Plan Review Details - Permit 09020580
Plan Review Stops For Permit 09020580
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-05 Cont ID  
Sent By lmartine Date 2009-05-05 Time 10:36 Rev Time 0.00
Received By lmartine Date 2009-05-05 Time 10:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-15 Cont ID  
Sent By shill Date 2009-04-15 Time 13:57 Rev Time 0.00
Received By shill Date 2009-04-15 Time 13:57 Sent To  
Notes
2009-04-15 13:58:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471. AS DISCUSSED, ENGINEERING IS NOT REQUIRED IN
 THIS CASE BUT IF PREPARED BY AN ENGINEER, MUST BE AN
 ORIGINAL SIGNED AND SEALED DOCUMENT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-04-06 Cont ID  
Sent By btrobaug Date 2009-04-06 Time 11:51 Rev Time 0.00
Received By btrobaug Date 2009-04-06 Time 11:41 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2009-05-28 Cont ID  
Sent By kstevens Date 2009-05-28 Time 09:17 Rev Time 0.00
Received By kstevens Date 2009-05-28 Time 09:17 Sent To  
Notes
2009-05-28 09:17:40GAS REVISION OK

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2009-05-20 Cont ID  
Sent By kstevens Date 2009-05-20 Time 15:50 Rev Time 0.00
Received By kstevens Date 2009-05-20 Time 15:50 Sent To  
Notes
2009-05-20 16:00:26REVISION DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE ISOMETRIC INDICATES 1 FT FROM THE
 METER TO THE HORIZONTAL UNDERGROUND P.E. PIPE. THE
 MINIMUM BURIAL DEPTH FOR UNDERGROUND PIPE IS 1 FT.
 PLEASE INDICATE THE MEASUREMENT FROM THE GROUND TO THE
 OUTLET OF THE METER. SECTION G2415.9, (404.9).
  
 2. THE ISOMETRIC SHOWS A 3/4" TO 1/2" REDUCER AT GROUND
 LEVEL. THE PIPING SHALL BE FULL SIZE THRU THE SHUT OFF
 VALVE. TABLE 402.4(20).
  
 3. THE ISOMETRIC SHOW THE PIPING TO BE 3/4". PER TABLE
 402.4(20) FOR 20 FT THE MINIMUM PIPE SIZE FOR 294,000
 BTU SHALL BE 1".
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-05-04 Cont ID  
Sent By kstevens Date 2009-05-04 Time 14:27 Rev Time 0.00
Received By kstevens Date 2009-05-04 Time 14:27 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-04-15 Cont ID  
Sent By kstevens Date 2009-04-15 Time 10:06 Rev Time 0.00
Received By kstevens Date 2009-04-15 Time 10:06 Sent To B
Notes
2009-04-15 10:52:38DENIED
 REFERENCE;
 FBC-2004 FUEL GAS/RESIDENTIAL
  
 1. CONFLICTING INFORMATION SUBMITTED. ON THE RISER
 DIAGRAM SUBMITTED FOR THE GAS PERMIT THERE IS INDICATED
 AN EXISTING GAS METER, BUT ON THE ELECTRICAL SHEET WITH
 THE LOAD CALCULATION THERE IS INDICATED A NEW GAS
 METER. PLEASE CLARIFY. IF THERE IS AN EXISTING GAS
 METER AND EXISTING GAS PIPING THEN THE TOTAL BTU LOAD
 OF THE EXISTING GAS PIPING AND DISTANCE TO THE MOST
 REMOTE OUTLET IN THE SYSTEM SHALL BE INDICATED ON THE
 PLANS. SECTIONS 402.4.1 OR G2413.4.1.
  
 2. PIPE MATERIAL IS INDICATED AS GALVANIZED. AS
 GALVANIZED PIPE IS NOT APPROVED UNDERGROUND PLEASE
 INDICATE IF THE PIPING WILL BE ABOVE THE GROUND. IF
 UNDERGROUND THEN THE PIPING SHALL BE FACTORY WRAPPED.
 SECTIONS 404.8, 404.8.2. & G2415.8, G2415.8.2.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). -- BTU LOAD IS INDICATED AS 250,000 BTU BUT
 THE MANUF. INFORMATION INDICATES THE BTU LOAD AS
 294,000. PLEASE CORRELATE. SECTIONS 402.2 & G24.13.2.
  
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- TABLE 402.4(24)
 SUBMITTED IS INDICATED AS 11.0 INCH WC BUT THE
 ISOMETRIC SUBMITTED SHOWS A 2ND STAGE REGULATOR. PLEASE
 CLARIFY. ALSO THE TABLE SUBMITTED IS FOR LP GAS AND THE
 PLANS INDICATE NATURAL GAS. PLEASE CLARIFY.
  
 5. A LISTED SHUT OFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTIONS 409.4
 & G2420.4.
  
 6. SUBMIT THE MANUF. SPECIFICATIONS FOR THE 2ND STAGE
 REGULATOR. REGULATOR SHALL INDICATE A LISTING, SHOW
 MODEL NUMBER AND SHOW OUTLET LOAD CAPACITY. SECTIONS
 410.2 & G2421.2.
  
 ****INFORMATIONAL**** THE LICENSE NUMBER 24451 IS FOR
 SALES OF GAS GENERATORS ONLY. PLEASE INDICATE THE
 LICENSE REQUIRED FOR GAS PIPE INSTALLATION, 24513 ON
 FUTURE APPLICATIONS FOR GAS PERMITS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcdouga Date 2009-05-15 Time 11:39 Sent To  
Notes
2009-05-15 11:40:05GAS REVISION TO KEN STEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-22 Cont ID  
Sent By swurafti Date 2009-04-22 Time 13:06 Rev Time 0.00
Received By swurafti Date 2009-04-22 Time 13:06 Sent To P
Notes
2009-04-22 13:06:23TO "KSTEVENS" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-04 Cont ID  
Sent By adarroug Date 2009-03-04 Time 10:45 Rev Time 0.00
Received By adarroug Date 2009-03-04 Time 10:45 Sent To E
Notes
2009-03-04 10:45:29TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-15 Cont ID  
Sent By shill Date 2009-04-15 Time 13:58 Rev Time 0.00
Received By shill Date 2009-02-27 Time 16:58 Sent To  
Notes
2009-02-27 16:58:09TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2009-03-03 Cont ID  
Sent By mcruz Date 2009-03-03 Time 13:38 Rev Time 0.00
Received By mcruz Date 2009-03-03 Time 13:37 Sent To I
Notes
***NONE***