Plan Review Details - Permit 09020255
Plan Review Stops For Permit 09020255
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-24 Cont ID  
Sent By jwitmer Date 2009-07-24 Time 14:30 Rev Time 0.50
Received By jwitmer Date 2009-07-24 Time 14:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-06-01 Cont ID  
Sent By jwitmer Date 2009-06-01 Time 09:30 Rev Time 0.85
Received By jwitmer Date 2009-06-01 Time 08:40 Sent To  
Notes
2009-06-01 09:32:51BUILDING PLAN REVIEW
 PERMIT: 09020255
 ADD: 1750 FLORIDA MANGO RD
 CONT: CARRICK CONSTRUCTION
 TEL: (954)415-5705
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 MONDAY, JUNE 01-2009
 2ND REVIEW
 ACTION: DENIED
  
 1-2 ) COMPLIED
 3A-C) SEMI-COMPLIED, THE SHEET SUPPLIED FROM EEI,
 ENGINEERED ENDEVORS INCORPORATED DOES INDICATE THE NEW
 SECTION OF TOWER AND BOLTING TO THE EXISTING TOWER
 STRUCTURE.
  
 3D) NEW COMMENT DEALS WITH THE ENGINEERS SEAL WITH THE
 WORDING " CERTIFIED". FBC* 106.1 THE NEW TYPE OF
 ENGINEER'S SEAL IS REQUIRED FOR ALL PLANS SEALED AFTER
 12/31/05. ENGINEER'S SEALS INCLUDING THE WORD
 "CERTIFICATE" ARE NO LONGER VALID. ON 2/5/04 THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS AMENDED THE
 'SEALS' RULE AND REQUIRED THAT ALL MEMBERS OBTAIN SEALS
 WITH THE WORD "LICENSE" INSTEAD OF "CERTIFICATE". THE
 EXTENDED GRACE PERIOD FOR COMPLIANCE ENDED ON 12/31/05.
 (REF: 471.025 F.S. AND RULE 61G15-23.001 F.A.C.)
  
 3E) EEI IS ALSO MISSING THERE CERTIFICATE OF
 AUTHORIZATION: FBC* 106.1 THE NEW TYPE OF ENGINEER'S
 SEAL IS REQUIRED FOR ALL PLANS SEALED AFTER 12/31/05.
 ENGINEER'S SEALS INCLUDING THE WORD "CERTIFICATE" ARE
 NO LONGER VALID. ON 2/5/04 THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AMENDED THE 'SEALS' RULE AND
 REQUIRED THAT ALL MEMBERS OBTAIN SEALS WITH THE WORD
 "LICENSE" INSTEAD OF "CERTIFICATE". THE EXTENDED GRACE
 PERIOD FOR COMPLIANCE ENDED ON 12/31/05. (REF: 471.025
 F.S. AND RULE 61G15-23.001 F.A.C.)
  
 4) 2ND REQUEST, IETS COVER-SHEET;
 4A) THE REPORT HAS PHOTOCOPIED SIGNATURES, NOT
 ORIGINALS, FL ADMINISTRATIVE CODE: 61G15-23.002(2) FL.
 ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER.
 (471.025 F.S. AND 471.023 F.S.).
  
 4B) 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF
 THE PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 4C) 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE
 TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-09 Cont ID  
Sent By shill Date 2009-03-09 Time 16:46 Rev Time 2.22
Received By jwitmer Date 2009-03-09 Time 16:46 Sent To  
Notes
2009-03-09 16:58:22BUILDING PLAN REVIEW
 PERMIT: 09020255
 ADD: 1750 FLORIDA MANGO RD
 CONT: CARRICK CONSTRUCTION
 TEL: (954)415-5705
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE
 UPDATE PLANS SHEET 6 OF 8 AND SHEET# 1 OF STRUCTURAL
 CALCULATIONS.
  
