Plan Review Stops For Permit 09020226 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2009-02-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2009-02-13 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2009-02-13 |
Time |
10:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-02-12 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2009-02-12 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2009-02-12 |
Time |
07:34 |
Sent To |
|
|
Notes |
2009-02-12 07:34:15 | 2004 FBC W/2007 REVISIONS | | RE-ROOF | | | | DENIED BY BUILDING | | | | 1) SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING | | AT PERIMETER AND CORNER AREAS AS REQUIRED BY LIMITATION | | NUMBER 7 ON PAGE 19 OF THE PRODUCT APPROVAL NOA FOR THE | | TAMKO MODIFIED ROOF SYSTEM. | | | | 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES FOR THE | | TAMKO MODIFIED SYSTEM LISTED IN THE NOA WILL BE | | INSTALLED. | | | | 3) SPECIFY THE FASTENING OPTION AND DESIGN PRESSURE FOR | | THE TAMKO SYSTEM THAT WILL BE USED. | | | | 4) IN ORDER TO VERIFY THE COST OF THE WORK, PLEASE | | SPECIFY THE AREA OF ROOF THAT IS SLOPED AND THE AREA OF | | OF ROOF THAT IS FLAT ON THE PERMIT APPLICATION. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
|