
Sent By kstevens Date 2009-04-30 Time 14:25 Rev Time 0.00
Received By kstevens Date 2009-04-30 Time 11:48 Sent To  
Notes
2009-04-30 14:40:53DENIED
 REFERENCE:
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 1. THE CODE CYCLE FOR ALL APPLICATIONS FOR PERMIT ON OR
 AFTER MARCH 1, 2009 IS FBC-2007 WITH 2009 SUPPLEMENTS.
 MANY SHEETS INCLUDING THE PLUMBING SHEET INDICATE THE
 DESIGN CRITERIA AS FBC-2004. PLEASE CORRECT ALL
 REFERENCES TO THE DESIGN CODE. SECTION 106.1.1.
  
 2. SHT A 120.1 THE DOOR TO THE ACCESSIBLE TOILET ROOM
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. SECTION 11-4.22.2(1). IT APPEARS THAT THE
 DOOR SWINGS INTO THE CLEAR FLOOR SPACE FOR THE LAV AND
 THE W/C. PLEASE SHOW DOOR SWING FOR THIS TOILET ROOM.
  
 3. SHTS A 120.1 & A 210.1 (DETAILS 8 & 9. PLEASE SHOW
 THE 30" BY 48" CLEAR FLOOR SPACE REQUIRED FOR THE SINK
 ON THE FLOOR PLAN, AND THE KNEE CLEARANCE, (27"), AND
 THE SINK DEPTH, (6-1/2" MAX), AS REQUIRED IN SECTIONS
 11-4.24.3 & 11-4.24.4.
  
 4. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved