Plan Review Details - Permit 09020337
Plan Review Stops For Permit 09020337
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-03-27 Cont ID  
Sent By btrobaug Date 2009-03-27 Time 17:57 Rev Time 0.00
Received By btrobaug Date 2009-03-27 Time 17:55 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-11 Cont ID  
Sent By btrobaug Date 2009-03-11 Time 13:42 Rev Time 0.00
Received By btrobaug Date 2009-03-11 Time 13:31 Sent To I
Notes
2009-03-11 13:42:50 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2006, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1}.105.3.1.2 NO PERMIT MAY BE ISSUED FOR ANY BUILDING
 CONSTRUCTION, ERECTION, ALTERATION, MODIFICATION,
 REPAIR, OR ADDITION UNLESS THE APPLICANT FOR SUCH
 PERMIT PROVIDES TO THE ENFORCING AGENCY WHICH ISSUES
 THE PERMIT ANY OF THE FOLLOWING DOCUMENTS WHICH APPLY
 TO THE CONSTRUCTION FOR WHICH THE PERMIT IS TO BE
 ISSUED AND WHICH SHALL BE PREPARED BY OR UNDER THE
 DIRECTION OF AN ENGINEER REGISTERED UNDER CHAPTER 471,
 FLORIDA STATUTES: 5. "ANY SPECIALIZED MECHANICAL,
 ELECTRICAL, OR PLUMBING DOCUMENT FOR ANY NEW BUILDING
 OR ADDITION WHICH INCLUDES A MEDICAL GAS, OXYGEN,
 STEAM, VACUUM, TOXIC AIR FILTRATION, HALON, OR FIRE
 DETECTION AND ALARM SYSTEM WHICH COSTS MORE THAN
 $5,000". DOCUMENTS REQUIRING AN ENGINEER SEAL BY THIS
 PART SHALL NOT BE VALID UNLESS A PROFESSIONAL ENGINEER
 WHO POSSESSES A VALID CERTIFICATE OF REGISTRATION HAS
 SIGNED, DATED, AND STAMPED SUCH DOCUMENT AS PROVIDED IN
 SECTION 471.025, FLORIDA STATUTES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-04-13 Cont ID  
Sent By mawillia Date 2009-04-13 Time 12:21 Rev Time 0.00
Received By mawillia Date 2009-04-13 Time 11:38 Sent To  
Notes
2009-04-13 11:54:57*****APPROVED W/PROVISO*****
  
 WORK TO COMPLY WITH NFPA 101 - 2006 EDITION - SECTION
 7.2.1.6.2 FOR ACCESS-CONTROLLED EGRESS DOORS.
  
  
 PLAN SHEET SEC-1 (OF 3) WAS STAMPED, INITIALED, AND
 DATED; READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-03-09 Cont ID  
Sent By mwennerg Date 2009-03-09 Time 09:57 Rev Time 0.00
Received By mwennerg Date 2009-03-09 Time 09:57 Sent To E
Notes
2009-03-09 10:03:36***DENIED***
  
 1) WORK TO COMPLY WITH NFPA 101, 2006 SEC. 7.2.1.6.2.
 FOR ACCESS CONTROLLED EGRESS DOORS.
  
 2) PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-26 Cont ID  
Sent By adarroug Date 2009-03-26 Time 16:25 Rev Time 0.00
Received By adarroug Date 2009-03-26 Time 16:25 Sent To E
Notes
2009-03-26 16:26:19TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-11 Cont ID  
Sent By btrobaug Date 2009-03-11 Time 13:43 Rev Time 0.00
Received By btrobaug Date 2009-02-18 Time 08:29 Sent To PC
Notes
2009-02-18 08:30:05TO "E" BOX