Plan Review Details - Permit 09030588
Plan Review Stops For Permit 09030588
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-12-07 Cont ID  
Sent By jwitmer Date 2009-12-07 Time 17:02 Rev Time 0.77
Received By jwitmer Date 2009-12-07 Time 17:02 Sent To  
Notes
2009-12-07 17:07:56BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 MISSING NOA WILLARD SHUTTER INC . NOA WILLARD SHUTTER
 INC MODEL "ISLANDER MODEL" TO BE USED AS A EQUIPMENT
 SCREEN. PLEASE NOTE NOA'S INTENDED USE AS A DECROTIVE
 CLADDING AND PROTECTIVE SUN SCREEN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-06-17 Cont ID  
Sent By jwitmer Date 2009-06-17 Time 11:00 Rev Time 1.00
Received By jwitmer Date 2009-06-17 Time 10:00 Sent To  
Notes
2009-06-17 10:42:46BUILDING PLAN REVIEW
 PERMIT: 09030588
 ADD: 105 EVERNIA STREET
 CONT: PLAN REVIEW
 TEL: (561)901-0481 JOHN TUCKER (CONTACT)
  
 FL BLD CODE= 2007FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 JUNE 17/2009
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2-6 COMPLIED.
  
 7) PLANS (A3.01 DETAIL 4) INDICATE THE USE OF BAT
 INSULATION DIRECTLY ON TOP OF THE LAY IN ACCUSTICAL
 CEILING.
 3-404.ABC.1 ROOF/CEILING THERMAL ENVELOPES. THE ROOF OR
 CEILING WHICH FUNCTIONS AS THE BUILDING'S THERMAL
 ENVELOPE SHALL BE INSULATED TO AN R -VALUE OF AT LEAST
 R-10. ROOF INSULATION SHALL NOT BE INSTALLED ON A
 SUSPENDED CEILING WITH REMOVABLE CEILING PANELS. WHERE
 CAVITIES BENEATH A ROOF DECK ARE VENTILATED, THE
 CEILING SHALL BE CONSIDERED THE ENVELOPE COMPONENT
 UTILIZED IN THE ENERGYGAUGE SUMMIT FLA/COM CALCULATION.
  
 8) PLANS ARE CURRENTLY IN AS A PLAN REVIEW, WILL
 REQUIRE A LICENSED CONTRACTOR TO APPLY FOR PERMIT
 BEFORE A PASS CAN OCCUR.
  
 9) INFORMATIONAL: THE REQUIRED SCREENING BY ZONING FOR
 ROOF TOP EQUIPMENT MAY CAUSE ADDITIONAL COMMENTS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-10 Cont ID  
Sent By jwitmer Date 2009-04-10 Time 16:41 Rev Time 1.77
Received By jwitmer Date 2009-04-10 Time 16:41 Sent To  
Notes
2009-04-10 16:57:46BUILDING PLAN REVIEW
 PERMIT: 09030588
 ADD: 105 EVERNIA STREET
 CONT: PLAN REVIEW
 TEL: (561)901-0481 JOHN TUCKER (CONTACT)
  
 FL BLD CODE= 2007FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) I PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS. THE 2007 EXISTING
 BUILDING CODE WITH 2009 SUPPLEMENTS. ALSO THE DESIGN
 PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO SECTION
 403,404 & 405 OF THIS CODE, 2007 EXISTING BUILDING
 CODE.
  
 2) THE WIND DESIGN FOUND ON SHEET M-4 WHICH REFRENECES
 ASCE 7-98. THE 2007 FBC REFRENECES THE ASCE 7-05,
 PLEASE CORRECT. SEE CHAPTER 35 FOR STANDARDS.
  
 3) PLEASE REVIEW SHEET A-1.02 FOR TYPE OF ROOF
 CONSTRUCTION. PLANS INDICATE BUILT UP ROOFING ON
 LIGHTWEIGHT CONCRETE ON 4 INCH CONCRETE PLANK
 STRUCTURAL SLAB. BUT THE DETAIL SHEET M-4 INDICATES THE
 USE OF BAR JOIST WITH METAL DECK, PLEASE CORRECT WITH
 PROPER CONNECTIONS INTO CONCRETE PLANK DECK.
  
