Plan Review Details - Permit 09020621
Plan Review Stops For Permit 09020621
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-08-19 Cont ID  
Sent By shill Date 2009-08-19 Time 18:15 Rev Time 0.00
Received By shill Date 2009-08-19 Time 18:15 Sent To  
Notes
2009-08-19 18:23:38**PROVISO**PROVIDE LETTER FROM ENGINEER OF RECORD
 CONFIRMING REVIEW OF DELEGATED ENGINEERING FAC61G15
 **PROVISO**PROVIDE UPDATED VALUE
  
 REVISION, STRUCTURAL DETAILS (CONCRETE) S1-S33 PREPARED
 BY BRIDGE DESIGN ASSOCIATES
 REVISION, SP1, A1.1, A1.2, A2.1 PREPARED BY GS&P
 (SECURITY GATES)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-02 Cont ID  
Sent By shill Date 2009-06-02 Time 13:27 Rev Time 0.00
Received By shill Date 2009-06-02 Time 13:27 Sent To  
Notes
2009-06-02 13:56:40PROVISO
 AT FIRST INSPECTION, PROVIDE A LETTER FROM ENGINEER (M
 & N) STATING THAT DESIGN COMPLIES WITH ASCE7-02
 (PLANS STATE ASCE7-05, SHOULD BE DESIGNED TO ASCE7-02
 PER FBC 2004 CHAPTER 35)
  
 PER GABRIEL PERDOMO, M & N
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-03 Cont ID  
Sent By shill Date 2009-04-03 Time 15:59 Rev Time 0.00
Received By shill Date 2009-04-03 Time 15:59 Sent To  
Notes
2009-04-03 16:07:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. G003, DECLARE EXPOSURE CLASSIFICATION FBC1603.1.4.
  
 2. DESIGN IS TO BE IN ACCORDANCE WITH FBC2004 WITH 2007
 REVISIONS/SUPPLEMENTS, FS553, FBC1604.2. PLEASE DECLARE
 GOVERNING CODE ON THE PLAN AND CONFIRM COMPLIANCE.
  
 3. PILE AND PILE CAP DESIGN AND CONSTRUCTION TO COMPLY
 WITH FBC18; PLEASE CONFIRM COMPLIANCE AND NOTE DESIGN
 CRITERIA ON THE PLAN.
  
 4. PLANS STATE THAT THE DRAWINGS ARE 100% COMPLETE BUT
 "NOT FOR CONSTUCTION;" PLEASE CLARIFY; THIS NOTE IS
 TYPICALLY USED FOR PRELIMINARY DRAWINGS IN DESIGN
 PHASE.
  
 5. THE SOIL BORING INFORMATION IN THE PLAN IS NOT
 LEGIBLE. PLEASE PROVIDE THE ORIGINAL SOILS REPORTS; SEE
 FBC1808.2.2.4, 1808.2.2.
  
 6. ENGINEER IS TO INCLUDE A TITLE BLOCK ON ALL SIGNED
 AND SEALED SHEETS WITH ALL INFORMATION REQUIRED BY
 FAC61G15-23.002. SHEETS PREPARED BY JOHN DERUGERIS, PE
 DO NOT INCLUDE A TITLE BLOCK.
  
 7. PLEASE HAVE THE ENGINEER OF RECORD FOR THE STRUCTURE
 REVIEW THE DELEGATED ENGINEERING, FAC61G15-31.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-05-26 Cont ID  
Sent By btrobaug Date 2009-05-26 Time 14:31 Rev Time 0.00
Received By btrobaug Date 2009-05-15 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-07 Cont ID  
Sent By btrobaug Date 2009-04-07 Time 10:08 Rev Time 0.00
Received By btrobaug Date 2009-04-07 Time 10:08 Sent To  
Notes
2009-04-08 15:24:17 
  
  
  
 APPLICATION #09020621 ELECTRICAL PLAN REVIEW
 400 S. FLAGLER DRIVE 3/27/09
 WEST PALM BEACH, FL.
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED ON THE PLAN.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS AND NRTL
 LISTING FOR ALL LUMINAIRES, BOLLARDS, POLES AND UTILITY
 PEDESTALS.
  
