Plan Review Details - Permit 09020579
Plan Review Stops For Permit 09020579 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-04-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-04-02 |
Time |
17:06 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-04-02 |
Time |
17:06 |
Sent To |
|
|
Notes |
2009-04-02 17:27:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. PROVIDE DIMENSIONS OF PROPOSED SHED TO PROPERTY | | LINES, FBC601. | | | | 2. DECLARE OCCUPANCY CLASSIFICATION, FBC CHAPTER 3. THE | | SHED PLANS DECLARE THIS STRUCTURE AS RESIDENTIAL LAWN | | STORAGE; THIS DOES NOT APPEAR TO BE APPLICABLE FOR THIS | | PROJECT. | | | | 3. DECLARE OCCUPANT LOAD, FBC CHAPTER 10. | | | | 4. PLANS SHOW THIS AS ONE PARCEL; PAPA SHOWS THIS AS | | THREE SEPARATE PARCELS. IF THIS IS THE CASE, EACH | | PARCEL SHOULD HAVE A SEPARATE PERMIT (OTHERWISE, PLEASE | | PROVIDE EVIDENCE THAT THESE THREE PARCELS HAVE BEEN | | COMBINED INTO ONE PARCEL). PLEASE SEE COMMENT 1; THIS | | WOULD BE APPLICABLE TO THE PROPERTY LINE OF THE PARCEL | | ON WHICH THE SHED WILL BE LOCATED, NOT THE ADJACENT | | PARCEL INCLUDED IN THIS PROJECT. | | | | 5. PROVIDE A DETAIL FOR THE PROPOSED WALL. | | | | 6. SHOW ACCESSIBLE ROUTE AS DESCRIBED IN | | FBC11-4.1.2(1), INCLUDING ACCESSIBILITY AT THE BUILDING | | ENTRANCE. | | | | 7. SEE COMMENT 4. FBC1002, SEE DEFINITION OF EXIT AND | | PUBLIC WAY. IT APPEARS THAT NO EXITING TO THE PUBLIC | | WAY IS PROVIDED FROM THE PROPOSED STRUCTURE WITHOUT | | CROSSING OVER OTHER PARCELS. PLEASE ADDRESS. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-03-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-03-26 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-03-26 |
Time |
16:49 |
Sent To |
|
|
Notes |
2009-03-26 16:49:42 | ** DENIED REVIEW ** | | | | 1) NOTE: PLEASE SEE THE ADDRESS LOCATION ON PLANS NEEDS | | TO CORRELATE WITH THE LOCATION AS APPLIED. THE PLANS | | CALL FOR AVON RD. HOWEVER ACTUAL LOCATION IS 425 | | BELVEDERE RD. | | | | 2) NOTE: RISER INDICATES AN EQUIPMENT GROUNDING | | CONDUCTOR FROM METER TO MAIN. THIS IS NOT PERMITTED PER | | 250.6,250.24 | | | | 3) NOTE: THE SUBMITTED LOAD CALCULATIONS DO NOT MEET | | THE MINIMUM NEC 220 REQUIREMENTS. PLEASE SEE NEC | | 220.12,220.14,220.44, 220.42 ETC | | PLEASE ALSO BE SURE TO SEE 215.3,230.42 ETC FOR ALL | | CONTINUOUS LOADS WHICH ARE REQUIRED TO BE SHOWN AT | | 125%. | | | | 3) NOTE: PLEASE BE SURE TO COORDINATE THE PANEL | | SCHEDULE AND LOAD CALCULATIONS. SOME EXAMPLES OF ITEMS | | WHICH DO NOT COORDINATE IS POOL PUMP, WATER COOLER/ | | BOTH DO THESE ARE NOT ON PANEL SCHEDULES. SOME ITEMS ON | | SCHEDULE NOT IN LOAD CALCULATIONS ARE SPRINKLER PUMP. | | 408.4, 220. | | | | 4) NOTE: PLEASE SEE SOME LIGHTS ON PLANS NOT ON ANY | | CONTROL OR CIRCUIT. THIS WAS REDLINED ON ONE COPY. | | PLEASE SEE 408.4, 310.16, 220 ETC FOR MINIMUMS. | | | | 5) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.4 FOR REQUIRED | | EXTERIOR LIGHTING CONTROLS. MAY NOT USE STANDARD SINGLE | | POLE SWITCHES. | | | | 6) NOTE: PLEASE PROVIDE PRESCRIPTIVE SPACE PERFORMANCE | | LEVELS PER 13-415.2.ABC.1.1, .1.2. PLEASE SEE | | 13-415.2.B.2 FOR EXTERIOR OF BUILDING