Plan Review Details - Permit 09020142
Plan Review Stops For Permit 09020142
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-01 Cont ID  
Sent By rmcdouga Date 2009-04-01 Time 15:31 Rev Time 0.00
Received By rmcdouga Date 2009-04-01 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-17 Cont ID  
Sent By rmcdouga Date 2009-02-17 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2009-02-17 Time 08:56 Sent To  
Notes
2009-02-17 09:24:212004 FBC W/2007 REVISIONS
 INSTALL FABRIC AWNING
  
 DENIED BY BUILDING
  
 1) ADDRESS ZONING COMMENTS.
  
 2) SHOW COMPLIANCE WITH FBC 3105.1.1.1 FABRIC AWNINGS
 AND FABRIC-COVERED FRAMES LOCATED OVER PUBLIC PROPERTY
 OR IN AREAS ACCESSIBLE TO THE GENERAL PUBLIC SHALL BE
 CONSTRUCTED SO THAT NO RIGID PART OF SUCH FABRIC
 AWNINGS OR FABRIC-COVERED FRAMES SHALL BE LESS THAN 7
 FEET, 6 INCHES (2286 MM) FROM THE GRADE DIRECTLY BELOW,
 AND NO PART OF THE CLOTH DROP SHALL BE LESS THAN 7 FEET
 (2134 MM).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-27 Cont ID  
Sent By mcruz Date 2009-03-27 Time 10:18 Rev Time 0.00
Received By mcruz Date 2009-03-25 Time 10:18 Sent To Z
Notes
2009-03-27 10:19:14DELIVERED TO ES IN ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-13 Cont ID  
Sent By adarroug Date 2009-02-13 Time 14:58 Rev Time 0.00
Received By adarroug Date 2009-02-13 Time 14:58 Sent To  
Notes
2009-02-13 14:59:33TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-17 Cont ID  
Sent By rmcdouga Date 2009-02-17 Time 09:24 Rev Time 0.00
Received By rmcdouga Date 2009-02-06 Time 10:12 Sent To  
Notes
2009-02-06 10:12:31TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2009-03-31 Cont ID  
Sent By eschneid Date 2009-03-31 Time 10:23 Rev Time 0.25
Received By eschneid Date 2009-03-31 Time 10:23 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-12 Cont ID  
Sent By eschneid Date 2009-02-12 Time 16:29 Rev Time 0.50
Received By eschneid Date 2009-02-12 Time 16:29 Sent To I
Notes
2009-02-12 16:30:05FAILED
  
 1) THE CITYPLACE "APPROVED" STAMP IS REQUIRED ON THE
 AWNING COLOR SHEET.
  
 2) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS
 MUST PROVIDE A MINIMUM OF EIGHT (8) FEET OF CLEARANCE
 BETWEEN THE FLOOR AND THE LOWEST POINT OF THE AWNING.
 PLEASE PROVIDE THE HEIGHT INFORMATION.
  
 3) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS
 ON THE SECOND FLOOR SHALL PROJECT THREE (3) FEET FROM
 THE BUILDING FACADE. THE AWNING IS SHOWN PROJECTING 7'
 3-1/2" FROM THE BUILDING FACADE.
  
 4) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT BOTH
 SIDES OF A SHED AWNING MUST BE OPEN. UNABLE TO TELL
 FROM DRAWINGS IF THE END OF THE AWNING NOT AFFIXED TO
 THE WALL IS OPEN. PLEASE PROVIDE INFORMATION.
  
 5) THE CITYPLACE MASTER SIGN PLAN DOES NOT ALLOW
 VALANCES ON SECOND STORY AWNINGS. UNABLE TO TELL FROM
 THE DRAWINGS IF AWNING HAS VALANCES. PLEASE PROVIDE
 INFORMATION.
  
 6) THE CITYPLACE MASTER SIGN PLAN ALLOWS VARIANCES FROM
 THE PROVISIONS OF 2, 3, 4 & 5 ABOVE. PROVIDE A
 NOTARIZED LETTER FROM CITYPLACE THAT THEY HAVE GRANTED
 THE SPECIFIC VARIANCES NEEDED TO CONSTRUCT THE PROPOSED
 AWNINGS OR REVISE AWNINGS TO ADHERE TO THE CITYPLACE
 MASTER SIGN PLAN REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  