 3} ALL SERVICES MUST COMPLY WITH 230.95 GROUND-FAULT
 PROTECTION OF EQUIPMENT
 GROUND-FAULT PROTECTION OF EQUIPMENT SHALL BE PROVIDED
 FOR SOLIDLY GROUNDED WYE ELECTRICAL SERVICES OF MORE
 THAN 150 VOLTS TO GROUND BUT NOT EXCEEDING 600 VOLTS
 PHASE-TO-PHASE FOR EACH SERVICE DISCONNECT RATED 1000
 AMPERES OR MORE. THE GROUNDED CONDUCTOR FOR THE SOLIDLY
 GROUNDED WYE SYSTEM SHALL BE CONNECTED DIRECTLY TO
 GROUND WITHOUT INSERTING ANY RESISTOR OR IMPEDANCE
 DEVICE.
 THE RATING OF THE SERVICE DISCONNECT SHALL BE
 CONSIDERED TO BE THE RATING OF THE LARGEST FUSE THAT
 CAN BE INSTALLED OR THE HIGHEST CONTINUOUS CURRENT TRIP
 SETTING FOR WHICH THE ACTUAL OVERCURRENT DEVICE
 INSTALLED IN A CIRCUIT BREAKER IS RATED OR CAN BE
 ADJUSTED. MAKE NOTE OF THIS ARTICLE ON SHEET E-300, OR
 SHEETS THAT THE SERVICE RISER DIAGRAMS ARE ON IF MOVED
 FROM THAT SHEET.
  
 4} THE LOCATION OF THE SERVICES WILL REQUIRE A
 DISCONNECT PER 225.31 & 32. LOCATE ALL ON THE PLANS.
  
 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 555.12 NEC.
 THE ???LOAD SCHEDULE??? ON SHEET E-300 DOES NOT
 INDICATE HOW THE DEMAND LOAD WAS CALCULATED.
  
 6} THE NOTE REGARDING THE 480 VOLT 3 PHASE FEEDER ON
 SHEET E-103 INCORRECTLY STATES #210G FOR THE EQUIPMENT
 GROUND. SEE 250.122 FOR SIZING.
  
 7} PER NFPA 303-2000, ARTICLE 3.3.1
 A BENCH MARK INDICATING THE ELECTRICAL DATUM PLANE OF
 THE LAND AREA SHALL BE PERMANENTLY LOCATED ON SHORE IN
 THE MARINA OR BOATYARD. INDICATE THE LOCATION ON THE
 PLANS.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-03-17 Cont ID  
Sent By dlauderm Date 2009-03-17 Time 13:45 Rev Time 0.00
Received By dlauderm Date 2009-03-17 Time 13:46 Sent To  
Notes
2009-03-17 13:45:24NO REVIEW REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-09-03 Cont ID  
Sent By mcarsill Date 2009-09-03 Time 11:29 Rev Time 0.00
Received By mcarsill Date 2009-09-02 Time 14:55 Sent To  
Notes
2009-09-03 11:29:09400 NORTH FLAGLER DRIVE
 09020621
 09020625
 09020628
 09020630
  
 1. ALL DOCK STANDPIPE SYSTEMS AND FIRE DEPARTMENT
 CONNECTIONS SHALL BE TESTED AT 200 PSIG FOR TWO HOURS.
  
 2. ALL HOSE VALVES SHALL BE EQUIPPED WITH THE 2 1/2 TO
 1 1/2 REDUCERS.
  
 3. ALL INSPECTIONS ARE SUBJECT TO FIELD INSPECTIONS AND
 APPROVAL.
  
 4. KNOX-BOXES SHALL BE INSTALLED AND OPERATIONAL PRIOR
 TO THE GATES BEING PLACED IN THE CLOSED POSITION.
  
 5. ALL DOCK STANDPIPE SYSTEMS SHALL BE PROPERLY
 SECURED.
  
 6. LOCKING CAPS ARE REQUIRED AT ALL FIRE DEPARTMENT
 CONNECTION LOCATIONS.
  
  
 APPROVED PROVISO;
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-06-01 Cont ID  
Sent By mcarsill Date 2009-06-01 Time 07:34 Rev Time 0.00
Received By mcarsill Date 2009-06-01 Time 07:26 Sent To  
Notes
2009-06-01 07:34:13THE FOLLOWING NOTES COVERS PERMIT # 09020621, 09020625,
 09020628, 09020630.
  