PERFORMANCE | | LEVELS. | | | | 7) NOTE: PLEASE PROVIDE INFORMATION ON WHAT THE *E* ON | | THE PLANS IS. THIS IS LOCATED ON THE SHED PLANS. IS | | THIS AN EXIT SIGN? | | IF SO THE SYMBOL LEGEND DOES NOT INDICATE THIS SYMBOL | | AND THERE IS NOT CIRCUIT SHOWN. PLEASE SEE 700.12F FOR | | CIRCUITING IF INDEED AN EXIT SIGN OR SOME SORT. | | | | 8) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL EQUIPMENT | | PER 110.9. ALL SERVICE EQUIPMENT AND BREAKERS SHALL BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | | 9) NOTE: PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION | | PER CHAPTER 3 OF THE FBC. | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | ** IMPORTANT ** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | ** IMPORTANT ** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2009-04-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-04-14 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-04-14 |
Time |
09:13 |
Sent To |
|
|
Notes |
2009-04-14 10:01:40 | *****UNSAT***** | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | OF EACH SUBMITTED PLAN SHEET. | | | | 2. DISPLAY/SHOW THE NUMERICAL ADDRESS OF THE BUILDING | | ON THE APPROPIATE EXTERIOR ELEVATION VISIBLE FROM | | BELVEDERE ROAD. AS PER WEST PALM BEACH CODE, THE | | ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND | | NO LESS THAN 1" IN WIDTH/STROKE. IN THE EVENT THAT THE | | VISIBILITY OF THE ADDRESS IS NOT PLAINLY VISIBLE FROM | | THE ROADWAY, A MARKEE AND/OR SIGN POST WITH THE ADDRESS | | WILL BE REQUIRED IN ADDITION TO THE ADDRESS ON THE | | BUILDING. | | | | 3. LANDSCAPING AND THE LIKE SUCH OPERATIONS SHALL NOT | | OBSTRUCT A FIRE HYDRANT OR FIRE PROTECTION APPLIANCE | | AND HINDER OR PREVENT ITS IMMEDIATE USE BY THE FIRE | | PERSONNEL. SUCH FIRE HYDRANT OR FIRE PROTECTION | | APPLIANCE SHALL BE MAINTAINED READILY VISIBLE AT ALL | | TIMES. | | | | 4. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | EXTINGUISHER LOCATED INSIDE THE STRUCTURE. | | | | 5. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | REFERENCED. | | | | 6. BASED ON THE ASSUMPTION THAT THIS STRUCTURE IS A | | STORAGE OCCUPANCY, CLASSIFY THE MATERIALS TO BE STORED | | AS LOW HAZARD, ORDINARY HAZARD, OR HIGH HAZARD. | | | | 7. ON SHEET A04, A SMOKE DETECTOR (SD) IS SHOWN IN THE | | ELECTRICAL FLOOR PLAN. IS THIS DEVICE A SMOKE DETECTOR | | OR A SMOKE ALARM (SA)? PLEASE BE ADVISED THAT A SMOKE | | DETECTOR IS TIED TO THE BUILDING'S FIRE ALARM SYSTEM | | WHEREAS A SMOKE DETECTOR ALERTS THE OCCUPANT(S) ONLY | | AND IS NOT TIED INTO A FIRE ALARM SYSTEM. | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHER E EACH COMMENT WAS ADDRESSED. | | | | CAPT MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2009-04-17 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2009-04-17 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2009-02-27 |
Time |
16:31 |
Sent To |
|
|
Notes |
2009-02-27 16:35:01 | TO "COMM" BD#46 |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
F |
Date |
2009-03-11 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2009-03-11 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2009-03-11 |
Time |
11:40 |
Sent To |
PC |
