Plan Review Details - Permit 09040267
Plan Review Stops For Permit 09040267
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-12-07 Cont ID  
Sent By mawillia Date 2009-12-07 Time 11:33 Rev Time 0.00
Received By mawillia Date 2009-12-03 Time   Sent To  
Notes
2009-12-07 11:06:17*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW WERE
 ADDRESSED. THE FIRE ALARM PLAN (FP-1 & FP-2)
 FIRE-STAMPED ACCORDINGLY; READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-17 Cont ID  
Sent By mwennerg Date 2009-04-17 Time 13:13 Rev Time 0.00
Received By mwennerg Date 2009-04-17 Time 13:13 Sent To  
Notes
2009-04-17 13:19:13***DENIED***
  
 1) THE FLOW TEST RESULTS ARE DATED 1/22/07. PLEASE
 PROVIDE RESULTS BASED ON INFORMATION TAKEN NOT GREATER
 THAN ONE YEAR FROM THE DATE OF PERMIT APPLICATION. IF
 NEW RESULTS ARE REQUIRED, CONTACT THE BUREAU OF FIRE
 PREVENTION AT (561) 804-4724.
  
 2) PLEASE VERIFY THAT THE SAFETY MARGIN OF THIS PROJECT
 IS NOT GREATER THAN 5.0 PSI.
  
 3) THE DOUBLE CHECK DETECTOR ASSEMBLY IS TO BE SECURED
 WITH A CHAIN AND LOCK IN ADDITION TO ELECTRONIC
 SUPERVISION.
  
 4) THE FIRE DEPARTMENT CONNECTION SHALL BE PROVIDED
 WITH KNOX LOCKING CAPS. AN APPLICATION IS AVAILABLE AT
 THE BUREAU OF FIRE PREVENTION. (561) 804-4724.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-01 Cont ID  
Sent By btrobaug Date 2009-12-01 Time 10:48 Rev Time 0.00
Received By btrobaug Date 2009-12-01 Time 10:48 Sent To FIRE
Notes
2009-12-01 10:49:29TO FIRE IN BOX./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-17 Cont ID  
Sent By mwennerg Date 2009-04-17 Time 13:20 Rev Time 0.00
Received By mwennerg Date 2009-04-10 Time 16:40 Sent To  
Notes
2009-04-10 16:40:12TO "F" BOX