 4) SHEET M-4 INDICATES A DETAIL FOR HURRICANE SUPPORT
 DETAIL FOR ROOF MOUNTED OR ROOF PENETRATING SYSTEMS.
 THE DETAIL INDICATES THE USE OF CABLE TO BE FASTENED
 INTO THE ROOF STRUCTURE, DOES THIS MEAN THE LIGHTWEIGHT
 CONCRETE OR THE 4 " CONCRETE PLANK ROOFING, PLEASE
 INDICATE AS SUCH. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 5) 2007 MECHANICAL CODE 301.12. WIND
 RESISTANCE.MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING (1609.6). THIS MAY BE
 ACCOMPLISHED BY DESIGN OR BY APPLICATION OF SECTION
 301.13.1. ROOF-MOUNTED MECHANICAL UNITS AND SUPPORTS
 SHALL BE SECURED TO THE STRUCTURE. THE USE OF WOOD
 ???SLEEPERS??? SHALL NOT BE PERMITTED. PLEASE PROVIDE
 DOCUMENTATION THAT THE ROOF TOP EQUIPMENT WILL MEET THE
 140 MPH REQUIREMENT. THE PLANS PROVIDE THE ATTACHMENT
 DETAILS FOR CURB TO ROOF ATTACHMENT WHEN CORRECTED, THE
 UNIT TO CURB ATTACHMENT THE CODE IS ALSO REQUIRING THE
 EQUIPMENT OR APPLIANCE TO MEET WIND LOADS.
  
 6) SHEET A1.02 INDICATES PART OF A PARAPET WALL BEING
 CUT FOR THE INSTALATION OF THE NEW ROOF TOP UNIT. THE
 PLANS DO NOT INDICATE SINCE A PORTION OF THE PARAPET
 WALL IS BEING REMOVED THE TIE IN OF THE REMAINED OF THE
 PARPET WALL WITH THE REMAINING TOP STEEL. THE OTHER
 ISSUE IS THE SUPPLY AND RETURN AIR DUCTS THAT ARE
 PENETRATING THE ROOF, WILL THEY PENETRATE THE ROOF DECK
 AT THE SAME LOCATION OR ARE THE PENETRATIONS REQUIRED
 TO BE LARGER OR IN ANOTHER AREA OF THE PLANK CONCRETE
 ROOF SYSTEM, HOW MUCH OF THE PLANK HAS BEEN REMOVED AND
 DOES THIS PLANK REQUIRE REINFORCEMENT FORTHE ADDITIONAL
 LOADS. 106.1.2.ADDITIONAL INFORMATION REQUIRED.
 1609.1.1WIND LOADS/ MWFRS- MAINWIND FORCE RESISTING
 SYSTEM.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-12-02 Cont ID  
Sent By dpalmer Date 2009-12-02 Time 17:01 Rev Time 0.00
Received By dpalmer Date 2009-12-02 Time 17:01 Sent To  
Notes
2009-12-02 17:01:50** NOTES **
  
 1) NOTE: RESPONSE MENTIONS THAT PREVIOUS METHOD C WAS
 SUBMITTED TO SHOW COMPLIANCE. HOWEVER AS PREVIOUSLY
 NOTED, AS OF MARCH 1ST,2009 THERE IS NO LONGER A METHOD
 C IN THE FLORIDA BUILDING CODE. AS THIS DOES NOT AFFECT
 ELECTRICAL IT NOTED FOR INFORMATION.
  
 METHOD A NOT ACCEPTED AS WHOLE BUILDING ONLY AS
 ADDITION. NOT STAMPED BY ELECTRICAL REVIEWER AS CODE
 COMPLIANT/REVIEWED AS THERE ARE COMPONENTS IN THE INPUT
 DATE REPORT WHICH ARE NOT AS PER PLANS FOR OTHER
 TRADES.
 ELECTRICAL PLANS ONLY STAMPED.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-06-15 Cont ID  
Sent By dpalmer Date 2009-06-15 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2009-06-15 Time 16:01 Sent To  
Notes
2009-06-15 16:01:41 
  
  
 ** DENIED 2ND REVIEW *
  
 1) NOTE: AS STATED ON THE PREVIOUS REVIEW NO PERMIT
 APPLICATION HAS BEEN MADE TO DATE BY A LICENSED
 CONTRACTOR. PLEASE BE AWARE THE ELECTRICAL CODE MAY
 CHANGE ON JULY 1ST 2009.
 ALL PERMIT APPLICATIONS MUST BE APPLIED FOR PERMIT
 BEFORE THAT DATE TO REMAIN UNDER THE 2005 NEC.
  
