Plan Review Details - Permit 09020255
Plan Review Stops For Permit 09020255 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2009-07-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-07-24 |
Time |
14:30 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
2009-07-24 |
Time |
14:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2009-06-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-06-01 |
Time |
09:30 |
Rev Time |
0.85 |
Received By |
jwitmer |
Date |
2009-06-01 |
Time |
08:40 |
Sent To |
|
|
Notes |
2009-06-01 09:32:51 | BUILDING PLAN REVIEW | | PERMIT: 09020255 | | ADD: 1750 FLORIDA MANGO RD | | CONT: CARRICK CONSTRUCTION | | TEL: (954)415-5705 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | MONDAY, JUNE 01-2009 | | 2ND REVIEW | | ACTION: DENIED | | | | 1-2 ) COMPLIED | | 3A-C) SEMI-COMPLIED, THE SHEET SUPPLIED FROM EEI, | | ENGINEERED ENDEVORS INCORPORATED DOES INDICATE THE NEW | | SECTION OF TOWER AND BOLTING TO THE EXISTING TOWER | | STRUCTURE. | | | | 3D) NEW COMMENT DEALS WITH THE ENGINEERS SEAL WITH THE | | WORDING " CERTIFIED". FBC* 106.1 THE NEW TYPE OF | | ENGINEER'S SEAL IS REQUIRED FOR ALL PLANS SEALED AFTER | | 12/31/05. ENGINEER'S SEALS INCLUDING THE WORD | | "CERTIFICATE" ARE NO LONGER VALID. ON 2/5/04 THE | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS AMENDED THE | | 'SEALS' RULE AND REQUIRED THAT ALL MEMBERS OBTAIN SEALS | | WITH THE WORD "LICENSE" INSTEAD OF "CERTIFICATE". THE | | EXTENDED GRACE PERIOD FOR COMPLIANCE ENDED ON 12/31/05. | | (REF: 471.025 F.S. AND RULE 61G15-23.001 F.A.C.) | | | | 3E) EEI IS ALSO MISSING THERE CERTIFICATE OF | | AUTHORIZATION: FBC* 106.1 THE NEW TYPE OF ENGINEER'S | | SEAL IS REQUIRED FOR ALL PLANS SEALED AFTER 12/31/05. | | ENGINEER'S SEALS INCLUDING THE WORD "CERTIFICATE" ARE | | NO LONGER VALID. ON 2/5/04 THE FLORIDA BOARD OF | | PROFESSIONAL ENGINEERS AMENDED THE 'SEALS' RULE AND | | REQUIRED THAT ALL MEMBERS OBTAIN SEALS WITH THE WORD | | "LICENSE" INSTEAD OF "CERTIFICATE". THE EXTENDED GRACE | | PERIOD FOR COMPLIANCE ENDED ON 12/31/05. (REF: 471.025 | | F.S. AND RULE 61G15-23.001 F.A.C.) | | | | 4) 2ND REQUEST, IETS COVER-SHEET; | | 4A) THE REPORT HAS PHOTOCOPIED SIGNATURES, NOT | | ORIGINALS, FL ADMINISTRATIVE CODE: 61G15-23.002(2) FL. | | ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL | | ENGINEER. | | (471.025 F.S. AND 471.023 F.S.). | | | | 4B) 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR | | INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED | | AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF | | THE PRODUCTION & PREPARATION OF EACH SECTION OF THE | | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION | | ON THE COVER SHEET OR INDEX. | | | | 4C) 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE | | TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN | | ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. | | THIS MAY BE ADDED BY HAND. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-03-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-03-09 |
Time |
16:46 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2009-03-09 |
Time |
16:46 |
Sent To |
|
|
Notes |
