Plan Review Details - Permit 09030065
Plan Review Stops For Permit 09030065
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-05 Cont ID  
Sent By rmcdouga Date 2009-05-05 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2009-05-05 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-31 Cont ID  
Sent By rmcdouga Date 2009-03-31 Time 08:50 Rev Time 0.00
Received By rmcdouga Date 2009-03-31 Time 08:50 Sent To  
Notes
2009-03-31 09:40:322007 FBC W/2007 REVISIONS
 9 FABRIC AWNINGS
  
 DENIED BY BUILDING
  
 1) THE 2007 FBC CAME INTO EFFECT ON MARCH 1, 2009. ALL
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH THE 2007 FBC. PLEASE UPDATE THE
 ENGINEERED DRAWINGS.
  
 2) THE EDITION OF ASCE7 HAS ALSO CHANGED. ASCE 7-05 IS
 THE ONE THAT IS REFERENCED BY THE 2007 FBC. PLEASE
 REVISE THE ENGINEERED DRAWINGS ACCORDINGLY.
  
 3) FBC 3105.1.1.2 A FIXED FABRIC AWNING OR
 FABRIC-COVERED FRAME SHALL NOT EXTEND OVER PUBLIC
 PROPERTY MORE THAN TWO-THIRDS THE DISTANCE FROM THE
 PROPERTY LINE TO THE NEAREST CURB LINE IN FRONT OF THE
 BUILDING SITE AS MEASURED FROM THE EXTERIOR FACE OF THE
 BUILDING NOR SHALL ANY PORTION BE CLOSER THAN 18 INCHES
 (457 MM) TO THE CURB LINE.
 EXCEPTIONS:
 1. IF INSTALLED OVER 14 FEET (4267 MM) IN HEIGHT, IT
 MAY OCCUPY THE ENTIRE WIDTH OF THE SIDEWALK.
 2. UNLESS OTHERWISE REGULATED BY LOCAL ZONING
 REQUIREMENTS.
  
 4) SEC. 94-212. NORTHWOOD MIXED USE DISTRICT--BUILDING
 TYPE II. (D) ARCHITECTURAL STANDARDS. ARCHITECTURAL
 STANDARDS FOR THE NORTHWOOD MIXED USE DISTRICT BUILDING
 TYPE II SHALL BE AS FOLLOWS: (15) ALL AWNINGS SHALL BE
 CONSISTENT WITH THE ARCHITECTURE OF THE BUILDING AND
 SHALL MEET THE REQUIREMENTS BELOW:
 A. AWNINGS AT THE SIDEWALK LEVEL SHALL PROJECT A
 MINIMUM OF FOUR FEET FROM THE BUILDING FACADE AND HAVE
 A MINIMUM OF NINE FEET IN CLEARANCE FROM THE SIDEWALK
 LEVEL TO THE BOTTOM OF THE AWNING.
 B. AWNINGS ON STORIES ABOVE THE SIDEWALK LEVEL SHALL
 PROJECT A MINIMUM OF THREE FEET FROM THE BUILDING
 FACADE. VALANCES SHALL NOT EXCEED EIGHT INCHES IN
 HEIGHT.
 C. WAIVERS FROM THE AWNING REQUIREMENTS MAY BE GRANTED
 ADMINISTRATIVELY BY THE PLANNING DIRECTOR OR HIS/HER
 DESIGNEE PURSUANT TO MEETING THE WAIVER CRITERIA FOUND
 IN SUBSECTION 94-273(A)(2), IN ORDER TO MAINTAIN THE
 ARCHITECTURAL CHARACTER OF A STRUCTURE, OR IF SITE
 FEATURES, SUCH AS, BUT NOT LIMITED TO, UTILITY LINE
 POLES OR STREET TREES, RESTRICT THE APPLICANT FROM FULL
 COMPLIANCE.
  
 NOTE: A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-05-05 Cont ID  
Sent By swurafti Date 2009-04-22 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2009-04-22 Time 15:04 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-12 Cont ID  
Sent By shill Date 2009-03-12 Time 09:01 Rev Time 0.00
Received By shill Date 2009-03-12 Time 09:01 Sent To B
Notes
2009-03-12 09:02:10TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-31 Cont ID  
Sent By rmcdouga Date 2009-03-31 Time 08:50 Rev Time 0.00
Received By rmcdouga Date 2009-03-05 Time 13:32 Sent To  
Notes
2009-03-05 13:32:34TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2009-05-04 Cont ID  
Sent By rmcdouga Date 2009-05-05 Time 16:14 Rev Time 0.00
Received By mcruz Date 2009-05-04 Time 12:51 Sent To B
Notes
2009-05-04 12:59:10***COPY/LOGO ON AWNINGS SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
  
 ROUTED TO RMC FOR BLDG REVIEW.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-03-11 Cont ID  
Sent By mcruz Date 2009-03-11 Time 11:45 Rev Time 0.00
Received By mcruz Date 2009-03-11 Time 11:13 Sent To I
Notes
2009-03-11 11:35:41PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE THE LINEAR CLEARANCE FROM THE SIDEWALK LEVEL
 TO THE BOTTOM OF THE 1ST FLOOR AWNING. NOTE: MINIMUM
 CLEARANCE REQUIRED IS LISTED IN THE PROVISION BELOW.
  
 3. PROVIDE A DETAIL FOR EACH TYPE OF AWNING, EXAMPLE,
 LABEL EACH DESIGN "1ST FLOOR AWNING" AND "2ND FLOOR
 AWNING". ENSURE SAID AWNINGS MEET THE FOLLOWING CODE
 STANDARDS:
  
 PURSUANT TO THE CITY OF WEST PALM BEACH, ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-212(D)(15):
  
 A. ALL AWNINGS AT SIDEWALK LEVEL SHALL PROJECT A
 MINIMUM OF FOUR FEET FROM THE BUILDING FACADE AND HAVE
 A MINIMUM OF NINE FEET IN CLEARANCE FROM THE SIDEWALK
 LEVEL TO THE BOTTOM OF THE AWNING.
  
 B. AWNINGS ON STORIES ABOVE THE SIDEWALK LEVEL SHALL
 PROJECT A MINIMUM OF THREE FEET FROM THE BUILDING
 FACADE. VALANCES SHALL NOT EXCEED EIGHT INCHES IN
 HEIGHT.
  
 4. PLEASE PROVIDE THE DIMENSIONS OF THE COPY OR LOGO ON
 THE PROPOSED AWNINGS. NOTE: PURSUANT TO THE ZLDR,
 SECTION 94-212(E)(1): IF THE STOREFRONT USES AWNINGS,
 THE COPY OR LOGO ON THE VALANCE SHALL NOT EXCEED SIX
 INCHES IN HEIGHT AND SHALL BE CONSIDERED AS SQUARE
 FOOTAGE AGAINST THE ALLOWABLE BUILDING SIGNAGE.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  