Plan Review Stops For Permit 09020479 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2009-10-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-10-05 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-10-05 |
Time |
08:13 |
Sent To |
|
|
Notes |
2009-10-05 08:14:49 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED (SAME | | PLANS SUBMITTED, NOT SIGNED & SEALED, ONLY ONE SET): | | | | 1. ADDRESSED. | | | | 2. PLANS ARE NOTED AS PRELIMINARY. PERMIT DOCUMENTS MAY | | BE SUBMITTED TO EXPEDITE THE PROCESS (OPTIONAL; NOT | | REQUIRED). THE PLANS WILL BE REVIEWED AND STAMPED WITH | | A FAILED REVIEW STATUS. WHEN CONTRACTOR HAS BEEN | | SELECTED, CONTRACTOR CAN THEN APPLY FOR PERMIT AND THE | | PLANS ALREADY STAMPED AS REVIEWED WILL BE DATE STAMPED | | AND ISSUED WITH THE PERMIT. THREE SETS REQUIRED IF | | SPECIAL INSPECTOR IS REQUIRED (SEE OTHER COMMENTS). | | | | SAME PLANS SUBMITTED. TWO ORIGINAL FINAL SETS OF PLANS | | REQUIRED, FAC61G15-23. PLEASE REVISE PLANS AND SUBMIT | | TWO SETS FOR PERMIT ISSUANCE. | | | | 3. PROVIDE THE ORIGINAL SOILS INVESTIGATION REPORT | | REFERRED TO ON S0.0. | | | | 4. SPECIAL INSPECTOR REQUIRED PER SHEET S0.0. PLEASE | | CONTACT KEN CONRAD, CHIEF BUILDING INSPECTOR REGARDING | | THE SPECIAL INSPECTOR REQUIREMENTS. THIS PROCESS MUST | | BE COMPLETED PRIOR TO PERMIT ISSUANCE. NOTE THAT THIS | | IS A REQUIREMENT OF THE ENGINEER. ALTERNATIVELY, THE | | REQUIREMENT MAY BE REMOVED FROM THE PLAN. | | | | 5. S0.0, GENERAL NOTE 2, PLEASE REVISE GOVERNING CODE | | (FBC2007 WITH 2008 SUPPLEMENTS). | | | | 6. PLEASE PROVIDE A SITE PLAN SHOWING PROPOSED | | LOCATION. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-03-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-03-26 |
Time |
07:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-03-26 |
Time |
07:30 |
Sent To |
E |
|
Notes |
2009-03-26 07:39:36 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. THIS IS A PLAN CHECK ONLY. THIS REVIEW WILL REMAIN | | IN FAILED STATUS UNTIL ALL COMMENTS ARE ADDRESSED AND A | | CONTRACTOR HAS APPLIED FOR PERMIT. | | | | 2. PLANS ARE NOTED AS PRELIMINARY. PERMIT DOCUMENTS MAY | | BE SUBMITTED TO EXPEDITE THE PROCESS (OPTIONAL; NOT | | REQUIRED). THE PLANS WILL BE REVIEWED AND STAMPED WITH | | A FAILED REVIEW STATUS. WHEN CONTRACTOR HAS BEEN | | SELECTED, CONTRACTOR CAN THEN APPLY FOR PERMIT AND THE | | PLANS ALREADY STAMPED AS REVIEWED WILL BE DATE STAMPED | | AND ISSUED WITH THE PERMIT. THREE SETS REQUIRED IF | | SPECIAL INSPECTOR IS REQUIRED (SEE OTHER COMMENTS). | | | | 3. PROVIDE THE ORIGINAL SOILS INVESTIGATION REPORT | | REFERRED TO ON S0.0. | | | | 4. SPECIAL INSPECTOR REQUIRED PER SHEET S0.0. PLEASE | | CONTACT KEN CONRAD, CHIEF BUILDING INSPECTOR REGARDING | | THE SPECIAL INSPECTOR REQUIREMENTS. THIS PROCESS MUST | | BE COMPLETED PRIOR TO PERMIT ISSUANCE. NOTE THAT THIS | | IS A REQUIREMENT OF THE ENGINEER. ALTERNATIVELY, THE | | REQUIREMENT MAY BE REMOVED FROM THE PLAN. | | | | 5. S0.0, GENERAL NOTE 2, PLEASE REVISE GOVERNING CODE | | (FBC2007 WITH 2008 SUPPLEMENTS). | | | | 6. PLEASE PROVIDE A SITE PLAN SHOWING PROPOSED | | LOCATION. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2014-02-19 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2014-02-19 |