 1. PLEASE CORRECT DEFICIENCIES TO THE PLANS AS
 IDENTIFIED FROM THE CONSTRUCTION SERVICES DEPARTMENT.
  
 2. THE INSTALLATION OF THE DOCKS SHALL COMPLY WITH NFPA
 303.
  
 3. THE FUEL INSTALLATION TO COMPLY WITH NFPA 30.
  
 4. THE STANDPIPE SYSTEM SHALL BE EQUIPPED WITH MAIL
 THREADS AT THE HOSE VALVES ON EACH DOCK.
  
 5. ENTIRE INSTALLATION IS SUBJECT TO FIELD INSPECTION
 AND APPROVAL.
  
 6. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND
 AFTER CONSTRUCTION.
  
  
 APPROVED PROVISO:
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4776

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-03 Cont ID  
Sent By mcarsill Date 2009-04-03 Time 09:57 Rev Time 0.00
Received By mcarsill Date 2009-04-03 Time 09:01 Sent To  
Notes
2009-04-03 09:56:41PALM HARBOR MARINA RENOVATIONS
  
 MARINA RECONSTRUCTION INCLUDING FIXED ACCESS DOCKS,
 FLOATING DOCKS, GANGWAYS, AND WATERSIDE UTILITIES.
 PERMIT NUMBERS 09020621, 09020625, 09020628, 09020630,
  
 1. THE PLANS DO NOT ILLUSTRATE ANY NEW OR EXISTING FIRE
 HYDRANTS, FIRELINES THAT SUPPLY THE DOCKS, OR FIRE
 DEPARTMENT CONNECTIONS.
  
 2. EMERGENCY ACCESS IS TO BE PROVIDED THROUGH THE
 SECURITY FENCES. PLEASE EXPLAIN HOW THIS ACCESS WILL
 OCCUR.
  
 3. NOTE # 30 ON PAGE M-001 SHOULD BE FURTHER CLARIFIED.
 VEHICLULAR ACCESS MUST BE PROVIDED AND MAINTAINED FOR
 FIRE AND PARAMEDICAL ACCESS.
  
 4. EACH DOCK SHALL BE PROVIDED WITH A FIRE DEPARTMENT
 CONNECTION USED TO SUPPLY EACH DOCK. KNOX-BOX LOCKING
 CAPS ARE TO BE PROVIDED AT EACH FIRE DEPARTMENT
 CONNECTION.
  
 5. THE FIREHOSE STANDPIPE DEATILS ON PAGE M-501 SHALL
 BE PROVIDED WITH 2/12 TO 1/2 REDUCERS.
  
 6. DOES THE FIRE EXTINGUISHER CABINET DETAIL ON PAGE
 M-501 HAVE A HANDLE OR A BREAK GLASS ROD.
  
 7. PLEASE INDICATE LOCATIONS OF ANY WARNING SIGNS TO
 INCLUDE "NO SMOKING SIGNS" NEAR THE FUEL DISPENSING
 PUMPS. SMOKING WILL BE PROHIBITED IN THESE AREAS.
  
 8. PLEASE INDICATE COMMUNICATION SYSTEM EQUIPMENT THAT
 IS REQUIRED TO REPORT EMERGENCIES.
  
 9. DOCKS WILL NEED TO BE IDENTIFIED FOR EMERGENCY
 PURPOSES.
  
 10. AN EMERGENCY PLAN FOR THE DOCKS IS TO BE PREPARED
 AND SUBMITTED TO THIS OFFICE FOR REVIEW.
  
 11. DOCKS ARE TO COMPLY WITH NFPA 303.
  
 12. PLEASE ILLUSTRATE ON THE PLANS FIRE RESCUE ACCESS
 AND WIDTHS USED TO ACCESS THE WEST SIDES OF THE VARIOUS
 DOCKS.
  
 13. NO INFORMATION ON THE FUEL DISPENSING SYSTEM.
 INFORMATION NEEDS TO BE SUBMITTED FOR THE FUEL STORAGE,
 FUEL DISPENSING EQUIPMENTS, HOSES, EMERGENCY SHUT-OFF,
 AND ANY OTHER APPURTENANT EQUIPMENT.
  
