Plan Review Details - Permit 09020618
Plan Review Stops For Permit 09020618
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2009-04-07 Cont ID  
Sent By btrobaug Date 2009-04-07 Time 13:15 Rev Time 0.00
Received By btrobaug Date 2009-04-07 Time 13:08 Sent To FIRE
Notes
2009-04-07 13:15:29 
  
  
 ALL WORK TO BE DONE UNDER THIS PERMIT IS REFERRED TO AS
 UTILITY WITH SITE LIGHTING TO REMAIN./WRT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-03-18 Cont ID  
Sent By dlauderm Date 2009-03-18 Time 10:00 Rev Time 0.00
Received By dlauderm Date 2009-03-17 Time 14:42 Sent To E
Notes
2009-03-18 10:05:09APPROVED. NEEDS, FIRE AND ELECRTICAL REVIEW. SENT TO
 BILL TROBRAUGH FOR ELECTRICAL REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-04-08 Cont ID  
Sent By mcarsill Date 2009-04-08 Time 09:17 Rev Time 0.00
Received By mcarsill Date 2009-04-08 Time 09:04 Sent To  
Notes
2009-04-08 09:17:26400 NORTH FLAGLER DRIVE
 UPLAND SITE CIVIL AND UNDERGROUND UTILITY WORK
 PERMIT # 09020618
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR THE REMOVAL
 OF THE EXISTING UNDERGROUND FUEL TANKS STATED TO BE
 REMOVED AS ILLUSTRATED ON PAGE C-5.
  
 2. THE EXISTING FIRE DEPARTMENT CONNECTION PLANNED TO
 BE REMOVED ON PAGE C-5 SHALL NOT BE PART OF THE
 BUILDINGS FIRE PROTECTION SYSTEM.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE PROPOSED UNDEGRROUND FUEL TANK
 ILLUSTRATED ON PAGE C-7. THE FUEL TANK INSTALLATION ALL
 APPURETANT EQUIPMENT SHALL COMPLY WITH NFPA 30.
  
 4. THE PROPOSED EIGHT INCH FIRE LINE SHALL BE INSTALLED
 IN ACCORDANCE WITH NFPA 24, THE STANDARD FOR FIRE
 SERVICE MAINS AND THEIR APPURTENANCES. THE FIRE LINE
 AND FIRE DEPARTMENT CONNECTIONS SHALL BE PROPERLY
 PRESSURE TESTED FOR TWO HOURS AT 200 PSIG.
  
 5. ADDITIONAL PLANS WILL NEED TO BE SUBMITTED FOR THE
 FIRE PROTECTION EQUIPMENT PLANNED TO BE INSTALLED FOR
 THE INDIVIDUAL DOCKS.
  
 6. THE PROPOSED FIRE LANE BETWEEN THE DOCKS AND THE
 BUILDINGS SHALL BE ABLE TO SUPPORT THE WEIGHT OF FIRE
 AND PARAMEDICAL EQUIPMENT. THE MINIMUM OF 32 TONS IS
 REQUIRED.
  
 7. THE FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED
 WITH KNOX-BOX LOCKING CAPS. APPLICATIONS FOR THESE
 DEVICES CAN BE OBTAINED FROM WEST PALM BEACH FIRE
 RESCUE BETWEEN THE HOURS OF 8 TO 5.
  
 8. THE BACKFLOW PREVENTION DEVICES USED TO CONTROL THE
 FIRE-LINE SHALL BE CHAINED AND LOCKED TO PREVENT
 TAMPERING.
  
 9. THE FIRE DEPARTMENT CONNECTION FOR THE SOUTHERNMOST
 DOCK APPEARS TO BE FACING THE WRONG DIRECTION.
  
 10. FIRE AND PARAMEDICAL ACCESS SHALL BE MAINTAINED
 DURING THE COURSE OF THE PROJECT SHOULD AN EMERGENCY
 RESPONSE BECOME NECESSARY.
  
 APPROVED PROVSIO:
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-16 Cont ID  
Sent By adarroug Date 2009-03-16 Time 10:17 Rev Time 0.00
Received By adarroug Date 2009-03-16 Time 10:17 Sent To ENG
Notes
2009-03-16 10:18:08TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-08 Cont ID  
Sent By lmartine Date 2009-04-08 Time 14:16 Rev Time 0.00
Received By lmartine Date 2009-03-02 Time 11:28 Sent To  
Notes
2009-03-02 11:28:16TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2009-03-13 Cont ID  
Sent By aaponte Date 2009-03-13 Time 16:29 Rev Time 0.00
Received By aaponte Date 2009-03-13 Time 16:02 Sent To  
Notes
***NONE***