Time |
12:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2014-02-19 |
Time |
12:18 |
Sent To |
|
|
Notes |
2014-02-19 12:19:52 | SEPARATE ELECTRICAL PLANS SUBMITTED UNDER ELECTRICAL | | PERMIT # 09080060 FOR GATEWAY SCULPTURE PARK LIGHTING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2009-09-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-09-22 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-09-22 |
Time |
14:46 |
Sent To |
|
|
Notes |
2009-09-22 14:47:01 | ** DENIED ** | | | | | | 1) NOTE: FIRST REVIEW UNDER PERMIT APPLICATION. | | COMMENTS FROM PREVIOUS REVIEW/REVIEWER NOT ADDRESSED. | | PLEASE SUBMIT COMPLETED ELECTRICAL PLANS IN CONFORMANCE | | WITH THE 2005 NFPA-70. | | PLEASE SHOW ELECTRICAL SERVICE FEEDING NEW ELECTRICAL | | FOR SCULPTURES AND OTHER ITEMS BEING FED WITH NEW | | ELECTRICAL. | | | | PLEASE SEE 240, 310.16, 110.9, 230.70 | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-03-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-03-26 |
Time |
17:14 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-03-26 |
Time |
16:08 |
Sent To |
B |
|
Notes |
2009-03-26 17:14:40 | | | | | APPLICATION #09020479 ELECTRICAL PLAN REVIEW | | 1025 OKEECHOBEE BLVD 3/26/09 | | WEST PALM BEACH, FL. | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE 2007 FBC AND REFERENCED STANDARDS THEREIN WILL | | BE THE GOVERNING CODE SINCE THE PROJECT WAS NOT IN | | APPLICATION STATUS UNTIL THAT CODE WAS ADOPTED. CHANGE | | ALL NOTES TO REFLECT THOSE CODES AT TIME OF | | APPLICATION. | | | | 2} IF THERE IS TO BE ELECTRICAL INSTALLED FOR LIGHTING | | OR ANY PURPOSE A DISCONNECT WILL BE REQUIRED PER | | 230.70(A)(1) AND MUST HAVE A GROUNDING ELECTRODE SYSTEM | | THAT WOULD INCLUDE BONDING TO BUILDING STEEL PER | | 250.52(A)(3). SHOW ALL ELECTRICAL WIRING ON THE PLANS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2009-09-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-09-01 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-09-01 |
Time |
13:17 |
Sent To |
|
|
Notes |
2009-09-01 13:24:10 | SENT TO C-7. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-03-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-03-04 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-03-04 |
Time |
10:41 |
Sent To |
B |
|
Notes |
2009-03-04 10:41:39 | TO "MISC" BOX#2 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
|
Date |
2009-04-06 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-03-26 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-02-26 |
Time |
10:24 |
Sent To |
|
|
Notes |
2009-02-26 10:24:16 | TO "Z" BOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2009-03-02 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2009-03-02 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2009-03-02 |
Time |
14:04 |
Sent To |
B |
|
Notes |
2009-03-02 14:05:41 | ZONING REVIEW: PASSED | | | | ** SITE PLAN AND LANDSCAPE PLAN FORTHCOMING AND TO BE | | SUBMITTED AS PART OF PERMIT APPROVAL | | | | MATT FLIS - 822-1445 |
|
|