Plan Review Details - Permit 09040032
Plan Review Stops For Permit 09040032
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-08-13 Cont ID  
Sent By shill Date 2009-08-13 Time 15:07 Rev Time 0.00
Received By shill Date 2009-08-13 Time 15:07 Sent To  
Notes
2009-08-13 15:07:21REVISION (ROOF NOA)

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-07-20 Cont ID  
Sent By shill Date 2009-07-20 Time 11:36 Rev Time 0.00
Received By shill Date 2009-07-20 Time 11:36 Sent To  
Notes
2009-07-20 11:43:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE SEE ATTACHED; THIS NOA HAS A "FILE CLOSED"
 STATUS. IT IS MY UNDERSTANDING THAT THIS NOA HAS
 TYPOGRAPHICAL ERRORS AND HAS BEEN SUPERSEDED BY A MORE
 CURRENT NOA.
  
 2. WHEN SUBMITTING A VALID, CURRENT PRODUCT APPROVAL,
 PLEASE SUBMIT A COMPLETE DOCUMENT. THE LAST PAGE OF THE
 NOA IS MISSING. (OTHER SHEETS FOR OTHER ASSEMBLIES DO
 NOT NEED TO BE SUBMITTED)
  
 3. WHEN RESUBMITTING, PLEASE NOTE WHICH APPROVED
 ASSEMBLY IS BEING USED. ALSO NOTE GENERAL LIMITATION #7
 ON THE LAST PAGE OF THE NOA; IF ENHANCED FASTENING IS
 REQUIRED, CALCULATIONS ARE TO BE PREPARED BY AN
 ENGINEER, ARCHITECT, OR REGISTERED ROOF CONSULTANT IF
 THAT REQUIREMENT IS LISTED ON THE NOA.
  
 4. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*103.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-16 Cont ID  
Sent By shill Date 2009-07-16 Time 19:25 Rev Time  
Received By shill Date 2009-07-16 Time 19:19 Sent To Z
Notes
2009-07-16 19:25:53REVISION #2, SP1, D1, A1, A2, S1, S2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-18 Cont ID  
Sent By shill Date 2009-05-18 Time 09:49 Rev Time 0.00
Received By shill Date 2009-05-18 Time 09:49 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-15 Cont ID  
Sent By shill Date 2009-04-15 Time 14:36 Rev Time 0.00
Received By shill Date 2009-04-14 Time 15:55 Sent To  
Notes
2009-04-15 15:09:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. INCORRECT ASCE-7 REFERENCE USED, FBC R43.
  
 2. ENHANCED FASTENING CALCULATIONS SPECIFY INCORRECT
 CODE VERSION (SHOULD BE FBC2007); PLEASE REVISE.
  
 3. ENHANCED FASTENING, FRACTION OF INCH CANNOT BE USED
 IN SPECIFICATION, RAS117 SECTION 9.
  
 4. PROVIDE CALCULATIONS FOR ZONE 3 DESIGN PRESSURES.
 SEE ASCE7-05 FIGURE 6-3 (ENCLOSED), ZONE 3, DESIGN
 PRESSURE IS -89PSF FOR EXPOSURE B; YOU'VE DECLARED -72
 FOR ZONE 3, EXPOSURE C, SEE ALSO COMMENT #7.
  
 5. SECTION 905.3 IS REFERENCED FOR SHINGLE
 INSTALLATION; THIS IS FOR ROOF TILE INSTALLATION.
  
 6. TWO DIFFERENT SHEATHING NAILING PATTERNS PROVIDED;
 ONE DOES NOT COMPLY WITH FBC R803.2.3.1; SEE SHEET S3
 PLYWOOD NAILING DETAIL.
  
 7. PLEASE SEE DEFINITION OF ENCLOSED BUILDING,
 ASCE7-05. IT APPEARS THAT THIS PORTION OF THE BUILDING
 WOULD BE DEFINED UNDER PARTIALLY ENCLOSED; PLEASE
 EXPLAIN RATIONALE FOR ENCLOSED (AS EVIDENCED BY .18
 COEFFICIENT).
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-08-13 Cont ID  
Sent By jgomez Date 2009-08-13 Time 12:59 Rev Time 0.00
Received By jgomez Date 2009-08-13 Time 12:59 Sent To  
Notes
2009-08-13 13:00:14SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-07-07 Cont ID  
Sent By dpalmer Date 2009-07-07 Time 17:05 Rev Time 0.00
Received By dpalmer Date 2009-07-07 Time 17:05 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-05-18 Cont ID  
Sent By shill Date 2009-05-18 Time 12:19 Rev Time 0.00
Received By shill Date 2009-05-11 Time 11:30 Sent To  
Notes
2009-05-13 11:32:30GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-04-23 Time   Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 14:14 Sent To  
Notes
2009-04-06 14:14:28TO "R15"

Review Stop Z ZONING
Rev No 3 Status P Date 2009-07-20 Cont ID  
Sent By mcruz Date 2009-07-20 Time 11:29 Rev Time 0.00
Received By mcruz Date 2009-07-20 Time 10:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-05-18 Cont ID  
Sent By mcruz Date 2009-05-18 Time 11:14 Rev Time 0.00
Received By mcruz Date 2009-05-18 Time 11:13 Sent To B
Notes
2009-05-18 11:13:51RE-STAMP
  
 SENT BACK TO SHILL

Review Stop Z ZONING
Rev No 1 Status P Date 2009-04-23 Cont ID  
Sent By mcruz Date 2009-04-23 Time 13:58 Rev Time 0.00
Received By mcruz Date 2009-04-23 Time 13:24 Sent To  
Notes
2009-04-23 13:58:47PLACED BACK ON RES. SHELF