Plan Review Details - Permit 09020448
Plan Review Stops For Permit 09020448
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-29 Cont ID  
Sent By btrobaug Date 2009-04-29 Time 11:47 Rev Time 0.00
Received By btrobaug Date 2009-04-28 Time 10:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-11 Cont ID  
Sent By btrobaug Date 2009-03-04 Time 16:43 Rev Time 0.00
Received By btrobaug Date 2009-03-04 Time 15:07 Sent To I
Notes
2009-03-04 16:40:17 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED. A PERMIT SHALL NOT BE ISSUED UNTIL FEES
 AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE
 BEEN PAID. 108.1 FBC. ADJUST THE VALUE AT THE PERMIT
 CLERK???S DESK, AND PAY THE DIFFERENCE IN FEES PRIOR TO
 RESUBMITTING.
  
 2} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. FOR
 LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE
 ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED.
  
 4} PER 220.43 (A) SHOW WINDOWS FOR SHOW-WINDOW
 LIGHTING, A LOAD OF NOT LESS THAN 660
 VOLT-AMPERES/LINEAR METER OR 200 VOLT-AMPERES/LINEAR
 FOOT SHALL BE INCLUDED FOR A SHOW WINDOW, MEASURED
 HORIZONTALLY ALONG ITS BASE.
  
 5} PER 220.42(B) TRACK LIGHTING FOR TRACK LIGHTING IN
 OTHER THAN DWELLING UNITS OR GUEST ROOMS OR GUEST
 SUITES OF HOTELS OR MOTELS, AN ADDITIONAL LOAD OF 150
 VOLT-AMPERES SHALL BE INCLUDED FOR EVERY 600 MM (2 FT)
 OF LIGHTING TRACK OR FRACTION THEREOF. WHERE
 MULTICIRCUIT TRACK IS INSTALLED, THE LOAD SHALL BE
 CONSIDERED TO BE DIVIDED EQUALLY BETWEEN THE TRACK
 CIRCUITS.
  
 6} 220.14 (F) SIGN AND OUTLINE LIGHTING SIGN AND
 OUTLINE LIGHTING OUTLETS SHALL BE CALCULATED AT A
 MINIMUM OF 1200 VOLT-AMPERES FOR EACH REQUIRED BRANCH
 CIRCUIT SPECIFIED IN 600.5(A).
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.
  
 7} 220.14(I) RECEPTACLE OUTLETS EXCEPT AS COVERED IN
 220.14(J) AND (K), RECEPTACLE OUTLETS SHALL BE
 CALCULATED AT NOT LESS THAN 180 VOLT-AMPERES FOR EACH
 SINGLE OR FOR EACH MULTIPLE RECEPTACLE ON ONE YOKE. A
 SINGLE PIECE OF EQUIPMENT CONSISTING OF A MULTIPLE
 RECEPTACLE COMPRISED OF FOUR OR MORE RECEPTACLES SHALL
 BE CALCULATED AT NOT LESS THAN 90 VOLT-AMPERES PER
 RECEPTACLE. THIS PROVISION SHALL NOT BE APPLICABLE TO
 THE RECEPTACLE OUTLETS SPECIFIED IN 210.11(C)(1) AND
 (C)(2).
  
 8} 220.18 MAXIMUM LOADS
 THE TOTAL LOAD SHALL NOT EXCEED THE RATING OF THE
 BRANCH CIRCUIT, AND IT SHALL NOT EXCEED THE MAXIMUM
 LOADS SPECIFIED IN 220.18(A) THROUGH (C) UNDER THE
 CONDITIONS SPECIFIED THEREIN.
 (A) MOTOR-OPERATED AND COMBINATION LOADS WHERE A
 CIRCUIT SUPPLIES ONLY MOTOR-OPERATED LOADS, ARTICLE 430
 SHALL APPLY. WHERE A CIRCUIT SUPPLIES ONLY
 AIR-CONDITIONING EQUIPMENT, REFRIGERATING EQUIPMENT, OR
 BOTH, ARTICLE 440 SHALL APPLY. FOR CIRCUITS SUPPLYING
 LOADS CONSISTING OF MOTOR-OPERATED UTILIZATION
 EQUIPMENT THAT IS FASTENED IN PLACE AND HAS A MOTOR
 LARGER THAN 1/ 8HP IN COMBINATION WITH OTHER LOADS, THE
 TOTAL CALCULATED LOAD SHALL BE BASED ON 125 PERCENT OF
 THE LARGEST MOTOR LOAD PLUS THE SUM OF THE OTHER LOADS.
  
 9} 215.2(A)(1) GENERAL FEEDER CONDUCTORS SHALL HAVE AN
 AMPACITY NOT LESS THAN REQUIRED TO SUPPLY THE LOAD AS
 CALCULATED IN PARTS III, IV, AND V OF ARTICLE 220. THE
 MINIMUM FEEDER-CIRCUIT CONDUCTOR SIZE, BEFORE THE
 APPLICATION OF ANY ADJUSTMENT OR CORRECTION FACTORS,
 SHALL HAVE AN ALLOWABLE AMPACITY NOT LESS THAN THE
 NONCONTINUOUS LOAD PLUS 125 PERCENT OF THE CONTINUOUS
 LOAD.*** NO CONTINUOS LOADS SHOWN IN THE CALCULATION
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-04 Cont ID  
Sent By btrobaug Date 2009-03-11 Time 15:40 Rev Time 0.00
Received By btrobaug Date 2009-02-25 Time 11:01 Sent To PC
Notes
2009-02-25 11:01:16TO "E" BOX