Plan Review Details - Permit 09020290
Plan Review Stops For Permit 09020290
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-06-19 Cont ID  
Sent By jwitmer Date 2009-06-19 Time 10:58 Rev Time 0.77
Received By jwitmer Date 2009-06-19 Time 08:02 Sent To  
Notes
2009-06-19 10:59:23BUILDING PLAN REVIEW
 PERMIT: 09020290
 ADD: 1515 N FLAGLER DR 7TH FLOOR
 CONT: LEIGHTON MCGINN
 TEL: (561)951-0946 MARK ANDREWS
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 PROVISO:
 LEVEL 1 ALTERATION
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THE ORIGINAL
 BUILDING WAS DESIGNED UNDER A WIND ZONE OF 110 MPH,
 FASTEST MILE, UNDER THE 2004 FBC THIS BUILDING IS
 LOCATED IN A 140 MPH WIND ZONE, 3 SECOND GUST. THE 2007
 SUPPLEMENTS TAKES THE BUILDINGS EXPOSURE CATEGORY FROM
 A ???B??? ZONE TO A ???C??? ZONE. THIS IS WHY WE HAVE
 REQUEST THE FOLLOWING INFORMATION.
  
  
 2) MISSING WIND DESIGN INFORMATION.
 603.1.4 WIND DESIGN DATA.
  
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF THE
 LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE
 6-1, ASCE 7 AND BUILDING CLASSIFICATION IN TABLE 1-1,
 ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL
 PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE
 USED FOR THE SELECTION OF EXTERIOR COMPONENTS AND
 CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 3) SINCE THE INTENT IS TO REUSE THE EXISTING GLAZING
 SYSTEM AND THE LOCATION OF THE GLAZING IS 60 FEET ABOVE
 GRADE ONLY WIND PRESSURE NEEDS TO BE MET. THE ENGINEER
 OF RECORD SHALL USE RATIONAL ANALYSIS TO VERIFY THAT
 THE GLAZING SYSTEM CAPABILITY TO WITHSTAND THE HIGHER
 WIND PRESSURES BOTH POSITIVE AND NEGATIVE BEFORE THE
 FIRST INSPECTION.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-24 Cont ID  
Sent By jwitmer Date 2009-04-24 Time 10:32 Rev Time 2.22
Received By jwitmer Date 2009-04-24 Time 10:32 Sent To  
Notes
2009-04-24 11:06:43BUILDING PLAN REVIEW
 PERMIT: 09020290
 ADD: 1515 N FLAGLER DR 7TH FLOOR
 CONT: LEIGHTON MCGINN
 TEL: (561)951-0946 MARK ANDREWS
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) MISSING WIND DESIGN INFORMATION.
 603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) PLANS DO NOT INDICATE THE WORK BEING COVERED UNDER
 THE 2004 EXISTING BUILDING CODE NOR LEVEL OF ALTERATION
 PER 2004 EXISTING BUILDING CODE 301.5 ADESSIGN
 PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 AND 305 OF THIS CODE.
  
 4) MISSING INFORMATION: 2004 EXISTING BUILDING CODE -
 LEVEL ONE -507.3. REPLACEMENT OF WINDOWS AND DOORS.
 THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHT, OPERATIVE AND INOPERATIVE WINDOWS SHALL BE
 DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF
 THE FLORIDA BUILDING CODE, BUILDING.
  
 5) MISSING WINDOW INFORMATION : 1609.1.4 PROTECTION OF
 OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, GLAZING IN BUILDINGS
 SHALL BE IMPACT RESISTANT OR PROTECTED WITH AN IMPACT
 RESISTANT COVERING MEETING THE REQUIREMENTS OF SSTD 12,
 ASTM E 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE
 DOORS AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND
 203 OR AAMA 506 REFERENCED THEREIN AS FOLLOWS:
 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF
 GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 FIXED GLAZING.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) THRESHOLD BUILDING:
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 5A)109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 5B)THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 5C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 6) ADDITIONAL INFORMATION IS REQUIRED, PICTURES TAKEN
 WHEN THE OPENING WAS CREATED INDICATES THE USE OF
 SCAFFOLDING THE FLOOR BELOW FOR THE LENGTH OF THE
 BUILDING WHERE CT SCANNER AND VARIOUS MRI UNITS ARE
 PLACED, PLEASE PROVIDE AN EXPLANATION, HAVE THE SAFE
 LIVE AND DEAD FLOOR LOADS BEEN EXCEDED? THESE FLOORS
 WOULD OF BEEN DESIGNED AS OFFICES WITH A SAFE LIVE LOAD
 OF 50 OR A CONCENTRATED LOAD OF 2,000 PSF OVER A 2.5
 TRIBUTARY AREA. TABLE 1607.1 LIVE LOADS AND 1607.3 LIVE
 LOADS & 1607.4 CONCENTRATED LOADS.
  