 2) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED. PLEASE PROVIDE AT WHAT ELEVATION THE SLAB
 WILL BE SET, THE FLOODZONE A9- MINIMUM ELEVATION 13.5
 FT.
  
 3A) 106.1.2 ADDITIONAL INFORMATION REQUIRED IETS
 STRUCTURAL REPORT INDICATES ON SHEET E-1 WHAT APPEARS
 TO BE THE TOP CONNECTION (SECTION) OF TOWER. THIS
 SECTION IS LOCATED AT HEIGHT 108.8' AND CONTINUES
 THROUGH TO 128.8'. THE PERMIT APPLICATION INDICATES
 ONLY A TEN FOOT SECTION IS BEING ADDED FROM 113' TO
 123'. PLEASE EXPLAIN THE DIFFERENCE.
  
 3B) THE IETS CALCULATIONS DO NOT INDICATE HOW THE TOP
 SECTION OF TOWER WILL BE ATTACHED NOR IS THERE ANY
 INFORMATION AS TO THE CONFIGURATION, TYPE OF MATERIAL
 NOR THICKNESS OF MATERIAL THIS NEW TOWER SECTION WILL
 BE CONSTRUCTED FROM, 106.1.2 ADDITIONAL INFORMATION/
 1609.6.2.1 MAIN WINDFORCE-RESISTING SYSTEM.
  
 3C) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE TYPE
 OF CONNECTION THE NEW SECTION OF THE TOWER WILL CONSIST
 OF, 106.1.2 ADDITIONAL INFORMATION. PLEASE ALSO PROVIDE
 WHERE THIS ANYLISS WOULD BE FOUND WITHIN YOUR DOCUMENT?
 106.1.2 ADDITIONAL INFORMATION/ 1609.6.2.1 MAIN
 WINDFORCE-RESISTING SYSTEM.
  
 4) IETS COVER-SHEET;
 4A) THE REPORT HAS PHOTOCOPIED SIGNATURES, NOT
 ORIGINALS, FL ADMINISTRATIVE CODE: 61G15-23.002(2) FL.
 ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER.
 (471.025 F.S. AND 471.023 F.S.).
  
 4B) 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF
 THE PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 4C) 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE
 TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-28 Cont ID  
Sent By dpalmer Date 2009-07-28 Time 11:30 Rev Time 0.00
Received By dpalmer Date 2009-07-28 Time 11:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-05-29 Cont ID  
Sent By dpalmer Date 2009-05-29 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2009-05-29 Time 16:15 Sent To  
Notes
2009-05-29 16:18:12*** DENIED 2ND REVIEW ****
  
 ** SOME OF THE EXACT SAME NOTES FROM PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM
 BUILDING REVIEWER ALSO. THE ENGINEERING LETTER ATTACHED
 TO PLANS FROM IETS DOES NOT CONTAIN AN ORIGINAL
 SIGNATURE. IT IS IN FACT A RUBBER STAMP SIGNATURE. THIS
 IS NOT PERMITTED UNDER FS 471.025. THIS CAN BE
 CONFIRMED WITH THE FLORIDA BOARD OF ENGINEERS. THIS WAS
 NOTED EXACTLY AS PER PREVIOUS REVIEW YET THE SAME
 LETTER WITH THE SAME RUBBER STAMP ON EACH WAS SUBMITTED
 BACK.
 ORIGINAL SIGNATURE IS REQUIRED, FAC 61G15-23.002,
 FS471.025
  
