Plan Review Details - Permit 09020219
Plan Review Stops For Permit 09020219
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-25 Cont ID  
Sent By lmartine Date 2009-07-25 Time 13:40 Rev Time 0.00
Received By lmartine Date 2009-07-25 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-06-02 Cont ID  
Sent By lmartine Date 2009-06-02 Time 15:58 Rev Time 0.00
Received By lmartine Date 2009-06-02 Time 15:58 Sent To  
Notes
2009-06-02 15:59:38STRUCT. CALC. FOR LIGHT POLES, OK LM

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-09-07 Cont ID  
Sent By dpalmer Date 2009-09-07 Time 10:35 Rev Time 0.00
Received By dpalmer Date 2009-09-07 Time 10:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-30 Cont ID  
Sent By dpalmer Date 2009-07-30 Time 08:43 Rev Time 0.00
Received By dpalmer Date 2009-07-30 Time 08:43 Sent To PC
Notes
2009-07-30 08:43:53** DENIED REVIEW **
  
 1) NOTE: ES SHEET IS OK WITH ELECTRICAL REVIEW HOWEVER
 THE SHEETS HAVE BEEN VOIDED BY OTHER REVIEWS. AT THIS
 TIME THE ES WILL NOT BE STAMPED BY ELECTRIC.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-02-13 Cont ID  
Sent By dpalmer Date 2009-02-13 Time 17:04 Rev Time 0.00
Received By dpalmer Date 2009-02-13 Time 17:04 Sent To  
Notes
2009-02-13 17:06:34SITE LIGHTING ONLY CONDUITS, POLES.
 SEPARATE ELECTRICAL PERMIT REQUIRED BY LICENSED
 CONTRACTOR.
 WILL REFERENCE THIS PERMIT FOR SITE LIGTHING ELECTRICAL
 PERMIT TURN AROUND. QUESTIONS: SEE DV PALMER.
  
  
 DEWEY PALMER
 561-805-6717

Review Stop ENG ENGINEERING CSD
Rev No 5 Status N Date 2009-09-10 Cont ID  
Sent By mgonzale Date 2009-09-10 Time   Rev Time 0.25
Received By mgonzale Date 2009-09-10 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2009-07-27 Cont ID  
Sent By dlauderm Date 2009-07-27 Time 09:28 Rev Time 3.00
Received By dlauderm Date 2009-07-27 Time 07:34 Sent To  
Notes
2009-07-27 09:44:21PASSED WITH PROVISOS:
 I DO NOT KNOW WHY THESE COMMENTS HAVE NOT BEEN
 ADDRESSED ALREADY, BUT THESE COMMENTS WERE GIVEN TO THE
 CIVIL ENGINEER.
 SHEET C-5:
 1. WATER SERVICES ARE NOT TO BE BUILT AS SHOWN IN THIS
 DETAIL. THE SERVICES WILL BE BUILT ACCORDING TO DETAIL
 WS-1 ON SHEET C7.
 2. A 3/4" METER WILL NOT GIVE THE REQUIRED FLOWS NEEDED
 FOR AN IRRIGATION METER. EITHER REDESIGN THE IRRIGATION
 SYSTEM, OR CHANGE THE DRAWING TO SHOW A 2" WATER
 SERVICE WITH A 1-1/2" IRRIGATION METER. A 3/4" METER
 WILL ONLY GIVE YOU 15 GPM AT A MAXIMUM CONTINUOUS FLOW
 RATE. A 1" METER WILL ONLY GIVE YOU 25 GPM MAX. CON.
 RATE. YOUR IRRIGATION PLANS SHOW 2 ZONES OVER 25 GPM,
 WHICH EXCEEDS A 1" METER, 10 OF THE ZONES EXCEEDS THE
 15 GPM RATE OF A 3/4" METER.
 3. THE STREET LIGHT POLE IS DESIGNATED TO BE RELOCATED
 BY OTHERS, THE OTHERS IS NOT THE CITY OF WEST PALM
 BEACH. IF THE LIGHT POLE IS IN THE WAY OF THE PROPOSED
 DRIVEWAY IT IS THE DEVELOPERS RESPONSIBILITY TO HAVE IT
 RELOCATED.
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2009-03-27 Cont ID  
Sent By dlauderm Date 2009-03-27 Time 11:29 Rev Time 0.00
Received By dlauderm Date 2009-03-27 Time 11:25 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2009-03-11 Cont ID  
Sent By mgonzale Date 2009-03-11 Time 16:26 Rev Time 1.00
Received By mgonzale Date 2009-03-11 Time 16:25 Sent To  
Notes
2009-03-11 16:28:07**** APPROVED AS-NOTED ******
  