 14. ALL LIGHT FIXTURES AND OTHER EQUIPMENT SHALL BE
 PROPERLY LISTED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-19 Cont ID  
Sent By lmartine Date 2009-08-19 Time 14:25 Rev Time 0.00
Received By lmartine Date 2009-08-19 Time 14:25 Sent To  
Notes
2009-08-19 14:30:32C-8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-05-15 Cont ID  
Sent By btrobaug Date 2009-05-15 Time 16:23 Rev Time 0.00
Received By btrobaug Date 2009-05-13 Time 15:21 Sent To  
Notes
2009-05-13 15:25:58C-28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-08 Cont ID  
Sent By rbrown Date 2009-04-08 Time 14:58 Rev Time 0.00
Received By rbrown Date 2009-03-03 Time 10:14 Sent To  
Notes
2009-03-03 10:14:12TO "COMM" BD#45

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-09-08 Cont ID  
Sent By kstevens Date 2009-09-08 Time 10:22 Rev Time 0.00
Received By kstevens Date 2009-08-20 Time 16:54 Sent To  
Notes
2009-09-08 10:23:06REVISIONS OK -- SHTS P-1 THRU P-5 REPLACING THE "M"
 SHEETS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-05-27 Cont ID  
Sent By kstevens Date 2009-05-27 Time 16:51 Rev Time 0.00
Received By kstevens Date 2009-05-27 Time 16:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-02 Cont ID  
Sent By kstevens Date 2009-04-02 Time 14:51 Rev Time 0.00
Received By kstevens Date 2009-04-02 Time 14:51 Sent To  
Notes
2009-04-02 15:06:45DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS PHM-001 THRU PHM-016. A TITLE BLOCK SHALL BE
 USED ON EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS
 AND LICENSE NUMBER OF THE ENGINEER OR IF APPLICABLE,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER, AND IF
 PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS. FAC
 61G15-23.002(2) & FS 471.025.
  
 2. ALL SHTS WITH MOFFATT & NICHOL TITLE BLOCKS. THE
 ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE,
 (3780 KILROY AIRPORT WAY LONG BEACH CALIFORNIA), DOES
 NOT REFLECT THE ADDRESS IN THE TITLE BLOCKS, (1509 W.
 SWANN AVE. TAMPA FLORIDA). FAC 61G15-23.002(2) & FS
 471.025. PLEASE UPDATE TITLE BLOCKS OR THE DBPR WEBSITE
 PRIOR TO RESUBMITTING TO THE CITY WPB FOR REVIEW. (THE
 ADDRESS ON THE DBPR WEBSITE CAN BE ADDED TO THE TITLE
 BLOCK OF EACH SHEET TO COMPLY WITH THIS REQUIREMENT).
  
 3. SHT G-003 CODE DESIGN CRITERIA SHALL INCLUDE THE
 FBC-2004 WITH 2007 REVISIONS. SECTION 106.1.1.
  
 4. THE WATER SUPPLY TO THE DOCKS SHALL BE PROTECTED
 FROM BACKFLOW PER SECTION 608.13.2. PLEASE INDICATE THE
 RPZV BACKFLOW LOCATION FOR EACH DOCK OR IF ALL DOCKS
 ARE CONNECTED TO ONE METER INDICATE ON PLANS THE
 LOCATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-09-14 Cont ID  
Sent By aaponte Date 2009-09-14 Time 10:37 Rev Time 0.00
Received By aaponte Date 2009-09-14 Time 10:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-03-18 Cont ID  
Sent By aaponte Date 2009-03-18 Time 11:39 Rev Time 0.00
Received By aaponte Date 2009-03-18 Time 11:39 Sent To  
Notes
***NONE***