Plan Review Details - Permit 09020560
Plan Review Stops For Permit 09020560
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-03 Cont ID  
Sent By jgomez Date 2009-08-03 Time 13:59 Rev Time 0.00
Received By jgomez Date 2009-08-03 Time 13:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-31 Cont ID  
Sent By jgomez Date 2009-03-31 Time 11:43 Rev Time 0.00
Received By jgomez Date 2009-03-31 Time 11:43 Sent To  
Notes
2009-03-31 11:59:15RESIDENTIAL (R3) REPAIR/RENOVATION BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- CLARIFY WHICH UNIT IS GOING TO BE REPAIRED. ADDRESS
 ON PERMIT APPLICATION IS FOR 836 ALMERIA RD. FLOOR
 PLANS STATE THAT UNIT 836 TO REMAIN AS IS. COORDINATE
 INFORMATION AS REQUIRED TO MATCH.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ENTRY AND REAR SWING DOORS. NOA 02-1211.12 SUBMITTED
 EXPIRED ON APRIL 14, 2008. NEED TO PROVIDE CURRENT ONE.
  
 B) EXTERIOR LOUVER SHOWN GABLE WALL ON NORTH ELEVATION.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SHOWN ON PLANS AND
 DETAILS. GO TO WWW.FLORIDA BUILDING.ORG. PROVIDE ONLY
 COPY OF THE FLORIDA PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING CONNECTOR. NO NEED TO DOWNLOAD COMPLETE
 REPORT. NOTE: THIS APPLIES TO STRUCTURAL CONNECTORS
 ONLY. OTHER PRODUCT APPROVALS NEED TO PROVIDE COMPLETE
 REPORT.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
 ALSO, MISSING APPROVAL ON SHINGLES PRODUCT APPROVAL.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE REVISED FORM 600C-04R.
  
 B) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 C) CLARIFY ITEM #8A. ACCORDING TO WALL SECTIONS SHOWN
 ON DRAWINGS THERE IS NOT SLAB ON GRADE. SEE PLANS AND
 REVISE AS REQUIRED.
  
 6- ARCHITECT TO PROVIDE THE ARCHITECTURAL FIRM LICENSE
 NUMBER ON TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004
 OF FLORIDA ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA
 STATUTE. UNABLE TO FIND AA-C002146 ON STATE WEBSITE.
  
 7- PLANS TO SPECIFY SIZE AND LOCATION OF ATTIC ACCESS.
 SEE SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN.
 SIZE, LOCATION AND CLEARANCE REQUIREMENTS.
  
 8- SHEET A-4:
 A) REVISE NOTES BELOW STRUCTURAL WOOD NOTE #6. THIS
 BUILDING HAS NO HIP ROOF, BUT GABLE ROOF. REFERENCE
 CODE SECTIONS FOR DRAFSTOPPING FROM THE 2004 FLORIDA
 RESIDENTIAL CODE WHICH IS THE CODE THAT GOVERNS ONE AND
 TWO FAMILY BUILDINGS.
 REVISE DIMENSIONS FOR ATTIC ACCESS. SEE SEC. R807 OF
 2004 FLORIDA RESIDENTIAL CODE. ALSO, REFERENCE PROPER
 SECTION FROM THE RESIDENTIAL CODE. SEE COMMENTS ON
 PLANS.
  
 B) REVISE DESIGN WIND LOADS SPECIFICATIONS. ASCE YEAR
 REFERENCE TO BE USED IS ASCE 7-02, NOT 98. CLARIFY IF
 STRUCTURE IS DESIGNED USING ASCE 7-02 OR FBC 2004 SEC.
 1609. REVISE NOTE STATING THAT THIS IS A BUILDING WITH
 A HIP ROOF. THIS IS A BUILDING WITH GABLE ENDS. REVISE
 ROOF SHEATHING SPECIFICATIONS TO COMPLY WITH SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. NEED TO
 IDENTIFY ROOF ZONE #3 AND MINIMUM NAIL TYPE AND SPACING
 TO BE USED. NEED 8D RING SHANK NAILS AT 4"O.C. AT EDGES
 AND INTERMEDIATE SUPPORTS. REVISE AS REQUIRED. SEE
 FIGURE 803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 ROOF SHEATHING NAILING ZONES.
  