2009-03-09 16:58:22 | BUILDING PLAN REVIEW | | PERMIT: 09020255 | | ADD: 1750 FLORIDA MANGO RD | | CONT: CARRICK CONSTRUCTION | | TEL: (954)415-5705 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, | | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: | | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | INSPECTION. | | | | 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE | | UPDATE PLANS SHEET 6 OF 8 AND SHEET# 1 OF STRUCTURAL | | CALCULATIONS. | | | | 2) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF | | ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN | | "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE | | REQUIRED. PLEASE PROVIDE AT WHAT ELEVATION THE SLAB | | WILL BE SET, THE FLOODZONE A9- MINIMUM ELEVATION 13.5 | | FT. | | | | 3A) 106.1.2 ADDITIONAL INFORMATION REQUIRED IETS | | STRUCTURAL REPORT INDICATES ON SHEET E-1 WHAT APPEARS | | TO BE THE TOP CONNECTION (SECTION) OF TOWER. THIS | | SECTION IS LOCATED AT HEIGHT 108.8' AND CONTINUES | | THROUGH TO 128.8'. THE PERMIT APPLICATION INDICATES | | ONLY A TEN FOOT SECTION IS BEING ADDED FROM 113' TO | | 123'. PLEASE EXPLAIN THE DIFFERENCE. | | | | 3B) THE IETS CALCULATIONS DO NOT INDICATE HOW THE TOP | | SECTION OF TOWER WILL BE ATTACHED NOR IS THERE ANY | | INFORMATION AS TO THE CONFIGURATION, TYPE OF MATERIAL | | NOR THICKNESS OF MATERIAL THIS NEW TOWER SECTION WILL | | BE CONSTRUCTED FROM, 106.1.2 ADDITIONAL INFORMATION/ | | 1609.6.2.1 MAIN WINDFORCE-RESISTING SYSTEM. | | | | 3C) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE TYPE | | OF CONNECTION THE NEW SECTION OF THE TOWER WILL CONSIST | | OF, 106.1.2 ADDITIONAL INFORMATION. PLEASE ALSO PROVIDE | | WHERE THIS ANYLISS WOULD BE FOUND WITHIN YOUR DOCUMENT? | | 106.1.2 ADDITIONAL INFORMATION/ 1609.6.2.1 MAIN | | WINDFORCE-RESISTING SYSTEM. | | | | 4) IETS COVER-SHEET; | | 4A) THE REPORT HAS PHOTOCOPIED SIGNATURES, NOT | | ORIGINALS, FL ADMINISTRATIVE CODE: 61G15-23.002(2) FL. | | ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL | | ENGINEER. | | (471.025 F.S. AND 471.023 F.S.). | | | | 4B) 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR | | INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED | | AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF | | THE PRODUCTION & PREPARATION OF EACH SECTION OF THE | | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION | | ON THE COVER SHEET OR INDEX. | | | | 4C) 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE | | TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN | | ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. | | THIS MAY BE ADDED BY HAND. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2009-07-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-07-28 |
Time |
11:30 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-07-28 |
Time |
11:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2009-05-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-05-29 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-05-29 |
Time |
16:15 |
Sent To |
|
|
Notes |