 2) NOTE: NOTED FOR INFORMATION, LOOK FOR COMMENT FROM
 BUILDING REVIEWER. THE DOCUMENTS ATTACHED FOR
 ENGINEERED ENDEAVORS INC ARE SEALED WITH A RAISED SEAL
 WHICH IS NO LONGER IN USE IN THE STATE OF FLORIDA. THE
 SAID SEAL FOR MR. MICHAEL MOREL HAS NOT BEEN VALID FOR
 SEVERAL YEARS. FAC 61G15-23.002 RULING WAS REVISED IN
 FEBRUARY OF 2004 WHICH REQUIRED THE SEAL TO BE REVISED
 TO CONTAIN THE WORDING OF LICENSE INSTEAD OF
 *CERTIFICATE*. AN EXTENSION WAS GIVEN TO DECEMBER 31ST,
 2005 HOWEVER ALL OLD SEALS AFTER SUCH DATE WERE NO
 LONGER PERMITTED TO BE USED IN THE STATE OF FLORIDA.
 NEW SEAL NEEDS TO BE OBTAINED.
 ** THIS IS ONLY NOTED BY THIS REVIEWER TO GIVE
 INFORMATION AHEAD OF TIME. THIS MAY HELP TO ALLEVIATE
 FURTHER DELAYS.
  
 3) NOTE: AS NOTED ON PREVIOUS REVIEW. THE SEAL ON THE
 ELECTRICAL PLANS ARE NOT CLEAR AND VISIBLE. EVEN USE OF
 LEAD RUB DOES NOT IDENTIFY THE REQUIRED INFORMATION ON
 SAID SEAL. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002, .001 AND FLORIDA STATUTES 471.025. ALL
 INFORMATION ON SEALS NEEDS TO BE CLEAR AND VISIBLE.
 **ENGINEER MAY RE-SEAL PLANS, SIGN AND DATE IN THIS
 OFFICE IF THIS WOULD HELP WITH THE PROJECT. THE SEAL
 MUST HAVE ALL INFORMATION CLEAR AND VISIBLE. OBTAIN NEW
 SEAL IF IT CAN BE READ.
  
 4) NOTE: THIS WAS NOTED ON PREVIOUS REVIEW. THERE ARE
 NOW TWO TRANSFER SWITCHES SHOWN ON PLANS. PLEASE SUBMIT
 THE MANUFACTURES SPECS/CUT SHEETS FOR ANY PROPOSED
 TRANSFER SWITCH AUTOMATIC, MANUAL, LEGALLY REQUIRED OR
 OPTIONAL STAND-BY.
 90.7, 110.3, 701.7, 702.6. NO REVIEW CAN BE DONE AT
 THIS TIME FOR THSE ITEMS.
 ** THE GENERATOR SPECS/CUT SHEETS ARE THE ONLY RELEVANT
 SPECS IN SETS. (ATTACHED TO FRONT)
  
  
  
  
 * IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-16 Cont ID  
Sent By dpalmer Date 2009-03-16 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2009-03-16 Time 09:37 Sent To  
Notes
2009-03-16 09:37:46** DENIED **
  
  
 1) NOTE: ENGINEERING LETTER ATTACHED TO PLANS FROM IETS
 DOES NOT CONTAIN AN ORIGINAL SIGNATURE. IT IS IN FACT A
 RUBBER STAMP SIGNATURE. THIS IS NOT PERMITTED UNDER FS
 471.025. THIS CAN BE CONFIRMED WITH THE FLORIDA BOARD
 OF ENGINEERS.
 PLEASE USE ORIGINAL SIGNATURES EVEN IF COMMENT IS NOT
 MADE BY OTHER TRADES.
  
 2) NOTE: PLEASE PROVIDE COMPLETE DOCUMENTATION ON THE
 TYPE OF GENERATOR SYSTEM BEING INSTALLED. IS THIS A
 LEGALLY REQUIRED SYSTEM? PLEASE SEE 701.11B3. ON SITE
 FUEL IS REQUIRED MEETING MINIMUM TIMES.
 PLEASE SEE FEDERAL CODE OF REGULATIONS TITLE 47 PART 12
 FOR UPDATES OF SYSTEMS FOR CELL TOWER POWER BACK UP.
 THIS INCLUDES ANY 911 OR E911 SYSTEMS.
 SHEET 4 OF THE SET MENTIONS POSSIBLE BATTERY CABINETS
 HOWEVER THIS WAS NOT LOCATED ON ELECTRICAL SHEETS. ARE
 THERE BATTERY CABINETS PROVIDING 8HRS BACK UP AND THE
 GENERATOR IS IN ADDITION TO THIS? IS THERE NOT GOING TO
 BE ANY GENERATOR AND ONLY BATTERY? SEE NOTE #4 BELOW.
  