 2) NOTE: AS STATED ON THE PREVIOUS REVIEW: NO *
 EQUIPMENT GROUNDING CONDUCTORS* ARE PERMITTED BEFORE
 THE FIRST MEANS OF DISCONNECT. THE RESPONSE FROM
 ENGINEER SPEAKS OF GROUNDING ELECTRODE CONDUCTORS. THIS
 WAS NOT THE PREVIOUS REVIEW COMMENT AND THE RISER STILL
 CLEARLY SHOWS EQUIPMENT GROUNDING CONDUCTORS BEFORE THE
 MAINS WHICH IS NOT PERMITTED.
 PLEASE SEE 250.6, 250.24.
 ** CALL IF THERE ARE ANY QUESTIONS.
  
 3) NOTE: THE PACKAGE NOW HAS A METHOD *A* FLA-COM
 SUBMITTED AS WELL AS A FORM 400C-07. PLEASE SEE FBC
 CHAPTER 13 AS ADOPTED ON MARCH 1ST 2009. THE GLITCHES
 WHICH WENT INTO EFFECT ON MARCH 1ST COMPLETELY REVISED
 CHAPTER 13. THERE IS NO MORE METHOD *C*. MAY ONLY USE
 METHOD *A* IF INCLUDING *ALL* COMPONENTS FOR THE WHOLE
 BUILDING METHOD.
 MAY NOT USE DIFFERENT METHODS PER 13-415.AB.5. BOTH A
 AND C WERE SUBMITTED BOTH OF WHICH DATED BY THE
 ENGINEER 5/22/09.
 IF USING METHOD A, ALL COMPONENTS MUST BE LISTED FOR
 WHOLE BUILDING COMPLIANCE. A CLEAR EXAMPLE IS THAT THE
 INPUT DATA REPORT ONLY INDICATES 4-50WATT FIXTURES FOR
 INTERIOR LIGHTS. THIS DOES NOT CORRELATE WITH PLANS.
 THERE ARE ALSO OTHER ITEMS SHOWN IN THE IDR WHICH ARE
 NOT PER PLANS.
 THERE ARE MORE THAN 4 FIXTURES ON PLANS ALONG WITH THE
 WATTAGE WHICH IS COMPLETELY DIFFERENT FROM THE IDR.
 ONE COPY OF FLA COM METHOD A AND ONE COPY OF FORM *C*
 IS BEING RETAINED BY THIS OFFICE ALONG WITH ONE COPY OF
 PLANS.
 4) NOTE: PLEASE LABEL NEW MAIN 6 OF 6. 230.2E
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-16 Cont ID  
Sent By dpalmer Date 2009-04-16 Time 08:42 Rev Time 0.00
Received By dpalmer Date 2009-04-16 Time 08:42 Sent To  
Notes
2009-04-16 08:42:57** DENIED**
  
  
  
 1) NOTE: PLEASE SEE NEC 250.6 AND 250 AS RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED. THIS 3/0 CONDUCTOR
 WOULD CREATE OBJECTIONABLE CURRENTS.
  
 2) NOTE: PLEASE PROVIDE LOCATION OF METERING EQUIPMENT.
 PLEASE SEE FPL MINIMUM SERVICE STANDARDS. IF EXISTING
 PLEASE SHOW.
  
 3) NOTE: PLANS SUBMITTED FOR PLAN REVIEW ONLY AND HAVE
 NOT BEEN SUBMITTED FOR PERMIT BY A LICENSED CONTRACTOR.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-12-08 Cont ID  
Sent By mawillia Date 2009-12-08 Time 12:07 Rev Time 0.00
Received By mawillia Date 2009-12-08 Time 11:50 Sent To  
Notes
2009-12-08 12:04:19*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-1.01 AND E-1.01 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-06-16 Cont ID  
Sent By mwennerg Date 2009-06-16 Time 14:00 Rev Time 0.00
Received By mwennerg Date 2009-06-16 Time 14:00 Sent To  
Notes
2009-06-16 14:03:28**DENIED***
  
 PLANS SUBMITTED FOR PLANS REVIEW ONLY.
  