|
Notes |
2009-03-11 16:55:25 | ***LANDSCAPE REVIEW FAILED*** | | | | PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN | | FORMAT. | | | | 1. PURSUANT TO SECTION 94-442(A), LANDSCAPE PLANS SHALL | | BE SIGNED AND SEALED BY A REGISTERED LANDSCAPE | | ARCHITECT. | | | | 2. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | AND LAND DEVELOPMENT REGULATIONS. | | | | 3. PURSUANT TO SECTION 94-442 (B)(1), AT LEAST ONE | | FLOWERING TREE SHALL BE PLANTED FOR EACH 6400 SQUARE | | FEET OF OPEN SPACE OR PORTION THEREOF. | | | | 4. PLEASE BE SPECIFIC AS TO WHAT TREES AND PLANT | | MATERIAL ARE BEING PROPOSED. COCONUT PALMS ARE NOT IN | | THE SAME CLASSIFICATION AS SABAL PALMS. JASMINE IS NOT | | A HEDGE AND SO ON. | | | | 5. PURSUANT TO SECTION 94-443(C)(3)(A), EACH ROW OF | | PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED | | ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH AND LOT | | LESS THAN THE LENGTH OF THE ADJACENT PARKING STALL. THE | | ISLAND AT THE NORTH END OF THE PARKING ROW IS NOT THE | | FULL LENGTH OF THE ADJACENT PARKING STALL. | | | | 6. UNLESS THE TRAVEL AISLE IS ONE-WAY ONLY, 90 DEGREE | | PARKING IS PREFERRED. | | | | 7. PURSUANT TO SECTION 94-443(C)(4), FOR OTHER PAVED | | AREAS UTILIZED BY MOTOR VEHICLES, INCLUDING AISLES, | | ADDITIONAL LANDSCAPING SHALL BE PROVIDED AS FOLLOWS: | | FOUR SQUARE FEET OF LANDSCAPED AREA SHALL BE REQUIRED | | FOR EACH 100 SQUARE FEET OR FRACTION THEREOF. | | | | 8. PURSUANT TO SECTION 94-443(C)(5)(A), LANDSCAPE AREAS | | SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY | | NONMOUNTABLE, CONCRETE CURBING OF THE TYPE | | CHARACTERIZED AS "TYPE D". CURBING WAS NOT SHOWN ALONG | | THE EAST SIDE OF THE DRIVE AISLE, ADJACENT TO THE | | POTTED PLANTS. | | | | 9. THE PAVED AREA BETWEEN THE DRIVE AISLE AND THE SHED | | IS DESIGNATED AS A LANDSCAPED AREA ON THE SITE PLAN. | | PLEASE CLARIFY. POTTED PLANTS CANNOT BE USED TO DEFINE | | A DRIVEWAY. | | | | 10. ON THE LANDSCAPE PLAN, PLEASE SHOW ALL UTILITIES, | | EASEMENTS, STREET LIGHTS AND TREES ON NEIGHBORING | | PROPERTY IN CLOSE PROXIMITY TO SHARED PROPERTY LINES | | AND ANYTHING ELSE THAT MAY INTERFERE WITH THE PROPOSED | | LANDSCAPING. | | | | 11.THERE ARE PROPOSED LIVE OAK TREES UNDER POWER LINES, | | YOU ARE REQUIRED TO FOLLOW FPL'S "PLANT THE RIGHT TREE | | IN THE RIGHT PLACE" GUIDELINES FOR WHAT IS ALLOWED TO | | BE PLANTED NEAR OF UNDER POWER LINES. THE GUIDELINES | | WOULD NOT ALLOW THE OAKS TO BE PLANTED IN THAT | | LOCATION. | | | | 12. FOR THIS TO BE UTILIZED AS ONE-WAY CIRCULATION, IT | | MUST BE STRIPED AND MARKED ACCORDINGLY PER CITY | | STANDARDS. | | | | 13. PURSUANT TO SECTION 94-442(D), PRIVATE LAND AND | | PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK | | SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN | | SPACE AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS | | SHALL BE SODDED. | | | | 14. PURSUANT TO SECTION 94-445(4)(G)(3), AUTOMATIC | | IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED | | LANDSCAPE AREAS FOR ALL PROPERTIES. THIS INCLUDES THE | | RIGHT-OF-WAY, ADJACENT TO AVON ROAD. | | | | 15. SUBMIT A CERTIFIED COST ESTIMATE THAT INCLUDES THE | | TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR. | | | | 16. HEDGE MATERIAL ADJACENT TO A RIGHT-OF-WAY SHALL BE | | PLANTED ALONG THE INTERIOR PERIMETER TO THE LANDSCAPE | | SETBACK (ON STREET SIDE OF A FENCE) . GROUND COVER AND | | SOD SHALL BE PLANTED BETWEEN THE HEDGE AND THE PROPERTY | | LINE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | KUSSNER @ (561) 822-1462. