Plan Review Details - Permit 09030122
Plan Review Stops For Permit 09030122
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-03-16 Cont ID  
Sent By shill Date 2009-03-16 Time 17:11 Rev Time 0.00
Received By shill Date 2009-03-16 Time 17:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-06 Cont ID  
Sent By shill Date 2009-03-06 Time 15:51 Rev Time 0.00
Received By shill Date 2009-03-16 Time 17:11 Sent To  
Notes
2009-03-06 15:52:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE PROVIDE EVIDENCE THAT THE SUBSTRATE MEETS
 MINIMUM CONCRETE STRENGTH OF 3100PSI, SEE PRODUCT
 APPROVAL PAGE 6. ALTERNATIVELY, ANCHOR SPACING FOR
 CONCRETE BLOCK MAY BE USED (WITH CONCRETE BLOCK
 SPECIFIED AS SUBSTRATE).
  
 2. SEE OPENING 2. CONCRETE BLOCK SUBSTRATE REQUIRES 8"
 SPACING, SEE PAGE 7. THIS IS AN EXAMPLE; PLEASE CHECK
 ALL OPENINGS AND REVISE AS NECESSARY.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-12 Cont ID  
Sent By shill Date 2009-03-12 Time 10:40 Rev Time 0.00
Received By shill Date 2009-03-12 Time 10:40 Sent To B
Notes
2009-03-12 10:40:38TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-06 Cont ID  
Sent By shill Date 2009-03-06 Time 15:52 Rev Time 0.00
Received By shill Date 2009-03-16 Time 17:11 Sent To  
Notes
***NONE***