Plan Review Details - Permit 09030005
Plan Review Stops For Permit 09030005
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-03-09 Cont ID  
Sent By rmcdouga Date 2009-03-09 Time 08:00 Rev Time 0.00
Received By rmcdouga Date 2009-03-09 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-04 Cont ID  
Sent By rmcdouga Date 2009-03-04 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2009-03-04 Time 13:51 Sent To  
Notes
2009-03-04 14:01:392007 W/2008 REVISIONS
 RE-ROOF
  
 DENIED BY BUILDING
  
 1) THE MAXIMUM DESIGN PRESSURE FOR THE TAMKO MODIFIED
 ROOFING SYSTEM IS TOO LOW FOR THE PERIMETER AND
 CORNERS. SUBMIT TWO COPIES OF ENHANCED FASTENING
 REQUIREMENTS FOR THE PERIMETER AND CORNER AREAS AS
 CALCULATED IN COMPLIANCE WITH RAS 117 AS REQUIRED BY
 GENERAL LIMITATION #7 ON PAGE 18 OF NOA 07-0730.03.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-06 Cont ID  
Sent By adarroug Date 2009-03-06 Time 10:00 Rev Time 0.00
Received By adarroug Date 2009-03-06 Time 10:00 Sent To B
Notes
2009-03-06 10:00:37TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-04 Cont ID  
Sent By rmcdouga Date 2009-03-04 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2009-03-03 Time 16:25 Sent To  
Notes
2009-03-03 16:27:41TO "RMCDOUGAL" DESK