Plan Review Details - Permit 09020541
Plan Review Stops For Permit 09020541
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-13 Cont ID  
Sent By jgomez Date 2009-04-13 Time 15:46 Rev Time 0.00
Received By jgomez Date 2009-04-13 Time 15:25 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-12 Cont ID  
Sent By jgomez Date 2009-03-12 Time 10:26 Rev Time 0.00
Received By jgomez Date 2009-03-12 Time 10:25 Sent To PC
Notes
2009-03-12 10:43:46RE-ROOF BUILDING REVIEW SECOND CHECKLIST.
  
 THE FOLLOWING ITEMS WERE NOT ADDRESSED FROM THE FIRST
 CHECKLIST:
  
 1- A) CONTRACTOR TO SELECT ON PRODUCT APPROVAL
 SUBMITTED THE SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED (REPEAT COMMENT. THIS WAS NOT DONE).
 CONTRACTOR WROTE "GAF 1-1/4 RING SHANK" NEXT TO THIS
 COMMENT, BUT THIS DOESN'T ADDRESS THE QUESTION ASKED.
  
 B) INDICATE SPECIFIC BASE SHEET FASTENING OPTION.
 REPEAT COMMENT. THIS WAS NOT DONE).
  
 ***NOTE: KEEP IN MIND THAT APPROVED ASSEMBLY IS FOR AN
 INSULATED ASSEMBLY SINCE PERMIT APPLICATION CALLS FOR
 INSULATION BOARD TO BE INSTALLED.
  
 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA 07-0111.03 SUBMITTED
 (REPEAT COMMENT. THIS WAS NOT DONE). CONTRACTOR WROTE "
 FIELD -47.3PSF, PER. -79.4PSF, CORNER -119.5PSF" NEXT
 TO THE COMMENT, BUT THIS DOESN'T ADDRESS THE QUESTION
 ASKED. THESE ARE JUST THE DESIGN PRESSURES THAT NEED TO
 BE RESISTED. STILL NEED TO PROVIDE INFORMATION SHOWING
 HOW THE FASTENERS WILL BE INSTALLED TO MEET THOSE
 DESIGN PRESSURES.
  
 3- PROVIDE RE-RECORDED NOTICE OF COMMENCEMENT. THE ONE
 THAT WAS PROVIDED IS EXPIRED BECAUSE IT WAS RECORDED ON
 12/01/2008. NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90
 DAYS IF WORK IS NOT STARTED (SEC. 713.13 FLORIDA
 STATUTE). NEED TO PROVIDE RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-26 Cont ID  
Sent By rmcdouga Date 2009-02-26 Time 07:07 Rev Time 0.00
Received By jgomez Date 2009-02-26 Time 07:07 Sent To  
Notes
2009-02-26 08:15:352004 FLORIDA BUILDING CODE &
 CITY OF WEST PALM BEACH AMENDMENTS TO THE 2004 FBC
 R-3 REROOF
  
 ****CORRECTIONS****
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____ 1.) EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER
 BARRIER REQUIRED FS553.844(5)(A). PROVIDE INFORMATION
 (PRODUCT APPROVAL OR SPECIFICATIONS) TO SHOW HOW YOU
 WILL COMPLY WITH THIS REQUIREMENT. INFORMATION IS
 AVAILABLE AT WWW.BOAF.NET, HURRICANE MITIGATION.
  
 __X__ 2.) CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION: AREA OF FLAT ROOF.
  
 ____ 3.) FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72. WWW.FLORIDABUILDING.ORG
  
 __X__ 4.) FOR THE FLAT ROOF, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING. ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 __X___ 5.) FOR THE FLAT ROOF, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES. THIS IS TO BE
 SUBMITTED ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE
 RESUB SHEET). SEE GENERAL LIMITATION #7 ON PAGE 19 OF
 NOA NO. 07-0111.03.
  
 ____ 6.) ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING. IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 ____ 7.) SEE PRODUCT LIMITATION #7. CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
 ____ 8.) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS. ONLY
 ONE WAS SUBMITTED.
  
 __X__ 9.) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 NOTE: DOUBLE UNDERLAYMENT REQUIRED FOR ASPHALT SHINGLES
 ON SLOPES LESS THAN 4:12 PER FBC R905.2.
  