Plan Review Details - Permit 09030474
Plan Review Stops For Permit 09030474
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-15 Cont ID  
Sent By shill Date 2009-04-15 Time 17:30 Rev Time 0.00
Received By shill Date 2009-04-15 Time 17:30 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-07 Cont ID  
Sent By shill Date 2009-04-07 Time 08:50 Rev Time 0.00
Received By shill Date 2009-04-07 Time 08:50 Sent To  
Notes
2009-04-07 08:52:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE REVISE GOVERNING CODE, FS553.
  
 2. PLEASE CLARIFY COMPLIANCE WITH FBC R4101.17. A CHILD
 BARRIER IS SHOWN, BUT NOTHING IS SHOWN BETWEEN THE
 CABANA HOUSE AND THE PROPOSED POOL.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-16 Cont ID  
Sent By dpalmer Date 2009-04-16 Time 15:14 Rev Time 0.00
Received By dpalmer Date 2009-04-16 Time 15:14 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-03 Cont ID  
Sent By dpalmer Date 2009-04-03 Time 16:23 Rev Time 0.00
Received By dpalmer Date 2009-04-03 Time 16:23 Sent To P
Notes
2009-04-03 16:23:10** DENIED **
  
  
 1) NOTE: PLANS SUBMITTED AFTER MARCH 1ST, 2009 SHALL
 ALL BE UNDER THE LATEST ADOPTED FLORIDA BUILDING CODES
 PER FS 553.73
 CURRENTLY 2007 FBEC W/ 2007 REVISIONS.
  
 2) NOTE: PLEASE COORDINATE ALL ELECTRICAL DEVICES,
 DETAILS ETC FOE ACTUAL EQUIPMENT SPECIFIC TO THIS
 LOCATION AND PROPOSED POOL. SOME DETAILS INCLUDE SPA
 ETC YET SOME OTHER AREAS OF PLANS HAVE DELETED SOME OF
 THESE ITEMS.
 NEC 2005 220, 680, 310.163, 240.4 GIVEN AS GENERAL AS
 IT IS NOT KNOWN WHICH IS TO BE REVIEW
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF RECORD
 PLANS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2009-04-06 Cont ID  
Sent By lwagner Date 2009-04-06 Time 13:51 Rev Time 0.00
Received By lwagner Date 2009-04-06 Time 11:21 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-10 Cont ID  
Sent By adarroug Date 2009-04-10 Time 11:13 Rev Time 0.00
Received By adarroug Date 2009-04-10 Time 11:13 Sent To Z
Notes
2009-04-10 11:14:02TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-01 Cont ID  
Sent By adarroug Date 2009-04-01 Time 08:32 Rev Time 0.00
Received By adarroug Date 2009-04-01 Time 08:32 Sent To E
Notes
2009-04-01 08:33:13TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-27 Cont ID  
Sent By mcruz Date 2009-03-27 Time 08:54 Rev Time 0.00
Received By mcruz Date 2009-03-24 Time 08:54 Sent To  
Notes
2009-03-27 08:54:50PLACED IN Z BOX.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-04-14 Cont ID  
Sent By lwagner Date 2009-04-14 Time 09:14 Rev Time 0.00
Received By lwagner Date 2009-04-14 Time 09:11 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-06 Cont ID  
Sent By lwagner Date 2009-04-06 Time 14:22 Rev Time 0.00
Received By lwagner Date 2009-04-06 Time 13:52 Sent To B
Notes
2009-04-06 13:53:40PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2007 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 FBC R4101.6 ENGINEERING DESIGN.
 DESIGN SHALL BE IN CONFORMITY WITH ANSI/NSPI 7 FOR
 ENTRAPMENT AVOIDANCE.
  
 NOTES:
 CALCULATIONS SHOWING TDH, PUMP HORSEPOWER, AND MAXIMUM
 FLOW RATES FOR MAINDRAIN BRANCH AND MAIN PIPING (
 VELOCITY FOR MAINDRAIN BRANCH PIPING IS 6 FEET PER
 SECOND MAXIMUM WHEN ONE OF A PAIR IS BLOCKED. ETC.)
  
 LISTED SUCTION OUTLETS ARE REQUIRED TO MEET ASME/ANSI
 A112.19.8 MOST RECENT EDITION.
  
 REVIEW BY LARRY WAGNER
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-04-15 Cont ID  
Sent By mcruz Date 2009-04-15 Time 11:48 Rev Time 0.00
Received By mcruz Date 2009-04-15 Time 11:48 Sent To B
Notes
2009-04-15 11:48:49GAVE TO LM

Review Stop Z ZONING
Rev No 2 Status N Date 2009-03-27 Cont ID  
Sent By mcruz Date 2009-03-27 Time 08:52 Rev Time 0.00
Received By mcruz Date 2009-03-24 Time 08:52 Sent To  
Notes
2009-03-27 08:53:12DISREGARD - INCORRECT ENTRY

Review Stop Z ZONING
Rev No 1 Status F Date 2009-03-27 Cont ID  
Sent By mcruz Date 2009-03-27 Time 13:25 Rev Time 0.00
Received By mcruz Date 2009-03-27 Time 13:15 Sent To  
Notes
2009-03-27 13:25:31PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO AN
 REQUIRED SETBACK.
  
 PURSUANT TO THE ZLDR, SECTION 94-72(A)(2): MINIMUM
 SETBACKS FOR PRINCIPAL BUILDING WITHIN THE
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT,
 ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 3. PURSUANT TO THE ZLDR, SECTION 94-304(D)(2)(B-E):
  
 B. EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
  
 C. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 D. IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT TO OR
 SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN AWAY
 FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  