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2009-04-17 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2009-04-17 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2009-04-17 |
Time |
09:55 |
Sent To |
|
|
Notes |
2009-04-17 09:57:05 | PERMIT NOT REQUIRED . |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2009-04-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-04-14 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-04-14 |
Time |
11:35 |
Sent To |
|
|
Notes |
2009-04-14 11:52:02 | DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. PLANS SHALL INDICATE THE LOCATION OF THE WORK IN THE | | TITLE BLOCK. THE ADDRESS INDICATED ON THE APPLICATION | | AND IN THE CITY ADDRESSING SYSTEM IS 425 BELVEDERE | | ROAD. SECTION 106.1.1 | | | | 2. SUBMIT A SITE PLAN INDICATING THE LOCATION OF THE | | SEWER CONNECTION, THE WATER METER, THE BACKFLOW, THE | | SEWER PIPING & THE WATER SERVICE LINE. SECTIONS 106.1.2 | | (MORE INFORMATION REQUIRED), 603, 701, 708, ETC. | | | | 3. PER TABLE 403.1 A SERVICE SINK IS REQUIRED IN ALL | | STORAGE OCCUPANCIES. PLEASE INDICATE THE LOCATION OF | | THE REQUIRED SINK. | | | | 4. SHOW COMPLIANCE FOR THE FOLLOWING: | | | | ___W/C: | | A. 11-4.16.2 CLEAR FLOOR SPACE | | B. 11-4.16.4 GRAB BARS (MINIMUM 36" REQUIRED BEHIND THE | | W/C - 30" SHOWN) | | | | ___LAV: | | A. 11-4.19.2 HEIGHT & CLEARANCES | | B. 11-4.19.3 CLEAR FLOOR SPACE | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | D. 11-4.19.5 FAUCETS | | | | ___D/F: | | A. 11-4.15.5 CLEAR FLOOR SPACE (FORWARD APPROACH REQD) | | B. 11-4.1.3(10(A) PROVISIONS FOR THOSE WHO HAVE | | DIFFICULTY BENDING OR STOOPING. | | | | 5. SHT 4 OF 4 SANITARY RISER DIAGRAM, A TWO WAY | | CLEANOUT SHALL BE USED NEAR THE JUNCTION OF THE | | BUILDING DRAIN AND THE BUILDING SEWER, OR A SEPARATE | | CLEANOUT FOR THE SEWER IS REQUIRED. SECTION 708.3.2. | | | | 6. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED PER | | SECTION 106.3.5.1.3. INDICATE ALL PIPE SIZES, VALVES, | | ETC. | | | | 7. HOT WATER IS REQUIRED FOR THE SERVICE SINK PER | | SECTION 607.1. PLEASE SHOW ON THE FLOOR PLAN AND THE | | WATER ISOMETRIC RISER DIAGRAM. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2009-03-10 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2009-03-10 |
Time |
20:31 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2009-03-10 |
Time |
20:31 |
Sent To |
|
|
Notes |