 ROOF DRAIN LINES HAVE 1' OF VERTICAL COVER IN SOME AREA
 ON-SITE
 (EOR SHOULD CONSIDER CHANGING DESIGN TO MAKE THESE
 DEEPER SO THAT TRAFFIC LOAD DOES NOT HINDER THESE PIPES
 OR THEIR FLOW)
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-02-17 Cont ID  
Sent By lmartine Date 2009-02-17 Time 13:43 Rev Time 0.00
Received By lmartine Date 2009-02-17 Time 13:43 Sent To  
Notes
2009-02-17 13:54:11REVIEW WILL REMAIN IN FAILED STATUS UNTIL THE CITY'S
 ENGINNEERING REVIEW IS APPROVED AT 45TH ST. LM

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-09-15 Cont ID  
Sent By mawillia Date 2009-09-15 Time 12:35 Rev Time 0.00
Received By mawillia Date 2009-09-15 Time 12:21 Sent To  
Notes
2009-09-15 12:35:43*****APPROVED*****
  
  
 PLAN SHEET C-3, WHICH WAS PREVIOUSLY FIRE-STAMPED BY
 M.R.WENNERGREN ON 02/17/09 AND M.A.WIILIAMS ON
 03/26/09, WAS STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-07-20 Cont ID  
Sent By mawillia Date 2009-07-20 Time 12:14 Rev Time 0.00
Received By mawillia Date 2009-07-20 Time 12:07 Sent To  
Notes
2009-07-20 12:13:52*****FIRE STAMPING NEEDED*****
  
  
 PLAN SHEET C-3, WHICH WAS PREVIOUSLY FIRE-STAMPED BY
 M.R.WENNERGREN ON 02/17/09 AND M.A.WIILIAMS ON
 03/26/09, TO BE FIRE-STAMPED WHEN THE OTHER TRADE
 REVIEWS HAVE BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-26 Cont ID  
Sent By mawillia Date 2009-03-26 Time 13:00 Rev Time 0.00
Received By mawillia Date 2009-03-26 Time 12:47 Sent To  
Notes
2009-03-26 13:00:25*****APPROVED*****
  
  
 PLAN SHEET C-3, WHICH WAS PREVIOUSLY FIRE-STAMPED BY
 M.R.WENNERGREN ON 02/17/09, WAS AGAIN STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-02-17 Cont ID  
Sent By mwennerg Date 2009-02-17 Time 11:36 Rev Time 0.00
Received By mwennerg Date 2009-02-17 Time 11:36 Sent To  
Notes
2009-02-17 11:39:121) EMERGENCY VEHICLE ACCESS TO COMPLY WITH NFPA 1, 2006
 CHAPTER-18.
  
 2) EXISTING AND OR NEW FIRE HYDRANTS SHALL BE FULLY
 OPERATIVE PRIOR TO, DURING AND AFTER CONSTRUCTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-31 Cont ID  
Sent By lmartine Date 2009-08-31 Time 14:28 Rev Time 0.00
Received By lmartine Date 2009-08-31 Time 14:28 Sent To  
Notes
2009-08-31 14:29:20C-11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-17 Cont ID  
Sent By shill Date 2009-06-17 Time 15:05 Rev Time 0.00
Received By shill Date 2009-06-17 Time 15:05 Sent To  
Notes
2009-06-17 15:08:03C 9
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-03 Cont ID  
Sent By adarroug Date 2009-03-03 Time 15:58 Rev Time 0.00
Received By adarroug Date 2009-03-03 Time 15:58 Sent To  
Notes
2009-03-03 16:01:50TO "COMM" BD#33

