Plan Review Details - Permit 09020479
Plan Review Stops For Permit 09020479
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-10-05 Cont ID  
Sent By shill Date 2009-10-05 Time 08:13 Rev Time 0.00
Received By shill Date 2009-10-05 Time 08:13 Sent To  
Notes
2009-10-05 08:14:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED (SAME
 PLANS SUBMITTED, NOT SIGNED & SEALED, ONLY ONE SET):
  
 1. ADDRESSED.
  
 2. PLANS ARE NOTED AS PRELIMINARY. PERMIT DOCUMENTS MAY
 BE SUBMITTED TO EXPEDITE THE PROCESS (OPTIONAL; NOT
 REQUIRED). THE PLANS WILL BE REVIEWED AND STAMPED WITH
 A FAILED REVIEW STATUS. WHEN CONTRACTOR HAS BEEN
 SELECTED, CONTRACTOR CAN THEN APPLY FOR PERMIT AND THE
 PLANS ALREADY STAMPED AS REVIEWED WILL BE DATE STAMPED
 AND ISSUED WITH THE PERMIT. THREE SETS REQUIRED IF
 SPECIAL INSPECTOR IS REQUIRED (SEE OTHER COMMENTS).
  
 SAME PLANS SUBMITTED. TWO ORIGINAL FINAL SETS OF PLANS
 REQUIRED, FAC61G15-23. PLEASE REVISE PLANS AND SUBMIT
 TWO SETS FOR PERMIT ISSUANCE.
  
 3. PROVIDE THE ORIGINAL SOILS INVESTIGATION REPORT
 REFERRED TO ON S0.0.
  
 4. SPECIAL INSPECTOR REQUIRED PER SHEET S0.0. PLEASE
 CONTACT KEN CONRAD, CHIEF BUILDING INSPECTOR REGARDING
 THE SPECIAL INSPECTOR REQUIREMENTS. THIS PROCESS MUST
 BE COMPLETED PRIOR TO PERMIT ISSUANCE. NOTE THAT THIS
 IS A REQUIREMENT OF THE ENGINEER. ALTERNATIVELY, THE
 REQUIREMENT MAY BE REMOVED FROM THE PLAN.
  
 5. S0.0, GENERAL NOTE 2, PLEASE REVISE GOVERNING CODE
 (FBC2007 WITH 2008 SUPPLEMENTS).
  
 6. PLEASE PROVIDE A SITE PLAN SHOWING PROPOSED
 LOCATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-26 Cont ID  
Sent By shill Date 2009-03-26 Time 07:30 Rev Time 0.00
Received By shill Date 2009-03-26 Time 07:30 Sent To E
Notes
2009-03-26 07:39:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THIS IS A PLAN CHECK ONLY. THIS REVIEW WILL REMAIN
 IN FAILED STATUS UNTIL ALL COMMENTS ARE ADDRESSED AND A
 CONTRACTOR HAS APPLIED FOR PERMIT.
  
 2. PLANS ARE NOTED AS PRELIMINARY. PERMIT DOCUMENTS MAY
 BE SUBMITTED TO EXPEDITE THE PROCESS (OPTIONAL; NOT
 REQUIRED). THE PLANS WILL BE REVIEWED AND STAMPED WITH
 A FAILED REVIEW STATUS. WHEN CONTRACTOR HAS BEEN
 SELECTED, CONTRACTOR CAN THEN APPLY FOR PERMIT AND THE
 PLANS ALREADY STAMPED AS REVIEWED WILL BE DATE STAMPED
 AND ISSUED WITH THE PERMIT. THREE SETS REQUIRED IF
 SPECIAL INSPECTOR IS REQUIRED (SEE OTHER COMMENTS).
  
 3. PROVIDE THE ORIGINAL SOILS INVESTIGATION REPORT
 REFERRED TO ON S0.0.
  
 4. SPECIAL INSPECTOR REQUIRED PER SHEET S0.0. PLEASE
 CONTACT KEN CONRAD, CHIEF BUILDING INSPECTOR REGARDING
 THE SPECIAL INSPECTOR REQUIREMENTS. THIS PROCESS MUST
 BE COMPLETED PRIOR TO PERMIT ISSUANCE. NOTE THAT THIS
 IS A REQUIREMENT OF THE ENGINEER. ALTERNATIVELY, THE
 REQUIREMENT MAY BE REMOVED FROM THE PLAN.
  