2009-05-29 16:18:12 | *** DENIED 2ND REVIEW **** | | | | ** SOME OF THE EXACT SAME NOTES FROM PREVIOUS REVIEW | | STILL NEED TO BE ADDRESSED. | | | | 1) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM | | BUILDING REVIEWER ALSO. THE ENGINEERING LETTER ATTACHED | | TO PLANS FROM IETS DOES NOT CONTAIN AN ORIGINAL | | SIGNATURE. IT IS IN FACT A RUBBER STAMP SIGNATURE. THIS | | IS NOT PERMITTED UNDER FS 471.025. THIS CAN BE | | CONFIRMED WITH THE FLORIDA BOARD OF ENGINEERS. THIS WAS | | NOTED EXACTLY AS PER PREVIOUS REVIEW YET THE SAME | | LETTER WITH THE SAME RUBBER STAMP ON EACH WAS SUBMITTED | | BACK. | | ORIGINAL SIGNATURE IS REQUIRED, FAC 61G15-23.002, | | FS471.025 | | | | 2) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM | | BUILDING REVIEWER. THE DOCUMENTS ATTACHED FOR | | ENGINEERED ENDEAVORS INC ARE SEALED WITH A RAISED SEAL | | WHICH IS NO LONGER IN USE IN THE STATE OF FLORIDA. THE | | SAID SEAL FOR MR. MICHAEL MOREL HAS NOT BEEN VALID FOR | | SEVERAL YEARS. FAC 61G15-23.002 RULING WAS REVISED IN | | FEBRUARY OF 2004 WHICH REQUIRED THE SEAL TO BE REVISED | | TO CONTAIN THE WORDING OF LICENSE INSTEAD OF | | *CERTIFICATE*. AN EXTENSION WAS GIVEN TO DECEMBER 31ST, | | 2005 HOWEVER ALL OLD SEALS AFTER SUCH DATE WERE NO | | LONGER PERMITTED TO BE USED IN THE STATE OF FLORIDA. | | NEW SEAL NEEDS TO BE OBTAINED. | | ** THIS IS ONLY NOTED BY THIS REVIEWER TO GIVE | | INFORMATION AHEAD OF TIME. THIS MAY HELP TO ALLEVIATE | | FURTHER DELAYS. | | | | 3) NOTE: AS NOTED ON PREVIOUS REVIEW. THE SEAL ON THE | | ELECTRICAL PLANS ARE NOT CLEAR AND VISIBLE. EVEN USE OF | | LEAD RUB DOES NOT IDENTIFY THE REQUIRED INFORMATION ON | | SAID SEAL. PLEASE SEE FLORIDA ADMINISTRATIVE CODE | | 61G15-23.002, .001 AND FLORIDA STATUTES 471.025. ALL | | INFORMATION ON SEALS NEEDS TO BE CLEAR AND VISIBLE. | | **ENGINEER MAY RE-SEAL PLANS, SIGN AND DATE IN THIS | | OFFICE IF THIS WOULD HELP WITH THE PROJECT. THE SEAL | | MUST HAVE ALL INFORMATION CLEAR AND VISIBLE. OBTAIN NEW | | SEAL IF IT CAN BE READ. | | | | 4) NOTE: THIS WAS NOTED ON PREVIOUS REVIEW. THERE ARE | | NOW TWO TRANSFER SWITCHES SHOWN ON PLANS. PLEASE SUBMIT | | THE MANUFACTURES SPECS/CUT SHEETS FOR ANY PROPOSED | | TRANSFER SWITCH AUTOMATIC, MANUAL, LEGALLY REQUIRED OR | | OPTIONAL STAND-BY. | | 90.7, 110.3, 701.7, 702.6. NO REVIEW CAN BE DONE AT | | THIS TIME FOR THSE ITEMS. | | ** THE GENERATOR SPECS/CUT SHEETS ARE THE ONLY RELEVANT | | SPECS IN SETS. (ATTACHED TO FRONT) | | | | | | | | | | * IMPORTANT ** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-03-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-03-16 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-03-16 |
Time |
09:37 |
Sent To |
|
|
Notes |
2009-03-16 09:37:46 | ** DENIED ** | | | | | | 1) NOTE: ENGINEERING LETTER ATTACHED TO PLANS FROM IETS | | DOES NOT CONTAIN AN ORIGINAL SIGNATURE. IT IS IN FACT A | | RUBBER STAMP SIGNATURE. THIS IS NOT PERMITTED UNDER FS | | 471.025. THIS CAN BE CONFIRMED WITH THE FLORIDA BOARD | | OF ENGINEERS. | | PLEASE USE ORIGINAL SIGNATURES EVEN IF COMMENT IS NOT | | MADE BY OTHER TRADES. | | | | 2) NOTE: PLEASE PROVIDE COMPLETE DOCUMENTATION ON THE | | TYPE OF GENERATOR SYSTEM BEING INSTALLED. IS THIS A | | LEGALLY REQUIRED SYSTEM? PLEASE SEE 701.11B3. ON SITE | | FUEL IS REQUIRED MEETING MINIMUM TIMES. | | PLEASE SEE FEDERAL CODE OF REGULATIONS TITLE 47 PART 12 | | FOR UPDATES OF SYSTEMS FOR CELL TOWER POWER BACK UP. | | THIS INCLUDES ANY 911 OR