Plan Review Details - Permit 09020379
Plan Review Stops For Permit 09020379
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-02-20 Cont ID  
Sent By jgomez Date 2009-02-20 Time 08:49 Rev Time 0.00
Received By jgomez Date 2009-02-20 Time 08:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-19 Cont ID  
Sent By jgomez Date 2009-02-19 Time 16:42 Rev Time 0.00
Received By jgomez Date 2009-02-19 Time 16:41 Sent To PC
Notes
2009-02-19 16:55:54RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- ACCORDING TO SHUTTER DRAWINGS TABLE 1 NOTE #3 ON
 SHEET 7 OF 13 "SHUTTER SPANS LESS THAN 32" ARE NOT
 ACCEPTABLE". NEED TO REVISE SHUTTER SPAN FOR OPENING #7
 AS REQUIRED.
  
 2- SPECIFY WHICH ONE IS GOING TO BE THE EMERGENCY
 EGRESS TO COMPLY WITH SEC. R310.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 3- CLEARLY MARK ON SHUTTER DRAWINGS SPECIFIC MOUNTING
 CONDITIONS (EG: WALL MOUNT SECTION "D" AS SHOWN ON
 SHEET 5 OF 13.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-19 Cont ID  
Sent By jgomez Date 2009-02-19 Time 16:55 Rev Time 0.00
Received By jgomez Date 2009-02-19 Time 16:41 Sent To  
Notes
***NONE***