Plan Review Details - Permit 09040163
Plan Review Stops For Permit 09040163
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-13 Cont ID  
Sent By jgomez Date 2009-04-13 Time 09:25 Rev Time 0.00
Received By jgomez Date 2009-04-13 Time 09:20 Sent To  
Notes
2009-04-13 09:27:21BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- NEED SEPARATE PERMIT FOR MECHANICAL EQUIPMENT ON
 ROOF. SEC. 301.12 2007 MECHANICAL CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-08 Cont ID  
Sent By jgomez Date 2009-04-08 Time 11:53 Rev Time 0.00
Received By jgomez Date 2009-04-08 Time 11:52 Sent To PC
Notes
2009-04-08 11:57:08RE-ROOF BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FBC WITH 2008 REVISIONS.
  
 1- ENGINEER CALCULATIONS NEED TO BE DONE USING ASCE
 7-05 NOT ASCE 7-02. CURRENT CODE IS THE FBC 2007 AND
 ASCE 7-05. REVISE CALCULATIONS AS REQUIRED USING THE
 ASCE 7-05.
  
 2- NEED A SEPARATE PERMIT FOR MECHANICAL EQUIPMENT ON
 THE ROOF TO COMPLY WITH SEC. 301.12 OF 2007 MECHANICAL
 CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-08 Cont ID  
Sent By jgomez Date 2009-04-08 Time 11:57 Rev Time 0.00
Received By jgomez Date 2009-04-08 Time 11:52 Sent To  
Notes
***NONE***