 5. S0.0, GENERAL NOTE 2, PLEASE REVISE GOVERNING CODE
 (FBC2007 WITH 2008 SUPPLEMENTS).
  
 6. PLEASE PROVIDE A SITE PLAN SHOWING PROPOSED
 LOCATION.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2014-02-19 Cont ID  
Sent By rbrown Date 2014-02-19 Time 12:18 Rev Time 0.00
Received By rbrown Date 2014-02-19 Time 12:18 Sent To  
Notes
2014-02-19 12:19:52SEPARATE ELECTRICAL PLANS SUBMITTED UNDER ELECTRICAL
 PERMIT # 09080060 FOR GATEWAY SCULPTURE PARK LIGHTING.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-09-22 Cont ID  
Sent By dpalmer Date 2009-09-22 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2009-09-22 Time 14:46 Sent To  
Notes
2009-09-22 14:47:01** DENIED **
  
  
 1) NOTE: FIRST REVIEW UNDER PERMIT APPLICATION.
 COMMENTS FROM PREVIOUS REVIEW/REVIEWER NOT ADDRESSED.
 PLEASE SUBMIT COMPLETED ELECTRICAL PLANS IN CONFORMANCE
 WITH THE 2005 NFPA-70.
 PLEASE SHOW ELECTRICAL SERVICE FEEDING NEW ELECTRICAL
 FOR SCULPTURES AND OTHER ITEMS BEING FED WITH NEW
 ELECTRICAL.
  
 PLEASE SEE 240, 310.16, 110.9, 230.70
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-26 Cont ID  
Sent By btrobaug Date 2009-03-26 Time 17:14 Rev Time 0.00
Received By btrobaug Date 2009-03-26 Time 16:08 Sent To B
Notes
2009-03-26 17:14:40 
  
 APPLICATION #09020479 ELECTRICAL PLAN REVIEW
 1025 OKEECHOBEE BLVD 3/26/09
 WEST PALM BEACH, FL.
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE 2007 FBC AND REFERENCED STANDARDS THEREIN WILL
 BE THE GOVERNING CODE SINCE THE PROJECT WAS NOT IN
 APPLICATION STATUS UNTIL THAT CODE WAS ADOPTED. CHANGE
 ALL NOTES TO REFLECT THOSE CODES AT TIME OF
 APPLICATION.
  
 2} IF THERE IS TO BE ELECTRICAL INSTALLED FOR LIGHTING
 OR ANY PURPOSE A DISCONNECT WILL BE REQUIRED PER
 230.70(A)(1) AND MUST HAVE A GROUNDING ELECTRODE SYSTEM
 THAT WOULD INCLUDE BONDING TO BUILDING STEEL PER
 250.52(A)(3). SHOW ALL ELECTRICAL WIRING ON THE PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-01 Cont ID  
Sent By kstevens Date 2009-09-01 Time 13:17 Rev Time 0.00
Received By kstevens Date 2009-09-01 Time 13:17 Sent To  
Notes
2009-09-01 13:24:10SENT TO C-7.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-04 Cont ID  
Sent By adarroug Date 2009-03-04 Time 10:41 Rev Time 0.00
Received By adarroug Date 2009-03-04 Time 10:41 Sent To B
Notes
2009-03-04 10:41:39TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2009-04-06 Cont ID  
Sent By lmartine Date 2009-03-26 Time 10:56 Rev Time 0.00
Received By lmartine Date 2009-02-26 Time 10:24 Sent To  
Notes
2009-02-26 10:24:16TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2009-03-02 Cont ID  
Sent By mflis Date 2009-03-02 Time 14:04 Rev Time 0.00
Received By mflis Date 2009-03-02 Time 14:04 Sent To B
Notes
2009-03-02 14:05:41ZONING REVIEW: PASSED
  
 ** SITE PLAN AND LANDSCAPE PLAN FORTHCOMING AND TO BE
 SUBMITTED AS PART OF PERMIT APPROVAL
  
 MATT FLIS - 822-1445