Review Stop L LANDSCAPING
Rev No 4 Status F Date 2009-09-29 Cont ID  
Sent By rkussner Date 2009-09-29 Time 17:11 Rev Time 0.00
Received By rkussner Date 2009-09-29 Time 17:11 Sent To  
Notes
2009-09-29 17:16:35***LANDSCAPE REVIEW FAILED***
  
 1. THE LOCATION OF THE STREET LIGHTS SHOWN ON THE
 PHOTOMETRIC PLAN IS STILL NOT CONSISTENT WITH THE
 LANDSCAPE PLAN. ALL PLANS SHALL BE CONSISTENT. ALSO,
 THE LIGHTS SHALL BE CENTERED BETWEEN THE TREES TO AVOID
 BLOCKAGE OF THE LIGHT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2009-06-18 Cont ID  
Sent By rkussner Date 2009-06-18 Time 09:45 Rev Time 0.00
Received By rkussner Date 2009-06-18 Time 09:45 Sent To  
Notes
2009-06-18 10:21:04***LANDSCAPE REVIEW FAILED***
  
 1. THE LOCATION OF THE PROPOSED SITE LIGHTING SHOWN ON
 THE PHOTOMETRIC PLAN DOES NOT CORRESPOND WITH THE
 LANDSCAPE PLAN. ALL PLANS SHALL BE CONSISTENT. LIGHT
 POLES SHALL BE CENTERED BETWEEN THE TREES. ALSO, THERE
 IS A 2 FOOT VEHICLE OVERHANG AREA ALONG THE EAST AND
 SOUTH SIDES OF THE SITE. THE POLES CANNOT BE PLACED
 WITHIN THE OVERHANG AREA.
  
 2. THE DOUBLE SIDED WHEEL STOP SHOWN ON SHEET C-6 DOES
 NOT MEET CITY REQUIREMENTS.
  
 3. SUBMIT A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN
 DOWN INTO UNIT COST.
  
 4. AN IRRIGATION PERMIT IS REQUIRED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-03-10 Cont ID  
Sent By jroach Date 2009-03-10 Time 18:43 Rev Time 0.00
Received By jroach Date 2009-03-10 Time 18:43 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-02-13 Cont ID  
Sent By jroach Date 2009-02-13 Time 10:40 Rev Time 0.00
Received By jroach Date 2009-02-13 Time 10:40 Sent To  
Notes
2009-02-13 10:40:17SEE ZONING COMMENTS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-09-08 Cont ID  
Sent By kstevens Date 2009-09-08 Time 17:42 Rev Time 0.00
Received By kstevens Date 2009-09-08 Time 17:42 Sent To  
Notes
2009-09-08 17:42:53REVISIONS OK -- SHTS L-3 & L-4.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-03-04 Cont ID  
Sent By kstevens Date 2009-03-04 Time 17:28 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-02-13 Cont ID  
Sent By kstevens Date 2009-02-13 Time 17:19 Rev Time 0.00
Received By kstevens Date 2009-02-13 Time 17:19 Sent To  
Notes
2009-02-13 17:37:31DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS L-3, L-4 & L-5 THE ADDRESS OF RECORD OF THE
 DESIGN PROFESSIONAL ON THE FLORIDA STATE DBPR WEBSITE,
 (10748 DEERWOOD PARK BLVD. SOUTH JACKSONVILLE, FL) DOES
 NOT REFLECT THE ADDRESS INDICATED ON THE TITLE BLOCKS,
 (1715 N. WESTSHORE BLVD. TAMPA FLORIDA). FAC
 61G1-16.004(1) & FS 481.306. PLEASE UPDATE THE TITLE
 BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING PLANS
 FOR REVIEW.
  