2009-03-10 21:17:21 | ZONING PLAN REVIEW | | | | PERMIT NO.: 09020579 | | ADDRESS: 425 BELVEDERE ROAD | | CONTRACTOR/CONTACT: ROBERT BROCKMAN | | TELEPHONE NO.: 561.719.3702 | | SCOPE OF REVIEW: INSTALLATION OF PRE-FABRICATED SHED | | AND RELATED SITE IMPROVEMENTS. | | | | REVIEW STATUS: FAILED | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1) TWO (2) COPIES OF A CURRENT/ACCURATE SURVEY SHALL BE | | PROVIDED; ONLY ONE (1) COPY WAS SUBMITTED WITH THE | | PERMIT APPLICATION. | | | | 2) SETBACK DIMENSIONS SHALL BE PROVIDED FROM ALL | | PROPERTY LINES TO THE EXTERIOR OF THE PROPOSED | | PRE-FABRICATED SHED. ALL SETBACKS SHALL CONFORM TO THE | | GENERAL COMMERCIAL (GC) ZONING DESIGNATION. | | | | 3) PLEASE CLARIFY THE CALCULATIONS PROVIDED IN THE SITE | | DATA TABLE. IMPERVIOUS AREA AND LANDCAPE ARE SHOULD | | EQUAL 100%. ADDITIONALLY, THE PERCENTAGE OF OPEN SPACE | | (LOT AREA MINUS BLDG. FOOTPRINT) SHALL BE PROVIDED. | | | | 4) PURSUANT TO SECTION 94-401 OF THE CITY'S ZONING AND | | LAND DEVELOPMENT REGULATIONS (ZLDRS), THE EXISTING SIGN | | POLES SHALL BE REMOVED. | | | | 5) ELEVATIONS OF THE PROPOSED SHED SHALL BE PROVIDED | | SHOWING THE OVERALL HEIGHT OF THE STRUCTURE. BUILDING | | HEIGHT SHALL BE MEASURED FROM GRADE TO THE MEAN POINT | | OF A PITCHED ROOF. THE PRODUCT APPROVALS SUBMITTED AS | | PART OF THE PERMIT APPLICATION DO NOT SHOW THE OVERALL | | HEIGHT IN THE DRAWINGS. | | | | 6) A DETAIL OF THE PROPOSED FENCE/GATE SHALL BE | | PROVIDED. | | | | 7) PLEASE INDICATE THE LOCATION OF ANY PROPOSED | | MECHANICAL EQUIPMENT. PURSUANT TO SECTION 94-444, ALL | | MECHANICAL EQUIPMENT SHALL BE SCREENED. SCREENING SHALL | | CONSIST OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE | | MASONRY, OR COMPARABLY DURABLE WOOD OR STEEL. | | ADDITIONALLY, SHRUBS OR HEDGES SHALL BE PLANTED AT | | 2-FOOT INTERVALS. | | | | 8) AN APPROVED TRAFFIC CONCURRECY LETTER FROM THE PALM | | BEACH COUNTY DEPARTMENT OF ENGINEERING AND PUBLIC WORKS | | - TRAFFIC ENGINEERING DIVISION SHALL BE SUBMITTED WITH | | THE PERMIT APPLICATION. | | | | 9) THE PROPOSED SITE PLAN ON SHEET A01 NEEDS TO BE | | ADJUSTED. THERE IS AN AREA LABELED AS "LANDSCAPE AREA" | | BUT IS SHADED AS "AREA CURRENTLY PAVED." ADDITIONALLY, | | THE LABEL "APPLIED STRIPES AS PER ADA" IS NOT POINTED | | AT ANYTHING. PLEASE ADJUST PLAN ACCORDINGLY. | | | | 10) PURSUANT TO SECTION 94-448(D)(2)(R), LANDSCAPE | | PLANS SHALL BE PREPARED BY A REGISTERED LANDSCAPE | | ARCHITECT. ADDITIONALLY, REFER TO SECTION 94-448(D)(2) | | REGARDING MINIMUM REQUIREMENTS OF THE LANDSCAPE PLANS. | | | | 11) PLEASE PROVIDE WRITTEN CONFIRMATION FROM THE CITY'S | | ENGINEERING SERVICES DEPARTMENT THAT A DUMPSTER IS NOT | | REQUIRED. IF A DUMPSTER IS REQUIRED, IT SHALL BE | | SCREENED IN ACCORDANCE WITH SECTION 94-444 OF THE | | ZLDRS. | | | | 12) A PARKING DETAIL SHALL BE PROVIDED SHOWING | | COMPLIANCE OF THE STRIPING (SEE ATTACHED). | | | | 13) THE AISLE WIDTH OF THE PARKING AREA SHALL BE | | DIMENSIONED AND SHALL BE A MINIMUM OF 13 FEET. | | | | 14) BICYCLE PARKING SHALL BE PROVIDED AT A RATE OF 1 | | SPACE PER 20 PARKING SPACES, OR FRACTION THEREOF. | | PLEASE REFER TO THE ATTACHED DOCUMENTATION REGARDING | | STYLE AND PLACEMENT OF BIKE RACKS. | | | | 15) A DATA TABLE SHOWING THE PARKING CALCULATIONS SHALL | | BE PROVIDED ON THE SITE PLAN. | | | | REMINDER, THE NURSERY IS TO BE FOR RETAIL SALES ONLY OF | | MATERIAL GROWN OFF-SITE....NO PLANTS ARE TO BE GROWN ON | | THE PROPERTY. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | AT (561) 822-1435. | | |
|
|
|