Plan Review Details - Permit 09020471
Plan Review Stops For Permit 09020471
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-19 Cont ID  
Sent By shill Date 2009-05-19 Time 15:09 Rev Time 0.00
Received By shill Date 2009-05-19 Time 15:09 Sent To  
Notes
2009-05-19 15:10:12PLANS REDLINED
 TAMKO 07-0111.03 REVIEWED BY DOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-30 Cont ID  
Sent By shill Date 2009-04-30 Time 09:42 Rev Time 0.00
Received By shill Date 2009-04-30 Time 08:09 Sent To  
Notes
2009-04-30 09:42:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STA
  
 1-4. ADDRESSED.
  
 4. SHOW COMPLIANCE WITH FBC R704, INSPECTION FOR
 TERMITES.
  
 2ND REVIEW, DETAILS SHOW STUCCO EXTENDING TO GRADE.
 PLEASE SEE FBC R704 AND REVISE DETAIL ACCORDINGLY.
  
 5-6. ADDRESSED.
  
 7. ROOF PERMIT HAS BEEN APPLIED FOR. THEREFORE, ALL
 ROOF PERMIT INFORMATION REQUIRED AT THIS TIME:
  
 A. ADDRESSED.
  
 B. PROVIDE ENHANCED FASTENING PATTERN FOR PERIMETER AND
 CORNER ZONES
  
 2ND REVIEW, PLAN WAS REVISED TO STATE "FASTEN TO ALL
 SUPPORTS W/8D NAILS @ 6"EDGES, 6" FIELD." IT APPEARS
 THAT THIS IS INTENDED TO BE PLYWOOD SHEATHING
 FASTENING, BUT THIS DOES NOT COMPLY WITH FBC R
 803.2.3.1 ZONE 3. ADDITIONALLY, THIS DOES NOT ADDRESS
 THE COMMENT FOR THE ROOF. PLEASE SEE NOA, GENERAL
 LIMITATION #7 ON PAGE 19, ENHANCED FASTENING TO BE IN
 ACCORDANCE WITH RAS117 (ALSO NOTE THAT THERE ARE TWO
 DIFFERENT FASTENING OPTIONS; ENHANCED FASTENING SHOULD
 REFER TO WHICH OPTION IS PROPOSED IN ORDER TO DETERMINE
 CODE COMPLIANCE UNLESS THE PATTERN PROPOSED COMPLIES
 WITH BOTH). PLEASE NOTE THAT IF ALL REQUIRED
 INFORMATION IS NOT PROVIDED PRIOR TO ISSUANCE OF THE
 MASTER PERMIT, THE ROOF PERMIT WILL BE VOIDED AND A
 SEPARATE PERMIT WILL BE REQUIRED IN ORDER TO AVOID
 DELAYS ON THE MASTER PERMIT.
  
 8. ADDRESSED.
  
 9. FBC R403.1.4, SHOW DISTANCE OF BOTTOM OF FOOTING TO
 GRADE.
  
 2ND REVIEW, THIS IS SHOWN AS 10IN. SEE FBC R403.1.4,
 MINIMUM DEPTH REQUIRED IS 12IN.
  
 10-11. ADDRESSED.
  
 12. ROOF SHEATHING NAILING NOT COMPLIANT WITH FBC R
 803.2.3.1. SEE DETAILS 1 A3, 2 A3, CHECK ALL.
  
 2ND REVIEW, 4IN REQUIRED AT ZONE 3, SEE FBC R803.2.3.1.
  
 13-14. ADDRESSED.
  
 15. IMPACT FEES MAY BE DUE. PLEASE CONTACT PALM BEACH
 COUNTY, 233-5025.
  
 2ND REVIEW, THE PLANS MUST BE STAMPED AND THE RECEIPT
 (IF FEES ARE DUE) ATTACHED TO THE APPLICATION. THIS MAY
 BE DONE AFTER ALL PLAN REVIEWS ARE COMPLETED BUT MUST
 BE DONE PRIOR TO PERMIT ISSUANCE.
  
 16-17. ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-30 Cont ID  
Sent By shill Date 2009-03-30 Time 13:50 Rev Time 0.00
Received By shill Date 2009-03-30 Time 13:50 Sent To  
Notes
2009-03-30 14:33:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STA
  
 1. TYPE IV CONSTRUCTION DECLARED; NOT CONSISTENT WITH
 DETAILS. TYPE IV IS HEAVY TIMBER; PLEASE CLARIFY.
  
 2. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD FBC*106.
  
 3. PROVIDE ROOM DESIGNATIONS ON THE PLAN, FBC*106.
  
 4. SHOW COMPLIANCE WITH FBC R704, INSPECTION FOR
 TERMITES.
  
 5. FBC R703.6.3, BOND BREAK REQUIRED, REVISE ALL
 AFFECTED DETAILS.
  
 6. ENERGY CALCS REQUIRED FBC 13-103.
  
 7. ROOF PERMIT HAS BEEN APPLIED FOR. THEREFORE, ALL
 ROOF PERMIT INFORMATION REQUIRED AT THIS TIME:
  
 A. INDICATE WHICH APPROVED ASSEMBLY IS TO BE INSTALLED
  
 B. PROVIDE ENHANCED FASTENING PATTERN FOR PERIMETER AND
 CORNER ZONES
  
 8. SHOW COMPLIANCE WITH FBC R401.3, DRAINAGE.
  
 9. FBC R403.1.4, SHOW DISTANCE OF BOTTOM OF FOOTING TO
 GRADE.
  
 10. SHOW FINISHED FLOOR ELEVATION IN RELATION TO GRADE,
 FBC*106.
  
 11. SMOKE ALARMS REQUIRED, FBC R313.1.
  
 12. ROOF SHEATHING NAILING NOT COMPLIANT WITH FBC R
 803.2.3.1. SEE DETAILS 1 A3, 2 A3, CHECK ALL.
  
 13. DETAIL 4 A3 SPECIFIES 2X WALL STUDS, IN CONFLICT
 WITH OTHER DETAILS, PLEASE CLARIFY DESIGN INTENT.
 CALCULATIONS MAY BE REQUIRED.
  
