Plan Review Stops For Permit 09020621 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2009-08-19 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-08-19 |
Time |
18:15 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-08-19 |
Time |
18:15 |
Sent To |
|
|
Notes |
2009-08-19 18:23:38 | **PROVISO**PROVIDE LETTER FROM ENGINEER OF RECORD | | CONFIRMING REVIEW OF DELEGATED ENGINEERING FAC61G15 | | **PROVISO**PROVIDE UPDATED VALUE | | | | REVISION, STRUCTURAL DETAILS (CONCRETE) S1-S33 PREPARED | | BY BRIDGE DESIGN ASSOCIATES | | REVISION, SP1, A1.1, A1.2, A2.1 PREPARED BY GS&P | | (SECURITY GATES) | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2009-06-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-06-02 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-06-02 |
Time |
13:27 |
Sent To |
|
|
Notes |
2009-06-02 13:56:40 | PROVISO | | AT FIRST INSPECTION, PROVIDE A LETTER FROM ENGINEER (M | | & N) STATING THAT DESIGN COMPLIES WITH ASCE7-02 | | (PLANS STATE ASCE7-05, SHOULD BE DESIGNED TO ASCE7-02 | | PER FBC 2004 CHAPTER 35) | | | | PER GABRIEL PERDOMO, M & N | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-04-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-04-03 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-04-03 |
Time |
15:59 |
Sent To |
|
|
Notes |
2009-04-03 16:07:46 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. G003, DECLARE EXPOSURE CLASSIFICATION FBC1603.1.4. | | | | 2. DESIGN IS TO BE IN ACCORDANCE WITH FBC2004 WITH 2007 | | REVISIONS/SUPPLEMENTS, FS553, FBC1604.2. PLEASE DECLARE | | GOVERNING CODE ON THE PLAN AND CONFIRM COMPLIANCE. | | | | 3. PILE AND PILE CAP DESIGN AND CONSTRUCTION TO COMPLY | | WITH FBC18; PLEASE CONFIRM COMPLIANCE AND NOTE DESIGN | | CRITERIA ON THE PLAN. | | | | 4. PLANS STATE THAT THE DRAWINGS ARE 100% COMPLETE BUT | | "NOT FOR CONSTUCTION;" PLEASE CLARIFY; THIS NOTE IS | | TYPICALLY USED FOR PRELIMINARY DRAWINGS IN DESIGN | | PHASE. | | | | 5. THE SOIL BORING INFORMATION IN THE PLAN IS NOT | | LEGIBLE. PLEASE PROVIDE THE ORIGINAL SOILS REPORTS; SEE | | FBC1808.2.2.4, 1808.2.2. | | | | 6. ENGINEER IS TO INCLUDE A TITLE BLOCK ON ALL SIGNED | | AND SEALED SHEETS WITH ALL INFORMATION REQUIRED BY | | FAC61G15-23.002. SHEETS PREPARED BY JOHN DERUGERIS, PE | | DO NOT INCLUDE A TITLE BLOCK. | | | | 7. PLEASE HAVE THE ENGINEER OF RECORD FOR THE STRUCTURE | | REVIEW THE DELEGATED ENGINEERING, FAC61G15-31. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2009-05-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-05-26 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-05-15 |
Time |
16:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-04-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-04-07 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-04-07 |
Time |
10:08 |
Sent To |
|
|
Notes |
2009-04-08 15:24:17 | | | | | | | | | APPLICATION #09020621 ELECTRICAL PLAN REVIEW | | 400 S. FLAGLER DRIVE 3/27/09 | | WEST PALM BEACH, FL. | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | OTHERWISE NOTED. | | | | 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | DESIGNED ON THE PLAN. | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS AND NRTL | | LISTING FOR ALL LUMINAIRES, BOLLARDS, POLES AND UTILITY | | PEDESTALS. | | | | 3} ALL SERVICES MUST COMPLY WITH 230.95 GROUND-FAULT | | PROTECTION OF EQUIPMENT | | GROUND-FAULT PROTECTION OF EQUIPMENT SHALL BE PROVIDED | | FOR SOLIDLY GROUNDED WYE ELECTRICAL SERVICES OF MORE | | THAN 150 VOLTS TO GROUND BUT NOT EXCEEDING 600 VOLTS | | PHASE-TO-PHASE FOR EACH SERVICE DISCONNECT RATED 1000 | | AMPERES OR MORE. THE GROUNDED CONDUCTOR FOR THE SOLIDLY | | GROUNDED WYE SYSTEM SHALL BE CONNECTED DIRECTLY TO | | GROUND WITHOUT INSERTING ANY RESISTOR OR IMPEDANCE | | DEVICE. | | THE RATING OF THE SERVICE DISCONNECT SHALL BE | | CONSIDERED TO BE THE RATING OF THE LARGEST FUSE THAT | | CAN BE INSTALLED OR THE HIGHEST CONTINUOUS CURRENT TRIP | | SETTING FOR WHICH THE ACTUAL OVERCURRENT DEVICE | | INSTALLED IN A CIRCUIT BREAKER IS RATED OR CAN BE | | ADJUSTED. MAKE NOTE OF THIS ARTICLE ON SHEET E-300, OR | | SHEETS THAT THE SERVICE RISER DIAGRAMS ARE ON IF MOVED | | FROM THAT SHEET. | | | | 