 C) SPECIFY ALL LIVE LOADS, INCLUDING THE ATTIC LIVE
 LOADS AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 TENANT SEPARATION WALL TO VERIFY COMPLIANCE WITH SEC.
 R317 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 E) REVISE SPECIFICATIONS FOR TRUSS CONNECTOR H10A. SEE
 PRODUCT APPROVAL FOR CORRECT UPLIFT CAPACITY AND
 SPECIFIED NUMBER OF NAILS. OTHERWISE PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR NUMBERS THAT DIFFER FROM THOSE
 TESTED AND PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 DESIGN PRESSURES OF SEC. R301.
  
 F) COORDINATE LOCATION OF ATTIC ACCESS WITH ITEM #7
 ABOVE.
  
 9- SHEET A-5:
 A) REVISE PRE-ENGINEERED WOOD TRUSSES NOTES: COORDINATE
 THE DESIGN LOADS WITH THOSE SHOWN ON SHEET A-4 AND
 INCLUDE THE ATTIC LIVE LOADS. REFERENCE CORRECT CODE
 SECTION AND CODE YEAR. ALSO, UPDATE YEAR EDITION OF
 ASCE 7. REFER TO ASCE 7-02 NOT 98. SEE COMMENTS ON
 PLANS.
  
 B) TYPICAL NEW WALL SECTION: REVISE ROOF SHEATHING
 NOTE. COORDINATE WITH ITEM #8B ABOVE. COORDINATE WITH
 ROOF SHINGLES NOTE ON SAME DRAWING. COORDINATE TRUSS
 AND WALL CONNECTORS WITH THOSE SHOWN ON SHEET A-4.
 REVISE NOTE REGARDING THE HIP ROOF. SPECIFY SIZE OF
 CONTINUOUS VENT TO VERIFY COMPLIANCE WITH SEC. R806 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 10- PLEASE RETURN REVIEWED SET AFTER CORRECTIONS ARE
 DONE TO ORIGINAL DRAWINGS TO EXPEDITE THE REVIEW
 PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-09-22 Cont ID  
Sent By jleahy Date 2009-09-22 Time 09:58 Rev Time 0.00
Received By jleahy Date 2009-09-22 Time 09:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-08-04 Cont ID  
Sent By btrobaug Date 2009-08-04 Time 11:59 Rev Time 0.00
Received By btrobaug Date 2009-07-31 Time 13:28 Sent To  
Notes
2009-08-04 11:59:45 
  
  
 APPLICATION #09020560 ELECTRICAL PLAN REVIEW
 836 ALMERIA ROAD #836-840 3/5/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THIS COMMENT WAS PART OF THE PREVIOUS REVIEW
 1} SEE 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE*** FROM THE PARTIAL RISER SUBMITTED IT
 CANNOT BE DETERMINED IF COMPLIANCE WITH THIS ARTICLE IS
 MET.
  
 NEW COMMENTS GENERATED BY THE RISER CHANGE.
  
 2} THE CONDUCTORS FROM THE DISCONNECT LOCATION NOW
 SHOWN ARE RUNNING OVERHEAD AND POSSIBLY PANEL "B" IS
 BEING FEED THROUGH BUILDING "A" IN VIOLATION OF 230..3
 NEC
  
 3} THE FEED FROM THE DICONNECTS TO THE PANEL MUST
 CONTAIN AN EQUIPMENT GROUND PER 250.122. NEC
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-07 Cont ID  
Sent By btrobaug Date 2009-03-06 Time 09:50 Rev Time 0.00
Received By btrobaug Date 2009-03-04 Time 08:01 Sent To P
Notes
2009-03-06 09:50:18 
  
  
 APPLICATION #09020560 ELECTRICAL PLAN REVIEW
 836 ALMERIA ROAD #836-840 3/5/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE RISER DIAGRAM INDICATES ONE METER AND TWO
 PANELS, THE PLAN LOCATES TWO METERS AND TWO MAIN
 DISCONNECTS. CORRELATE THE PLAN AND THE RISER AS TO THE
 INTENT OF THE DESIGNER. ALSO SEE 230.2 NUMBER OF
 SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE.
  