 14. DETAIL 4 A3 SPECIFIES "APPROVED HURRICANE STRAP,"
 PLEASE SPECIFY (BRAND, MODEL #). CHECK ALL DETAILS.
  
 15. IMPACT FEES MAY BE DUE. PLEASE CONTACT PALM BEACH
 COUNTY, 233-5025.
  
 16. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE WINDOW, FAC9B72.
  
 17. IMPACT PROTECTION REQUIRED FOR THE NEW WINDOW, FBC
 R301.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-16 Cont ID  
Sent By btrobaug Date 2009-04-16 Time 14:31 Rev Time 0.00
Received By btrobaug Date 2009-04-16 Time 13:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-09 Cont ID  
Sent By btrobaug Date 2009-03-09 Time 10:04 Rev Time 0.00
Received By btrobaug Date 2009-03-09 Time 09:44 Sent To M
Notes
2009-03-09 10:04:48 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES
  
 2} 210.70(B)(B) FOR DWELLING UNITS, ATTACHED GARAGES,
 AND DETACHED GARAGES WITH ELECTRIC POWER, AT LEAST ONE
 WALL SWITCH???CONTROLLED LIGHTING OUTLET SHALL BE
 INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR SIDE
 OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS.
 A VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS
 AN OUTDOOR ENTRANCE OR EXIT.
  
 2} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-04-13 Cont ID  
Sent By swurafti Date 2009-04-13 Time 12:30 Rev Time 0.00
Received By swurafti Date 2009-04-13 Time 12:29 Sent To  
Notes
2009-04-13 12:30:36HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-05-19 Cont ID  
Sent By shill Date 2009-05-19 Time 15:09 Rev Time 0.00
Received By shill Date 2009-05-19 Time 11:29 Sent To  
Notes
2009-05-19 11:29:48TO SAMANTA'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-13 Cont ID  
Sent By mjacobs Date 2009-04-13 Time 15:48 Rev Time 0.00
Received By mjacobs Date 2009-04-13 Time 15:48 Sent To  
Notes
2009-04-13 15:50:19TO 'SFR' #1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-30 Cont ID  
Sent By shill Date 2009-03-30 Time 14:34 Rev Time 0.00
Received By shill Date 2009-02-26 Time 08:38 Sent To  
Notes
2009-02-26 08:41:06TO "SFR" "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2009-04-17 Cont ID  
Sent By hmoser Date 2009-04-17 Time 13:15 Rev Time 0.00
Received By hmoser Date 2009-04-17 Time 13:15 Sent To  
Notes
2009-04-17 13:18:47MECHANICAL PERMIT IS NOT REQUIRED .( WALL UNITS)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-03-25 Cont ID  
Sent By hmoser Date 2009-03-25 Time 15:03 Rev Time 0.00
Received By hmoser Date 2009-03-25 Time 15:03 Sent To P
Notes
2009-03-25 15:04:13NO MECHANICAL PLANS .

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-03-27 Cont ID  
Sent By kstevens Date 2009-03-27 Time 15:35 Rev Time 0.00
Received By kstevens Date 2009-03-27 Time 15:35 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-04-29 Cont ID  
Sent By mcruz Date 2009-04-29 Time 12:59 Rev Time 0.00
Received By mcruz Date 2009-04-29 Time 12:54 Sent To P
Notes
2009-04-29 12:59:35ROUTED TO SH

Review Stop Z ZONING
Rev No 1 Status F Date 2009-03-05 Cont ID  
Sent By mcruz Date 2009-03-05 Time 11:55 Rev Time 0.00
Received By mcruz Date 2009-03-05 Time 11:47 Sent To E
Notes
2009-03-05 11:55:10PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE THE SETBACK DIMENSIONS FROM ANY EXTERIOR
 IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES. PURSUANT
 TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-72(A)(2):
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 3. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. PURSUANT TO THE ZLDR, SECTION 94-305(B):
 OVERHANGS SHALL NOT PROJECT MORE THAN THREE (3) FEET
 INTO A REQUIRED SETBACK.
  
 4. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED ADDITION ON
 THE ELEVATION PLAN. PURSUANT TO THE ZLDR, SECTION
 94-611, THE HEIGHT SHALL BE MEASURED AS THE VERTICAL
 DISTANCE FROM THE AVERAGE ELEVATION OF THE FINISHED
 GRADE OF THE BUILDING TO THE MEAN HEIGHT LEVEL BETWEEN
 EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS.
  
 5. INDICATE IF ANY TREES WILL BE REMOVED AS A RESULT OF
 THE PROPOSED PROJECT. IF YES, A TREE ALTERATION/REMOVAL
 PERMIT WILL BE REQUIRED. CONTACT ROBERT KUSSNER, CITY
 LANDSCAPE PLANNER, AT (561) 822-1462 FOR THE
 APPLICATION.
  
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  