4} THE LOCATION OF THE SERVICES WILL REQUIRE A | | DISCONNECT PER 225.31 & 32. LOCATE ALL ON THE PLANS. | | | | 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 555.12 NEC. | | THE ???LOAD SCHEDULE??? ON SHEET E-300 DOES NOT | | INDICATE HOW THE DEMAND LOAD WAS CALCULATED. | | | | 6} THE NOTE REGARDING THE 480 VOLT 3 PHASE FEEDER ON | | SHEET E-103 INCORRECTLY STATES #210G FOR THE EQUIPMENT | | GROUND. SEE 250.122 FOR SIZING. | | | | 7} PER NFPA 303-2000, ARTICLE 3.3.1 | | A BENCH MARK INDICATING THE ELECTRICAL DATUM PLANE OF | | THE LAND AREA SHALL BE PERMANENTLY LOCATED ON SHORE IN | | THE MARINA OR BOATYARD. INDICATE THE LOCATION ON THE | | PLANS. | | | | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH | | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM | | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO | | REVIEW COMMENTS IN WRITING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2009-03-17 |
|
|
Cont ID |
|
Sent By |
dlauderm |
Date |
2009-03-17 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
dlauderm |
Date |
2009-03-17 |
Time |
13:46 |
Sent To |
|
|
Notes |
2009-03-17 13:45:24 | NO REVIEW REQUIRED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2009-09-03 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-09-03 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-09-02 |
Time |
14:55 |
Sent To |
|
|
Notes |
2009-09-03 11:29:09 | 400 NORTH FLAGLER DRIVE | | 09020621 | | 09020625 | | 09020628 | | 09020630 | | | | 1. ALL DOCK STANDPIPE SYSTEMS AND FIRE DEPARTMENT | | CONNECTIONS SHALL BE TESTED AT 200 PSIG FOR TWO HOURS. | | | | 2. ALL HOSE VALVES SHALL BE EQUIPPED WITH THE 2 1/2 TO | | 1 1/2 REDUCERS. | | | | 3. ALL INSPECTIONS ARE SUBJECT TO FIELD INSPECTIONS AND | | APPROVAL. | | | | 4. KNOX-BOXES SHALL BE INSTALLED AND OPERATIONAL PRIOR | | TO THE GATES BEING PLACED IN THE CLOSED POSITION. | | | | 5. ALL DOCK STANDPIPE SYSTEMS SHALL BE PROPERLY | | SECURED. | | | | 6. LOCKING CAPS ARE REQUIRED AT ALL FIRE DEPARTMENT | | CONNECTION LOCATIONS. | | | | | | APPROVED PROVISO; | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2009-06-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-06-01 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-06-01 |
Time |
07:26 |
Sent To |
|
|
Notes |
2009-06-01 07:34:13 | THE FOLLOWING NOTES COVERS PERMIT # 09020621, 09020625, | | 09020628, 09020630. | | | | 1. PLEASE CORRECT DEFICIENCIES TO THE PLANS AS | | IDENTIFIED FROM THE CONSTRUCTION SERVICES DEPARTMENT. | | | | 2. THE INSTALLATION OF THE DOCKS SHALL COMPLY WITH NFPA | | 303. | | | | 3. THE FUEL INSTALLATION TO COMPLY WITH NFPA 30. | | | | 4. THE STANDPIPE SYSTEM SHALL BE EQUIPPED WITH MAIL | | THREADS AT THE HOSE VALVES ON EACH DOCK. | | | | 5. ENTIRE INSTALLATION IS SUBJECT TO FIELD INSPECTION | | AND APPROVAL. | | | | 6. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND | | AFTER CONSTRUCTION. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4776 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2009-04-03 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-04-03 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-04-03 |
Time |
09:01 |
Sent To |
|
|
Notes |
2009-04-03 09:56:41 | PALM HARBOR MARINA RENOVATIONS | | | | MARINA RECONSTRUCTION INCLUDING FIXED ACCESS DOCKS, | | FLOATING DOCKS, GANGWAYS, AND WATERSIDE UTILITIES. | | PERMIT NUMBERS 09020621, 09020625, 09020628, 09020630, | | | | 1. THE PLANS DO NOT ILLUSTRATE ANY NEW OR EXISTING FIRE | | HYDRANTS, FIRELINES THAT SUPPLY THE DOCKS, OR FIRE | | DEPARTMENT CONNECTIONS. | | | | 2. EMERGENCY ACCESS IS TO BE PROVIDED THROUGH THE | | SECURITY FENCES. PLEASE EXPLAIN HOW THIS ACCESS WILL | | OCCUR. | | | | 3. NOTE # 30 ON PAGE M-001 SHOULD BE FURTHER CLARIFIED. | | VEHICLULAR ACCESS MUST BE PROVIDED AND MAINTAINED FOR | | FIRE AND PARAMEDICAL ACCESS. | | | | 4. EACH DOCK SHALL BE PROVIDED WITH A FIRE DEPARTMENT | | CONNECTION USED TO SUPPLY EACH DOCK. KNOX-BOX LOCKING | | CAPS ARE TO BE PROVIDED AT EACH FIRE DEPARTMENT | | CONNECTION. | | | | 5. THE FIREHOSE STANDPIPE DEATILS ON PAGE M-501 SHALL | | BE PROVIDED WITH 2/12 TO 1/2 REDUCERS. | | | | 6. DOES THE FIRE EXTINGUISHER CABINET DETAIL ON PAGE | | M-501 HAVE A HANDLE OR A BREAK GLASS ROD. | | | | 7. PLEASE INDICATE LOCATIONS OF ANY WARNING SIGNS TO | | INCLUDE "NO SMOKING SIGNS" NEAR THE FUEL DISPENSING | | PUMPS. SMOKING WILL BE PROHIBITED IN THESE AREAS. | | | | 8. PLEASE INDICATE COMMUNICATION SYSTEM EQUIPMENT THAT | | IS REQUIRED TO REPORT EMERGENCIES. | | | | 9. DOCKS WILL NEED TO BE IDENTIFIED FOR EMERGENCY | | PURPOSES. | | | | 10. AN EMERGENCY PLAN FOR THE DOCKS IS TO BE PREPARED | | AND SUBMITTED TO THIS OFFICE FOR REVIEW. | | | | 11. DOCKS ARE TO COMPLY WITH NFPA 303. | | | | 12. PLEASE ILLUSTRATE ON THE PLANS FIRE RESCUE ACCESS | | AND WIDTHS USED TO ACCESS THE WEST SIDES OF THE VARIOUS | | DOCKS. | | | | 13. NO INFORMATION ON THE FUEL DISPENSING SYSTEM. | | INFORMATION NEEDS TO BE SUBMITTED FOR THE FUEL STORAGE, | | FUEL DISPENSING EQUIPMENTS, HOSES, EMERGENCY SHUT-OFF, | | AND ANY OTHER APPURTENANT EQUIPMENT. | | | | 14. ALL LIGHT FIXTURES AND OTHER EQUIPMENT SHALL BE | | PROPERLY LISTED. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2009-08-19 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-08-19 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-08-19 |
Time |
14:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-05-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-05-15 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-05-13 |
Time |
15:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2009-04-08 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2009-04-08 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2009-03-03 |
Time |
10:14 |
Sent To |
|
|
Notes |
2009-03-03 10:14:12 | TO "COMM" BD#45 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2009-09-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-09-08 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-08-20 |
Time |
16:54 |
Sent To |
|
|
Notes |
2009-09-08 10:23:06 | REVISIONS OK -- SHTS P-1 THRU P-5 REPLACING THE "M" | | SHEETS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2009-05-27 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-05-27 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-05-27 |
Time |
16:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2009-04-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-04-02 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-04-02 |
Time |
14:51 |
Sent To |
|
|
Notes |
2009-04-02 15:06:45 | DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. SHTS PHM-001 THRU PHM-016. A TITLE BLOCK SHALL BE | | USED ON EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS | | AND LICENSE NUMBER OF THE ENGINEER OR IF APPLICABLE, | | THE NAME AND LICENSE NUMBER OF THE ENGINEER, AND IF | | PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING | | BUSINESS, THE NAME, ADDRESS AND CERTIFICATE OF | | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS. FAC | | 61G15-23.002(2) & FS 471.025. | | | | 2. ALL SHTS WITH MOFFATT & NICHOL TITLE BLOCKS. THE | | ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE, | | (3780 KILROY AIRPORT WAY LONG BEACH CALIFORNIA), DOES | | NOT REFLECT THE ADDRESS IN THE TITLE BLOCKS, (1509 W. | | SWANN AVE. TAMPA FLORIDA). FAC 61G15-23.002(2) & FS | | 471.025. PLEASE UPDATE TITLE BLOCKS OR THE DBPR WEBSITE | | PRIOR TO RESUBMITTING TO THE CITY WPB FOR REVIEW. (THE | | ADDRESS ON THE DBPR WEBSITE CAN BE ADDED TO THE TITLE | | BLOCK OF EACH SHEET TO COMPLY WITH THIS REQUIREMENT). | | | | 3. SHT G-003 CODE DESIGN CRITERIA SHALL INCLUDE THE | | FBC-2004 WITH 2007 REVISIONS. SECTION 106.1.1. | | | | 4. THE WATER SUPPLY TO THE DOCKS SHALL BE PROTECTED | | FROM BACKFLOW PER SECTION 608.13.2. PLEASE INDICATE THE | | RPZV BACKFLOW LOCATION FOR EACH DOCK OR IF ALL DOCKS | | ARE CONNECTED TO ONE METER INDICATE ON PLANS THE | | LOCATION. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2009-09-14 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2009-09-14 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2009-09-14 |
Time |
10:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2009-03-18 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2009-03-18 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2009-03-18 |
Time |
11:39 |
Sent To |
|
|
Notes |
|
|