 COMMENTS TAKEN DIRECTLY FROM FIRST REVIEW. PLEASE NOTE
 THAT A RESPONSE LETTER HAS BEEN PROVIDED FOR PREVIOUS
 REVIEWS WITH EXCEPTION OF THE FIRE REVIEW. A RESPONSE
 LETTER WOULD HELP EXPEDITE THE PLAN REVIEW PROCESS AS
 COMMENT #3 WILL REQUIRE A WRITTEN RESPONSE.
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2006. PLEASE
 ADD NOTE TO CODE SUMMARY ON SHEET A-1.01.
  
 2) PLANS SEEM TO SHOW CONFLICTING INFORMATION REGARDING
 SMOKE DETECTOR PLACEMENT. DUCT SMOKE DETECTORS SHALL BE
 PROVIDED IN THE SUPPLY DUCT IN ACCORDANCE WITH THE
 MECHANICAL CODE. IF PROJECT IS PROVIDED WITH A FIRE
 ALARM SYSTEM, DUCT SMOKE DETECTORS TO BE TIED TO THE
 ALARM SYSTEM AND INITIATE A GENERAL FIRE ALARM IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) WILL THIS WORK HAVE ANY IMPACT ON EXISTING FIRE
 PROTECTION SYSTEMS?
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-17 Cont ID  
Sent By mwennerg Date 2009-04-17 Time 14:05 Rev Time 0.00
Received By mwennerg Date 2009-04-17 Time 14:05 Sent To  
Notes
2009-04-17 14:12:50***DENIED***
  
 PLANS SUBMITTED FOR PLANS REVIEW ONLY.
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2006. PLEASE
 ADD NOTE TO CODE SUMMARY ON SHEET A-1.01.
  
 2) PLANS SEEM TO SHOW CONFLICTING INFORMATION REGARDING
 SMOKE DETECTOR PLACEMENT. DUCT SMOKE DETECTORS SHALL BE
 PROVIDED IN THE SUPPLY DUCT IN ACCORDANCE WITH THE
 MECHANICAL CODE. IF PROJECT IS PROVIDED WITH A FIRE
 ALARM SYSTEM, DUCT SMOKE DETECTORS TO BE TIED TO THE
 ALARM SYSTEM AND INITIATE A GENERAL FIRE ALARM IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) WILL THIS WORK HAVE ANY IMPACT ON EXISTING FIRE
 PROTECTION SYSTEMS?
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-16 Cont ID  
Sent By shill Date 2009-11-16 Time 10:56 Rev Time 0.00
Received By shill Date 2009-11-16 Time 10:56 Sent To  
Notes
2009-11-16 10:56:57C32
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-17 Cont ID  
Sent By shill Date 2009-06-17 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2009-06-02 Time 10:26 Sent To  
Notes
2009-06-02 10:31:03COMM BOARD C15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-17 Cont ID  
Sent By mwennerg Date 2009-04-17 Time 14:15 Rev Time 0.00
Received By mwennerg Date 2009-03-31 Time 14:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-12-19 Cont ID  
Sent By rregueir Date 2009-12-19 Time 12:31 Rev Time 0.00
Received By rregueir Date 2009-12-19 Time 12:09 Sent To  
Notes
2009-12-19 12:32:55**PROVISO**
 PROVIDE RTU AND EXHAUST FAN MANUFACTURER'S DATA SHOWING
 THESE APPLIANCE ARE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-06-15 Cont ID  
Sent By rregueir Date 2009-06-12 Time 16:49 Rev Time 0.00
Received By rregueir Date 2009-06-12 Time 16:35 Sent To  
Notes
2009-06-15 16:05:15TEMP FAIL PENDING APPLICATION BY CERTIFIED CONTRACTOR

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-14 Cont ID  
Sent By rregueir Date 2009-04-14 Time 16:15 Rev Time 0.00
Received By rregueir Date 2009-04-14 Time 14:09 Sent To  
Notes
2009-04-14 16:15:22REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: PLANS SUBMITTED FOR PLANS REVIEW ONLY. NO PERMIT
 APPLICATION SUBMITTED AT THIS TIME.
  
 1. PAGE M-3: EXHAUST FAN SCHEDULE CALLS FOR EF-1 AND
 EF-2 WHILE PAGE M-3 SHOWS EF-4 AND EF-5. PLEASE
 COORIDINATE PLANS AND EQUIPMENT SCHEDULES.
  
 2. PAGE M-3: MECHANICAL NOTES 15, 16 AND 18 REFERENCE
 THE 2004 FBC. PLEASE UPDATE ALL CODES TO REFERENCE THE
 2007 FBC, WHICH IS IN EFFECT AS OF MARCH 1, 2009.
  
