Plan Review Details - Permit 09030304
Plan Review Stops For Permit 09030304
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-28 Cont ID  
Sent By shill Date 2009-04-28 Time 13:57 Rev Time 0.00
Received By shill Date 2009-04-28 Time 13:57 Sent To  
Notes
2009-04-28 13:58:57PER BUILDING OFFICIAL - THIS JOB IS IN EXPOSURE C.
 HOWEVER, EOR USED DESIGN CRITERIA FOR 160MPH, 1.15
 IMPORTANCE FACTOR, EXPOSURE B. EOR AND BO AGREED THAT
 EOR'S DESIGN CRITERIA EXCEEDED MINIMUM CODE COMPLIANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-10 Cont ID  
Sent By shill Date 2009-04-10 Time 16:41 Rev Time 0.00
Received By shill Date 2009-04-10 Time 16:41 Sent To  
Notes
2009-04-10 16:45:56****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE REVISE GOVERNING CODE, FBC2007 WITH 2008
 SUPPLEMENTS.
  
 2. PLEASE PROVIDE INFORMATION REGARDING SURROUNDING
 TERRAIN, FBC1609. EXPOSURE B WAS DECLARED. PLEASE NOTE
 THAT THE DEFINITION OF EXPOSURE B AND EXPOSURE C HAVE
 CHANGED, ASCE7-05.
  
 3. PLEASE INDICATE WHICH ASSEMBLY YOU PROPOSE TO USE ON
 THE ROOF NOA. PLEASE NOTE THAT ONLY ONE COMPLIES WITH
 DESIGN PRESSURES SPECIFIED BY ENGINEER.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2009-04-22 Cont ID  
Sent By dpalmer Date 2009-04-22 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2009-04-22 Time 12:07 Sent To B
Notes
2009-04-22 12:09:16NO ELECTRICAL APPLIED FOR, ELECTRICAL REMOVED FROM
 PLANS. LIGHTING AND LIGHTNING PROTECTION UNDER SEPARATE
 PLANS AND FEES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-03 Cont ID  
Sent By dpalmer Date 2009-04-03 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2009-04-03 Time 17:02 Sent To Z
Notes
2009-04-03 17:02:53** DENIED **
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER
 MARCH 1ST, 2009 ARE REQUIRED TO BE UNDER THE 2007 FBC
 WITH 2009 AMENDMENTS.
 ALL GROUNDING AND SYSTEM DETAILS NEED TO BE SHOWN.
 250.106
  
 2) NOTE: ALL LIGHTNING PROTECTION SYSTEMS SHALL SHOW
 ALL COMPLIANCE WITH NFPA-780. THIS WILL ALSO BE UNDER A
 SEPARATE PERMIT.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-22 Cont ID  
Sent By dpalmer Date 2009-04-22 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2009-04-22 Time 12:07 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-10 Cont ID  
Sent By shill Date 2009-04-10 Time 16:46 Rev Time 0.00
Received By shill Date 2009-03-16 Time 09:00 Sent To  
Notes
2009-03-16 10:25:26TO "E" BOX--STRUCTURAL ROOF, GOES TO "E" AND "MISC"
 BOX#2(PER LMARTINEZ)
2009-03-16 09:01:15TO "RMCDOUGAL" DESK

Review Stop Z ZONING
Rev No 1 Status N Date 2009-04-08 Cont ID  
Sent By lfranco Date 2009-04-08 Time 15:04 Rev Time 0.00
Received By lfranco Date 2009-04-08 Time 15:04 Sent To B
Notes
***NONE***