 3) NOTE: THE FOLLOWING CODES NEED TO BE STATED ON
 ELECTRICAL PLANS.
 2005 NFPA-70.
  
 4) NOTE: THERE IS CONFUSION OVER WHAT SCOPE OF WORK IS
 BEING APPLIED FOR: THE PERMIT APPLICATION MENTIONS THE
 INSTALLATION OF A PERMANENT GENERATOR, ALONG WITH
 ATTACHED SPECS/CUT SHEETS, AND THE GAS PLAN. HOWEVER
 THE ELECTRICAL PLANS INDICATES A MANUAL TRANSFER SWITCH
 WITH A RECEPTACLE FOR A PORTABLE GENERATOR. THE
 ELECTRICAL RISER INDICATES POSSIBLY BATTERY CABINET OR
 GENERATOR. THE PROPOSED SCOPE OF WORK NEEDS TO BE
 SPECIFIC TO THE LOCATION. THERE ARE TOO MANY UNKNOWNS
 AT THIS TIME FOR THE WORK.
 FBC 106.1.1, 106.1.2, 106.3.5.1.2, 106.5. (
 ADMINISTRATIVE SECTIONS FOR ADDITIONAL INFORMATION,
 CLARITY AND COORDINATION OF PLANS.
 NEC 2005 ALL CHAPTERS AS APPLICABLE AS THE SCOPE IS NOT
 CLEAR. ALSO SEE NOTES #2 ABOVE.
  
 5) NOTE: THE SEAL ON THE ELECTRICAL PLANS ARE NOT CLEAR
 AND VISIBLE. EVEN USE OF LEAD RUB DOES NOT IDENTIFY THE
 REQUIRED INFORMATION ON SAID SEAL. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002, .001 AND FLORIDA
 STATUTES 471.025. ALL INFORMATION ON SEALS NEEDS TO BE
 CLEAR AND VISIBLE.
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR ANY PROPOSED TRANSFER SWITCH AUTOMATIC,
 MANUAL, LEGALLY REQUIRED OR OPTIONAL STAND-BY.
 90.7, 110.3, 701.7, 702.6
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-06-16 Cont ID  
Sent By mwennerg Date 2009-06-16 Time 12:48 Rev Time 0.00
Received By mwennerg Date 2009-06-16 Time 12:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-01 Cont ID  
Sent By mwennerg Date 2009-04-01 Time 15:09 Rev Time 0.00
Received By mwennerg Date 2009-04-01 Time 15:09 Sent To  
Notes
2009-04-01 15:15:09***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2006. SHT 2
 OF 8
  
 2) GENERATOR AND ASSOCIATED EQUIPMENT MAY REQUIRE
 PROTECTION AGAINST THE POSSIBILITY OF MECHANICAL
 DAMAGE.
  
 3) WHAT IS THE LOCATION OF REFERENCED EQUIPMENT
 RELATIVE TO NEARBY STRUCTURES?
  
 4) GENERATOR TO COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS.
  