 3. PAGE M-4: DIFFUSER DETAIL SHOWS FLEX DUCT SUPPORTED
 BY 1 INCH BAND. ALL SUPPORTS FOR FLEX DUCT SHALL BE
 MIN. 1 1/2" WIDE MINIMUM PER FBC-M 603.5.6.6.
  
 4. PAGE M-4: ROOF CURB DETAILS SHOW ATTACHMENT BASED ON
 ROOF JOIST AND METAL DECK CONSTRUCTION. ARCHITECTURAL
 PLANS INDICATE THIS BUILDING ROOF STRUCTURE IS CONCRETE
 DECK/PLANKS. PLEASE PROVIDE CURB INSTALLATION DETAIL
 APPROPRIATE FOR THE EXISTING CONSTRUCTION, DESIGNED FOR
 WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
  
 5. PAGE M-4 AND E-1.01: THESE PAGES SHOW DUCT SMOKE
 DETECTOR INSTALLED IN THE RETURN DUCT WHILE PAGE M-1
 SHOWS THE DUCT SMOKE DETECTOR INSTALLED IN THE SUPPLY
 DUCT. PLEASE COORDINATE PLANS AND DETAILS, SHOWING THE
 DUCT SMOKE DETECTOR BEING INSTALLED IN THE SUPPLY DUCT
 IN ACCORDANCE WITH FBC-M 606.2.1.
  
 6. PROVIDE MANUFACTURER'S DATA FOR THE PROPOSED RTU
 SHOWING IT IS DESIGNED FOR WIND RESOSTANCE. MECHANICAL
 APPLIANCES EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M
 301.12.
  
 7. ON DOWN-FLOW UNITS (SUCH AS THE PROPOSED RTU), A
 WATER-LEVEL MONITORING DEVICE SHALL BE INSTALLED INSIDE
 THE PRIMARY DRAIN PAN IN ACCORDANCE WITH FBC-M
 307.2.3.1. THIS DEVICE SHALL SHUT OFF THE EQUIPMENT
 SERVED IN THE EVENT THAT THE PRIMARY DRAIN BECOMES
 RESTRICTED. EXTERNALLY INSTALLED DEVICES AND DEVICES
 INSTALLED IN THE DRAIN LINE SHALL NOT BE PERMITTED.
  
 NOTE: MECHANICAL PLANS WERE NOT SIGNED AND SEALED BY
 THE ENGINEER. ONCE PLANS ARE SUBMITTED FOR PERMIT,
 PLANS SHALL BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL IN ACCORDANCE WITH FS 471 AND FAC RULE
 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2009-12-09 Cont ID  
Sent By aaponte Date 2009-12-09 Time 10:02 Rev Time 0.00
Received By aaponte Date 2009-12-09 Time 10:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2009-06-03 Cont ID  
Sent By mflis Date 2009-06-03 Time 14:02 Rev Time 0.00
Received By mflis Date 2009-06-03 Time 13:53 Sent To  
Notes
2009-06-03 14:05:44ZONING REVIEW: FAILED
  
 ** PREVIOUS COMMENT/QUESTION UNADDRESSED: PORTION OF
 SCREEN WALL TO BE REMOVED; ALL MECHNICAL EQUIPMENT MUST
 BE SCREENED FROM VIEW. THE PROPOSED MODIFICATION
 INDICATES RTU WILL BE VISIBLE FROM SW SIDE. PLEASE
 INDICATE SCREENING OR DEMONSTRATE EQUIPMENT WILL NOT BE
 VISIBLE.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2009-04-08 Cont ID  
Sent By mflis Date 2009-04-08 Time 08:42 Rev Time 0.00
Received By mflis Date 2009-04-08 Time 08:42 Sent To  
Notes
2009-04-08 08:44:47ZONING REVIEW: FAILED
  
 1) INSTALLATION OF NEW RTU REQUIRES REMOVAL OF PORTION
 OF SCREEN WALL. MECHANICAL EQUIPMENT SHOULD BE SCREENED
 ON ALL SIDES. WITH THIS NEW CONFIGURATION, WILL RTU BE
 EXPOSED AND VISIBLE FROM SOUTHWEST? PLEASE ADDRESS.
  
 MATT FLIS - 822-1445