 1. SHT L-3 PLEASE INDICATE THE LOCATION OF THE BACKFLOW
 PREVENTER AND THE RAIN SENSOR ON THE IRRIGATION PLAN.
 SECTIONS 106.1.2 AND APPENDIX F(J) AS WELL AS FS
 3373.62. PLEASE INDICATE IF THERE WILL BE A SEPARATE
 METER FOR THE IRRIGATION. IF CONNECTING TO THE WATER
 SERVICE FOR THE BUILDING, THEN A REDUCED PRESSURE
 BACKFLOW CAN BE USED. TABLE 608.1. (SEE CIVIL SHEET C7
 UTILITY DETAIL
  
 3. SHT L-4 DETAIL 5/L-04 DOUBLE CHECK ASSEMBLY IS NOT
 APPROVED. AN RPZV BACKFLOW PREVENTOR IS REQUIRED.
 SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 4 Status F Date 2009-09-14 Cont ID  
Sent By jroach Date 2009-09-14 Time 22:02 Rev Time 0.00
Received By jroach Date 2009-09-14 Time 22:02 Sent To  
Notes
2009-09-14 22:04:17ZONING PLAN REVIEW
  
 PERMIT NO.: 090200219
 ADDRESS: 1615 PALM BEACH LAKES BOULEVARD
 CONTRACTOR/CONTACT: NEYITA LEIVA
 TELEPHONE NO.: 561.856.6655
  
 REVIEW STATUS: FAILED
  
 THE FOLLOWING ARE REPEAT COMMENTS FROM THE PREVIOUS
 REVIEW. PLEASE PROVIDE A WRITTEN RESPONSE TO THE
 FOLLOWING PLAN REVIEW COMMENTS:
  
 1) NOT ALL LANDSCAPE COMMENTS FROM THE PREVIOUS REVIEW
 HAVE BEEN ADDRESSED. PLEASE NOTE THE FOLLOWING:
  
 A) THE LOCATION OF THE PROPOSED SITE LIGHTING SHOWN ON
 THE PHOTOMETRIC PLAN DOES NOT CORRESPOND WITH THE
 LANDSCAPE PLAN. ALL PLANS SHALL BE CONSISTENT.
  
 THE FOLLOWING COMMENTS ARE BASED UPON THE RECENT
 SUBMITTAL:
  
 1) IT APPEARS THAT THE REVISED LOCATION OF THE SANITARY
 LINE (AS SHOWN ON SHEET C-5) CONFLICTS WITH THE
 INSTALLATION OF TREES ALONG THE NORTH PROPERTY LINE.
 PLEASE CLARIFY.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2009-06-30 Cont ID  
Sent By jroach Date 2009-06-30 Time 09:54 Rev Time 0.00
Received By jroach Date 2009-06-30 Time 09:54 Sent To  
Notes
2009-06-30 09:55:45SEE LANDSCAPE REVIEW COMMENTS. ONCE LANDSCAPE REVIEW
 HAS BEEN PASSED, ZONING REVIEW WILL ALSO BE PASSED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-03-10 Cont ID  
Sent By jroach Date 2009-03-10 Time 18:43 Rev Time 0.00
Received By jroach Date 2009-03-10 Time 18:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-03-27 Cont ID  
Sent By jroach Date 2009-02-13 Time 10:30 Rev Time 0.00
Received By jroach Date 2009-02-13 Time 10:30 Sent To  
Notes
2009-02-13 10:39:52ZONING PLAN REVIEW
  
 PERMIT NO.: 090200219
 ADDRESS: 1615 PALM BEACH LAKES BOULEVARD
 CONTRACTOR/CONTACT: RICHARD RHODES
 TELEPHONE NO.: (954) 429.3700
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) INFORMAL SITE PLAN REVIEW APPLICATION MUST BE
 APPROVED PRIOR TO THE ISSUANCE OF A BUILDING PERMIT. AS
 PER DISCUSSIONS WITH WACHOVIA, THERE ARE FEW
 OUTSTANDING ISSUES THAT ARE BEING RESOLVED WITH THE
 CITY???S ENGINEERING SERVICES DEPARTMENT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  