 5) PROVIDE INFORMATION EXPLAINING THE PURPOSE OF THE
 GENERATOR. THE SCOPE OF WORK APPEARS SOMEWHAT
 CONFUSING.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-07-28 Cont ID  
Sent By kstevens Date 2009-07-28 Time 16:43 Rev Time 0.00
Received By kstevens Date 2009-07-28 Time 16:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-05-28 Cont ID  
Sent By kstevens Date 2009-05-28 Time 10:33 Rev Time 0.00
Received By kstevens Date 2009-05-28 Time 10:33 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-03-18 Cont ID  
Sent By kstevens Date 2009-03-18 Time 12:03 Rev Time 0.00
Received By kstevens Date 2009-03-17 Time 15:07 Sent To  
Notes
2009-03-18 12:04:31DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. -- THE ISOMETRIC AS SHOWN DOES NOT SHOW
 ANY PIPING UNDERGROUND. THE PIPING TO THE METER AND OUT
 OF THE METER DOES NOT DROP DOWN FROM THE METER NOR DOES
 IT RISE UP TO THE METER ON THE SUPPLY SIDE. PLEASE
 CLARIFY.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- NOTE ON SHT 1
 OF 1 NG GENERATOR INSTALLATION STATES, "3/4" BLACK IRON
 PIPE SUITABLE FOR NATURAL GAS ABOVE GROUND TO BE ROUTED
 TO 3/4" POLYETHELENE FROM THE TANK TO THE GENERATOR
 WITH A MINIMU 12-INCHES OF COVER". PLEASE INDICATE WHAT
 TANK. PLEASE SEE COMMENT #1 AS THE ISOMETRIC DOES NOT
 SHOW THE PIPING UNDERGROUND, OR IF PIPING IS SHOWN
 UNDERGROUND, THEN THE METER IS INDICATED BELOW GROUND.
 PLEASE CLARIFY.
  
 3. ALL SHEETS, THE PROJECT DATA SHALL INCLUDE THE
 FBC-2004 WITH 2007 SUPPLEMENTS. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-07-14 Cont ID  
Sent By dpalmer Date 2009-07-14 Time 14:40 Rev Time 0.00
Received By dpalmer Date 2009-07-14 Time 14:40 Sent To  
Notes
2009-07-20 09:19:56B-21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2009-05-29 Time   Rev Time 0.00
Received By jgomez Date 2009-05-19 Time 10:52 Sent To  
Notes
2009-05-19 10:57:45TO COMMERCIAL BOX #C22.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-01 Cont ID  
Sent By mwennerg Date 2009-04-01 Time 15:16 Rev Time 0.00
Received By mwennerg Date 2009-02-13 Time 11:12 Sent To  
Notes
2009-02-13 11:12:40TO "COMM" BD#28

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-05-22 Cont ID  
Sent By rkussner Date 2009-05-22 Time 10:37 Rev Time 0.00
Received By rkussner Date 2009-05-22 Time 08:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-03-27 Cont ID  
Sent By rregueir Date 2009-03-27 Time 14:00 Rev Time 0.00
Received By rregueir Date 2009-03-27 Time 14:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2009-06-04 Cont ID  
Sent By jroach Date 2009-06-04 Time 10:52 Rev Time 0.00
Received By jroach Date 2009-06-04 Time 10:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2009-05-21 Cont ID  
Sent By jroach Date 2009-05-21 Time 17:47 Rev Time 0.00
Received By jroach Date 2009-05-21 Time 17:47 Sent To  
Notes
2009-05-21 17:57:46ZONING PLAN REVIEW
  
 PERMIT NO.: 09020255
 ADDRESS: 1750 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: WILL ENGLISH
 TELEPHONE NO.: (954) 415-5705
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 THE FOLLOWING ARE REPEAT COMMENTS:
  
 1) PURSUANT TO THE FINAL ORDER ISSUED BY THE ZONING
 BOARD OF APPEALS (ZBA) ON JANUARY 8, 2009, THE
 FOLLOWING ITEMS SHALL BE ADDRESSED:
  