 2} THERE ARE NO MAIN DISCONNECTS ON THE RISER, BUT
 INDICATED AT THE BUILDING. 215.5
  
 3} SEE 250.66 REGARDING GEC SIZE AND LOCATION. LOCATION
 WILL BE DETERMINED BY COMMENT #2 RESPONSE
  
 4} THE PANEL LOCATION IN THE UNITS ARE IN VIOLATION OF
 110.26 SPACING REQUIREMENTS.
  
 5} 210.11(C) (1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B).***ONLY
 ONE ON THE SCHEDULE.
  
 6} CIRCUIT #11 IS LABELED "LAUNDRY ROOM" BUT APPEARS TO
 BE LIVING ROOM. ALSO IT DOES NOT MEET THE REQUIREMENTS
 OF A LAUNDRY ROOM CIRCUIT PER 210.11(C)(2).
  
 7} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED
 UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY
 IN THE FIELD AND COMPLIANCE WITH 106.1.3 FBC AS AMENDED
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-14 Cont ID  
Sent By lmartine Date 2009-09-14 Time 09:22 Rev Time 0.00
Received By lmartine Date 2009-09-14 Time 09:22 Sent To  
Notes
2009-09-14 09:23:01GAVE TO BILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-22 Cont ID  
Sent By lmartine Date 2009-07-22 Time 11:42 Rev Time 0.00
Received By lmartine Date 2009-07-22 Time 11:42 Sent To  
Notes
2009-07-22 11:43:13R-2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-31 Cont ID  
Sent By lmartine Date 2009-03-31 Time 14:55 Rev Time 0.00
Received By lmartine Date 2009-02-27 Time 15:34 Sent To  
Notes
2009-02-27 15:44:09TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-03-27 Cont ID  
Sent By hmoser Date 2009-03-27 Time 08:43 Rev Time 0.00
Received By hmoser Date 2009-03-27 Time 08:43 Sent To B
Notes
2009-03-27 08:48:36PLANS SHOW WALL A/C UNITS .

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-09-22 Cont ID  
Sent By jwitmer Date 2009-09-22 Time 10:38 Rev Time 0.22
Received By jwitmer Date 2009-09-22 Time 10:38 Sent To  
Notes
2009-09-22 10:39:20RVISIONA-6 DATED 9-03-09

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-04 Cont ID  
Sent By jwitmer Date 2009-08-04 Time 14:57 Rev Time 0.40
Received By jwitmer Date 2009-08-04 Time 14:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-03-11 Cont ID  
Sent By btrobaug Date 2009-05-07 Time 15:37 Rev Time 0.00
Received By kstevens Date 2009-03-11 Time 10:14 Sent To M
Notes
2009-03-11 10:26:50DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
  
 1. SUBMIT AN EXISTING FLOOR PLAN SO THAT THE EXTENT OF
 THE REPAIR WORK CAN BE VERIFIED. DESCRIPTION OF WORK ON
 APPLICATION "REPAIR EXISTING DUPLEX" DOES NOT INDICATE
 ALL WORK TO BE DONE. INDICATE ON THE PLANS THE SCOPE OF
 WORK FOR THIS PERMIT. SECTION 106.1.2. (MORE
 INFORMATION REQUIRED).
  
 2. APPLICATION WORK ADDRESS INDICATES APT #1 & 2, BUT
 NOTE ON SHEET A-2 STATES UNIT 840 TO BE RENOVATED -
 UNIT 836 TO REMAIN AS IS. PLEASE CLARIFY. SECTION
 106.1.1.
  
 3. PLANS SHALL INDICATE THE CODE CRITERIA FOR THE
 DESIGN. PRESENT CODE IS FBC-2004 WITH 2007 REVISIONS.
 PLANS SHALL ALSO INDICATE THE LEVEL OF ALTERATION PER
 CHAPTERS 5, 6 & 7 OF THE EXISTING BUILDING CODE.
 SECTION 106.1.1.
  
 4. NOTE: PLANS ARE NOT 100%. WHEN COMMENTS ARE
 ADDRESSED AND MORE INFORMATION IS PROVIDED, MORE
 COMMENTS MAY BE FORTHCOMING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  