E911 SYSTEMS. | | SHEET 4 OF THE SET MENTIONS POSSIBLE BATTERY CABINETS | | HOWEVER THIS WAS NOT LOCATED ON ELECTRICAL SHEETS. ARE | | THERE BATTERY CABINETS PROVIDING 8HRS BACK UP AND THE | | GENERATOR IS IN ADDITION TO THIS? IS THERE NOT GOING TO | | BE ANY GENERATOR AND ONLY BATTERY? SEE NOTE #4 BELOW. | | | | 3) NOTE: THE FOLLOWING CODES NEED TO BE STATED ON | | ELECTRICAL PLANS. | | 2005 NFPA-70. | | | | 4) NOTE: THERE IS CONFUSION OVER WHAT SCOPE OF WORK IS | | BEING APPLIED FOR: THE PERMIT APPLICATION MENTIONS THE | | INSTALLATION OF A PERMANENT GENERATOR, ALONG WITH | | ATTACHED SPECS/CUT SHEETS, AND THE GAS PLAN. HOWEVER | | THE ELECTRICAL PLANS INDICATES A MANUAL TRANSFER SWITCH | | WITH A RECEPTACLE FOR A PORTABLE GENERATOR. THE | | ELECTRICAL RISER INDICATES POSSIBLY BATTERY CABINET OR | | GENERATOR. THE PROPOSED SCOPE OF WORK NEEDS TO BE | | SPECIFIC TO THE LOCATION. THERE ARE TOO MANY UNKNOWNS | | AT THIS TIME FOR THE WORK. | | FBC 106.1.1, 106.1.2, 106.3.5.1.2, 106.5. ( | | ADMINISTRATIVE SECTIONS FOR ADDITIONAL INFORMATION, | | CLARITY AND COORDINATION OF PLANS. | | NEC 2005 ALL CHAPTERS AS APPLICABLE AS THE SCOPE IS NOT | | CLEAR. ALSO SEE NOTES #2 ABOVE. | | | | 5) NOTE: THE SEAL ON THE ELECTRICAL PLANS ARE NOT CLEAR | | AND VISIBLE. EVEN USE OF LEAD RUB DOES NOT IDENTIFY THE | | REQUIRED INFORMATION ON SAID SEAL. PLEASE SEE FLORIDA | | ADMINISTRATIVE CODE 61G15-23.002, .001 AND FLORIDA | | STATUTES 471.025. ALL INFORMATION ON SEALS NEEDS TO BE | | CLEAR AND VISIBLE. | | | | 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | SHEETS FOR ANY PROPOSED TRANSFER SWITCH AUTOMATIC, | | MANUAL, LEGALLY REQUIRED OR OPTIONAL STAND-BY. | | 90.7, 110.3, 701.7, 702.6 | | | | | | | | ** IMPORTANT ** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2009-06-16 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2009-06-16 |
Time |
12:48 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2009-06-16 |
Time |
12:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2009-04-01 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2009-04-01 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2009-04-01 |
Time |
15:09 |
Sent To |
|
|
Notes |
2009-04-01 15:15:09 | ***DENIED*** | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2006. SHT 2 | | OF 8 | | | | 2) GENERATOR AND ASSOCIATED EQUIPMENT MAY REQUIRE | | PROTECTION AGAINST THE POSSIBILITY OF MECHANICAL | | DAMAGE. | | | | 3) WHAT IS THE LOCATION OF REFERENCED EQUIPMENT | | RELATIVE TO NEARBY STRUCTURES? | | | | 4) GENERATOR TO COMPLY WITH NFPA 110, STANDARD FOR | | EMERGENCY AND STANDBY POWER SYSTEMS. | | | | 5) PROVIDE INFORMATION EXPLAINING THE PURPOSE OF THE | | GENERATOR. THE SCOPE OF WORK APPEARS SOMEWHAT | | CONFUSING. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2009-07-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-07-28 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-07-28 |
Time |
16:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2009-05-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-05-28 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-05-28 |
Time |
10:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2009-03-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-03-18 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-03-17 |