 7) DETAIL SHEET FROM ALBERT A. GARGIULO P. E. ONLY ONE
 OF THE THREE DETAILED SHEETS ARE RAISED SEAL ORIGINAL
 SIGNATURE, THEY ARE COPIES.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-02-20 Cont ID  
Sent By mjacobs Date 2009-02-20 Time 07:35 Rev Time 0.00
Received By mjacobs Date 2009-02-20 Time 06:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2009-07-08 Cont ID  
Sent By btrobaug Date 2009-07-08 Time 09:26 Rev Time 0.00
Received By btrobaug Date 2009-07-08 Time 09:03 Sent To  
Notes
2009-07-08 09:05:18 
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-05-08 Cont ID  
Sent By btrobaug Date 2009-05-08 Time 09:27 Rev Time 0.00
Received By btrobaug Date 2009-05-08 Time 09:24 Sent To PC
Notes
2009-05-08 09:26:57 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} THERE IS NO ELECTRICAL WORK SUBMITTED OR SHOWN ON
 THE SUBMITTED PLANS. PLEASE SUBMIT A FLOOR PLAN AND
 INDICATING THE LOCATION OF ALL EQUIPMENT AND DEVICES
 BEING INSTALLED UNDER THE SCOPE OF THIS
 APPLICATION.106.1.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-02-19 Cont ID  
Sent By btrobaug Date 2009-02-19 Time 12:15 Rev Time 0.00
Received By btrobaug Date 2009-02-19 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-06-29 Cont ID  
Sent By mawillia Date 2009-06-29 Time 13:36 Rev Time 0.00
Received By mawillia Date 2009-06-29 Time 13:20 Sent To  
Notes
2009-06-29 13:36:21*****REVISION APPROVED*****
  
 REVISED PLAN SHEET D1/A1 WAS STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-04-24 Cont ID  
Sent By mawillia Date 2009-04-24 Time 13:01 Rev Time 0.00
Received By mawillia Date 2009-04-24 Time 12:43 Sent To  
Notes
2009-04-24 13:01:52*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE
 PERMITTED TO BE OCCUPIED DURING CONSTRUCTION, REPAIR,
 ALTERATIONS, OR ADDITIONS ONLY WHERE REQUIRED MENAS OF
 EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE IN
 PLACE AND CONTINUOUSLY MAINTAINED OR WHERE ALTERNATIVE
 LIFE SAFETY MEASURES ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION ARE IN PLACE. HOW WILL AND/OR HOW HAS
 COMPLIANCE BEEN SATISFIED?
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-02-20 Cont ID  
Sent By mawillia Date 2009-02-20 Time 12:04 Rev Time 0.00
Received By mawillia Date 2009-02-20 Time 11:48 Sent To  
Notes
2009-02-20 11:56:38*****PROVISO*****
  
  
 STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-16 Cont ID  
Sent By lmartine Date 2009-06-16 Time 16:08 Rev Time 0.00
Received By lmartine Date 2009-06-15 Time 16:07 Sent To  
Notes
2009-06-16 16:09:13B-8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-22 Cont ID  
Sent By dpalmer Date 2009-04-22 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2009-04-22 Time 08:26 Sent To  
Notes
2009-04-22 08:27:34TO B-6, BFE, INT DEMO INCREASE SCOPE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-04 Cont ID  
Sent By rregueir Date 2009-03-04 Time 09:23 Rev Time 0.00
Received By rregueir Date 2009-02-17 Time 10:35 Sent To PC
Notes
2009-02-17 10:38:37TO "BOB"#1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-03-04 Cont ID  
Sent By rregueir Date 2009-03-04 Time 09:23 Rev Time 0.00
Received By rregueir Date 2009-03-04 Time 09:23 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-02-27 Cont ID  
Sent By kstevens Date 2009-02-27 Time 16:31 Rev Time 0.00
Received By kstevens Date 2009-02-27 Time 16:31 Sent To  
Notes
2009-02-27 16:31:49NO PLUMBING WORK SHOWN ON PLANS.