 1A) PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE
 APPLICANT SHALL OBTAIN APPROVAL FROM THE CITY'S
 ENGINEERING SERVICE DEPARTMENT INDICATING THAT THE
 PROPOSED MECHANICAL PLATFORM WILL NOT NEGATIVELY AFFECT
 THE RETENTION CAPACITY OF THE ADJACENT RETENTION POND.
 ALL DOCUMENTS NECESSARY FOR SUCH DETERMINATION SHALL BE
 PROVIDED BY THE APPLICANT. WHILE YOUR RESPONSE LETTER
 INDICATES THAT THERE WILL BE NO IMPACT, NO SUCH
 APPROVAL WAS PROVIDED FROM THE CITY'S ENGINEERING
 SERVICES DEPARTMENT.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-19 Cont ID  
Sent By jroach Date 2009-02-19 Time 14:04 Rev Time 0.00
Received By jroach Date 2009-02-19 Time 11:46 Sent To  
Notes
2009-02-19 14:04:48ZONING PLAN REVIEW
  
 PERMIT NO.: 09020255
 ADDRESS: 1750 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: THOMAS CARRICK
 TELEPHONE NO.: (954) 415-5705
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PURSUANT TO THE FINAL ORDER ISSUED BY THE ZONING
 BOARD OF APPEALS (ZBA) ON JANUARY 8, 2009, THE
 FOLLOWING ITEMS SHALL BE ADDRESSED:
  
 1A) PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE
 APPLICANT SHALL OBTAIN APPROVAL FROM THE CITY???S
 ENGINEERING SERVICE DEPARTMENT INDICATING THAT THE
 PROPOSED MECHANICAL PLATFORM WILL NOT NEGATIVELY AFFECT
 THE RETENTION CAPACITY OF THE ADJACENT RETENTION POND.
 ALL DOCUMENTS NECESSARY FOR SUCH DETERMINATION SHALL BE
 PROVIDED BY THE APPLICANT.
  
 1B) UPON SUBMITTAL OF A BUILDING PERMIT APPLICATION FOR
 THE TOWER EXTENSION, A LANDSCAPE PLAN, SIGNED AND
 SEALED BY A REGISTERED LANDSCAPE ARCHITECT, SHALL BE
 PROVIDED IDENTIFYING THE FOLLOWING:
  
 1BI) REMOVAL OF ALL PROHIBITED SPECIES FROM THE ENTIRE
 PROPERTY; AND
  
 1BII) REPLACEMENT OF ALL LANDSCAPING ON THE ENTIRE
 PROPERTY THAT HAS BEEN DAMAGED OR REMOVED SINCE
 DEVELOPMENT OF THE SITE. SUCH LANDSCAPING SHALL
 INCLUDE, BUT NOT BE LIMITED TO TREES AND SHRUBS; AND
  
 1BIII) INSTALLATION OF SCREENING AROUND THE BASE OF THE
 COMMUNICATIONS TOWER.
  
 2) PURSUANT TO THE PLANS APPROVED BY THE ZBA, THE
 EQUIPMENT COMPOUND IS TO BE ENCLOSED BY AN EIGHT (8)
 FOOT HIGH WOOD FENCE WITH BARBED WIRE. THIS WAS TO
 APPLY TO THE NEW EQUIPMENT COMPOUND, AS WELL AS
 REPLACEMENT OF THE EXISTING CHAINLINK FENCE WITH A WOOD
 FENCE. ALL GATES WERE TO BE WOOD AS WELL. THE PROPOSED
 PLANS SHOW A CHAIN-LINK FENCE WITH WOOD SLATS. THE WOOD
 FENCE IS REQUIRED...SLATS SHALL NOT BE PERMITTED. IF
 NECESSARY, PLEASE CONTACT ME REGARDING CLARIFICATION OF
 THIS COMMENT.
  
 3) THE PARENT TRACT DETAIL ON SHEET 3 OF 8 SHOWS THE
 TOWER HEIGHT AT 127 FEET...ALL OTHER REFERENCES
 INDICATE 123 FEET. PLEASE CLARIFY AND ADJUST
 ACCORDINGLY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  