Plan Review Details - Permit 09020198
Plan Review Stops For Permit 09020198
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-06 Cont ID  
Sent By jgomez Date 2009-05-06 Time 15:31 Rev Time 0.00
Received By jgomez Date 2009-05-06 Time 14:25 Sent To PC
Notes
2009-05-06 15:32:07NEED REVISED ENERGY CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-10 Cont ID  
Sent By jgomez Date 2009-03-10 Time 10:29 Rev Time 0.00
Received By jgomez Date 2009-03-10 Time 10:01 Sent To PC
Notes
2009-03-10 10:51:20RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- REVISE ENERGY CALCULATIONS:
 A) NEED TO USE REVISED FORM 600C-04R. FORM SUBMITTED IS
 NOT THE REVISED ONE.
  
 B) COMPLETE ALL INFORMATION ON TOP OF FORM INCLUDING
 PERMITTING OFFICE (CITY OF WEST PALM BEACH) AND
 JURISDICTION # (604700).
  
 C) COMPLETE ITEM #2.
  
 D) REVISE ITEM #10A. MIN. UNDER ATTIC INSULATION IS
 R-30 AS REQUIRED BY TABLE 6C-1 ON SECOND PAGE OF ENERGY
 CALCULATIONS.
  
 E) COMPLETE INFORMATION ON TABLE 6C-2 ON SECOND PAGE OF
 ENERGY CALCULATIONS.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR WINDOW MULLIONS AS SHOWN ON PLANS.
 **NOTE: CLEARLY SPECIFY ON PRODUCT APPROVAL MULLION
 SIZE AND ANCHORING TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVED IN WRITING
 MULLION PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 5- ENGINEER TO PROVIDE HIS LICENSE NUMBER IN ALL SHEETS
 TITLE BLOCK AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 6- ENGINEERING DRAWING SHEET #2:
 A) REVISE DESIGN CRITERIA: THIS IS THE CITY OF WEST
 PALM BEACH JURISDICTION NOT CITY OF PORT ST. LUCIE.
  
 B) UPDATE INFORMATION REFER TO FBC 2004 WITH 2007
 REVISIONS, NOT 2006.
  
 C) ENGINEER SPECIFIES IMPACT RESISTANT ASSEMBLY FOR
 COMPONENTS AND CLADDING. PRODUCT APPROVALS SUBMITTED
 FOR FRENCH DOORS AND FIXED WINDOWS ARE FOR NON-IMPACT
 ASSEMBLIES. SPECIFY HOW COMPLYING WITH THE GLASS IMPACT
 PROTECTION OF SEC. R301.2.1.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 ***NOTE: IF USING ANY TYPE SHUTTERS FOR IMPACT
 PROTECTION, THEN PROVIDE COMPLETE INSTALLATION SCHEDULE
 (SEE ATTACHED SAMPLE) AND PROVIDE PRODUCT APPROVALS
 REVIEWED AND APPROVED BY THE ENGINEER OF RECORD.
  
 D) CLARIFY WHY NOT SPECIFYING VERTICAL REINFORCEMENT AT
 EACH END OF DOUBLE WINDOW OPENING TO VERIFY COMPLIANCE
 WITH SEC. R606 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-02-12 Cont ID  
Sent By btrobaug Date 2009-02-12 Time 08:37 Rev Time 0.00
Received By btrobaug Date 2009-02-12 Time 07:02 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 14:23 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 14:23 Sent To  
Notes
2009-04-29 14:27:19TO R-23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 11:20 Rev Time 0.00
Received By jgomez Date 2009-02-24 Time 11:20 Sent To B
Notes
2009-02-24 11:21:16TO "SFR" "BLDG"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-10 Cont ID  
Sent By jgomez Date 2009-03-10 Time 11:11 Rev Time 0.00
Received By jgomez Date 2009-02-11 Time 16:21 Sent To  
Notes
2009-02-11 16:21:19TO "SFR" "Z"

Review Stop Z ZONING
Rev No 1 Status P Date 2009-02-23 Cont ID  
Sent By mcruz Date 2009-02-23 Time 08:29 Rev Time 0.00
Received By mcruz Date 2009-02-23 Time 08:29 Sent To I
Notes
***NONE***