Plan Review Details - Permit 09040258
Plan Review Stops For Permit 09040258
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-06 Cont ID  
Sent By jwitmer Date 2009-05-06 Time 11:15 Rev Time 1.25
Received By jwitmer Date 2009-05-06 Time 9:59 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-15 Cont ID  
Sent By jwitmer Date 2009-04-15 Time 09:22 Rev Time 2.22
Received By jwitmer Date 2009-04-15 Time 09:22 Sent To  
Notes
2009-04-15 09:37:00BUILDING PLAN REVIEW
 PERMIT: 09040258
 ADD: 6251 MARTIN AVE.
 CONT: C. R. DUNN
 TEL: (561)585-2155
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS. PLEASE UPDATE SHEET
 E-16 WHICH INDICATES PER FLORIDA BUILDING CODE, LATEST
 EDITION.
  
 2) THE ENGINEER OF RECORD HAS NOT INDICATED THAT THEY
 HAVE REVIEWED THE POLE DESIGN AND EMBEDMENT
 CALCULATIONS BY YOUSSEF HACHEM P.E. BY AFFIXING A SHOP
 DRAWING STAMP INDICATING THIS DOCUMENT HAS BEEN
 REVIEWED AND APPROVED. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 3) THE ENGINEER OF RECORD AND THE ENGINEER THAT CREATED
 THE POLE DESIGN DO NOT HAVE THE SAME DESIGN CRITERIA,
 PLEASE CORRELATE SO THE CALCULATIONS AND DESIGNER OF
 RECORD WILL MATCH IN DESIGN.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-05-05 Cont ID  
Sent By dpalmer Date 2009-05-05 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2009-04-30 Time 17:08 Sent To B
Notes
2009-05-05 10:02:48PLANS STAMPED WITH 2005 NEC.
2009-04-30 17:10:02IN ELEC FOR REVIEW. WAITING ON E-MAIL AFTER CALL TO
 STEVE HOCKMAN AS PLANS NOW STATE THE 2008 NEC WHICH IS
 NOT YET ADOPTED.
 REVIEW TO CONTINUE AND BE COMPLETED ON 5/5/09

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-04-16 Cont ID  
Sent By dpalmer Date 2009-04-16 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2009-04-16 Time 13:25 Sent To  
Notes
2009-04-16 13:27:56REDLINED PLANS.
  
 PANELS NEED TO BE REVISED TO INCLUDE SPECIFIC STREET
 LOCATIONS/IDENTIFICATIONS.408.4
  
 PLEASE PROVIDE WORST CASE VOLTAGE DROP CALCULATIONS.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2009-04-30 Cont ID  
Sent By mgonzale Date 2009-04-30 Time 14:40 Rev Time 1.00
Received By mgonzale Date 2009-04-30 Time 14:38 Sent To  
Notes
2009-04-30 14:40:04**** PASSED ****
  
 HURRICANE WIND CALCULATIONS SUBMITTED,
 PLANS REVISED
  
 [email protected]
 (561) 494-1085
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-04-24 Cont ID  
Sent By efabian Date 2009-04-24 Time 14:33 Rev Time 0.00
Received By efabian Date 2009-04-24 Time 14:32 Sent To B
Notes
2009-04-24 14:33:20PASSED - HOWEVER IT IS NOTED THAT THE POLE MODEL TYPE
 SHOWN ON SHEET E-16 OF THE PLAN ARE INCONSISTENT WITH
 THE EXISTING POLE MODEL TYPE SELECTED FOR INSTALLATION
 IN THE BROADMOOR NEIGHBORHOOD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 12:38 Sent To E
Notes
2009-04-29 12:38:41TO DVP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-04-24 Time   Rev Time 0.00
Received By mjacobs Date 2009-04-10 Time 16:13 Sent To  
Notes
2009-04-13 14:19:40TO COMM BD #23