Time |
15:07 |
Sent To |
|
|
Notes |
2009-03-18 12:04:31 | DENIED | | REFERENCE: | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | | | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS | | PERMIT: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. -- THE ISOMETRIC AS SHOWN DOES NOT SHOW | | ANY PIPING UNDERGROUND. THE PIPING TO THE METER AND OUT | | OF THE METER DOES NOT DROP DOWN FROM THE METER NOR DOES | | IT RISE UP TO THE METER ON THE SUPPLY SIDE. PLEASE | | CLARIFY. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. -- NOTE ON SHT 1 | | OF 1 NG GENERATOR INSTALLATION STATES, "3/4" BLACK IRON | | PIPE SUITABLE FOR NATURAL GAS ABOVE GROUND TO BE ROUTED | | TO 3/4" POLYETHELENE FROM THE TANK TO THE GENERATOR | | WITH A MINIMU 12-INCHES OF COVER". PLEASE INDICATE WHAT | | TANK. PLEASE SEE COMMENT #1 AS THE ISOMETRIC DOES NOT | | SHOW THE PIPING UNDERGROUND, OR IF PIPING IS SHOWN | | UNDERGROUND, THEN THE METER IS INDICATED BELOW GROUND. | | PLEASE CLARIFY. | | | | 3. ALL SHEETS, THE PROJECT DATA SHALL INCLUDE THE | | FBC-2004 WITH 2007 SUPPLEMENTS. SECTION 106.1.1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2009-07-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-07-14 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-07-14 |
Time |
14:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2009-05-29 |
Time |
|
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-05-19 |
Time |
10:52 |
Sent To |
|
|
Notes |
2009-05-19 10:57:45 | TO COMMERCIAL BOX #C22. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2009-04-01 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2009-04-01 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2009-02-13 |
Time |
11:12 |
Sent To |
|
|
Notes |
2009-02-13 11:12:40 | TO "COMM" BD#28 |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
P |
Date |
2009-05-22 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2009-05-22 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2009-05-22 |
Time |
08:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2009-03-27 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-03-27 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-03-27 |
Time |
14:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2009-06-04 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2009-06-04 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2009-06-04 |
Time |
10:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2009-05-21 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2009-05-21 |
Time |
17:47 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2009-05-21 |
Time |
17:47 |
Sent To |
|
|
Notes |
2009-05-21 17:57:46 | ZONING PLAN REVIEW | | | | PERMIT NO.: 09020255 | | ADDRESS: 1750 FLORIDA MANGO ROAD | | CONTRACTOR/CONTACT: WILL ENGLISH | | TELEPHONE NO.: (954) 415-5705 | | | | REVIEW STATUS: FAILED | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | THE FOLLOWING ARE REPEAT COMMENTS: | | | | 1) PURSUANT TO THE FINAL ORDER ISSUED BY THE ZONING | | BOARD OF APPEALS (ZBA) ON JANUARY 8, 2009, THE | | FOLLOWING ITEMS SHALL BE ADDRESSED: | | | | 1A) PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE | | APPLICANT SHALL OBTAIN APPROVAL FROM THE CITY'S | | ENGINEERING SERVICE DEPARTMENT INDICATING THAT THE | | PROPOSED MECHANICAL PLATFORM WILL NOT NEGATIVELY AFFECT | | THE RETENTION CAPACITY OF THE ADJACENT RETENTION POND. | | ALL DOCUMENTS NECESSARY FOR SUCH DETERMINATION SHALL BE | | PROVIDED BY THE APPLICANT. WHILE YOUR RESPONSE LETTER | | INDICATES THAT THERE WILL BE NO IMPACT, NO SUCH | | APPROVAL WAS PROVIDED FROM THE CITY'S ENGINEERING | | SERVICES DEPARTMENT. | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN ROACH, SENIOR PLANNER | | CITY OF WEST PALM BEACH | | PLANNING AND ZONING DEPARTMENT | | 401 CLEMATIS STREET - P.O. BOX 3366 | | WEST PALM BEACH, FLORIDA 33402 | | | | PHONE: 561.822.1435 | | FAX: 561.822.1459 | | | | EMAIL: [email protected] | | | | WWW.CITYOFWPB.COM | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2009-02-19 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2009-02-19 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2009-02-19 |
Time |
11:46 |
Sent To |
|
|
Notes |
2009-02-19 14:04:48 | ZONING PLAN REVIEW | | | | PERMIT NO.: 09020255 | | ADDRESS: 1750 FLORIDA MANGO ROAD | | CONTRACTOR/CONTACT: THOMAS CARRICK | | TELEPHONE NO.: (954) 415-5705 | | | | REVIEW STATUS: FAILED | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1) PURSUANT TO THE FINAL ORDER ISSUED BY THE ZONING | | BOARD OF APPEALS (ZBA) ON JANUARY 8, 2009, THE | | FOLLOWING ITEMS SHALL BE ADDRESSED: | | | | 1A) PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE | | APPLICANT SHALL OBTAIN APPROVAL FROM THE CITY???S | | ENGINEERING SERVICE DEPARTMENT INDICATING THAT THE | | PROPOSED MECHANICAL PLATFORM WILL NOT NEGATIVELY AFFECT | | THE RETENTION CAPACITY OF THE ADJACENT RETENTION POND. | | ALL DOCUMENTS NECESSARY FOR SUCH DETERMINATION SHALL BE | | PROVIDED BY THE APPLICANT. | | | | 1B) UPON SUBMITTAL OF A BUILDING PERMIT APPLICATION FOR | | THE TOWER EXTENSION, A LANDSCAPE PLAN, SIGNED AND | | SEALED BY A REGISTERED LANDSCAPE ARCHITECT, SHALL BE | | PROVIDED IDENTIFYING THE FOLLOWING: | | | | 1BI) REMOVAL OF ALL PROHIBITED SPECIES FROM THE ENTIRE | | PROPERTY; AND | | | | 1BII) REPLACEMENT OF ALL LANDSCAPING ON THE ENTIRE | | PROPERTY THAT HAS BEEN DAMAGED OR REMOVED SINCE | | DEVELOPMENT OF THE SITE. SUCH LANDSCAPING SHALL | | INCLUDE, BUT NOT BE LIMITED TO TREES AND SHRUBS; AND | | | | 1BIII) INSTALLATION OF SCREENING AROUND THE BASE OF THE | | COMMUNICATIONS TOWER. | | | | 2) PURSUANT TO THE PLANS APPROVED BY THE ZBA, THE | | EQUIPMENT COMPOUND IS TO BE ENCLOSED BY AN EIGHT (8) | | FOOT HIGH WOOD FENCE WITH BARBED WIRE. THIS WAS TO | | APPLY TO THE NEW EQUIPMENT COMPOUND, AS WELL AS | | REPLACEMENT OF THE EXISTING CHAINLINK FENCE WITH A WOOD | | FENCE. ALL GATES WERE TO BE WOOD AS WELL. THE PROPOSED | | PLANS SHOW A CHAIN-LINK FENCE WITH WOOD SLATS. THE WOOD | | FENCE IS REQUIRED...SLATS SHALL NOT BE PERMITTED. IF | | NECESSARY, PLEASE CONTACT ME REGARDING CLARIFICATION OF | | THIS COMMENT. | | | | 3) THE PARENT TRACT DETAIL ON SHEET 3 OF 8 SHOWS THE | | TOWER HEIGHT AT 127 FEET...ALL OTHER REFERENCES | | INDICATE 123 FEET. PLEASE CLARIFY AND ADJUST | | ACCORDINGLY. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | AT (561) 822-1435. | | |
|
|
|