Plan Review Details - Permit 09020141
Plan Review Stops For Permit 09020141
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-21 Cont ID  
Sent By shill Date 2009-04-21 Time 15:08 Rev Time 0.00
Received By shill Date 2009-04-21 Time 15:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-06 Cont ID  
Sent By shill Date 2009-04-06 Time 09:37 Rev Time 0.00
Received By shill Date 2009-04-06 Time 09:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-05 Cont ID  
Sent By shill Date 2009-03-05 Time 10:37 Rev Time 0.00
Received By shill Date 2009-03-05 Time 10:37 Sent To  
Notes
2009-03-05 10:42:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. POOL SAFETY NOTE DOES NOT COMPLY WITH FBC R4101.7.
 IT STATES ONE OF THE FOLLOWING MUST BE INSTALLED;
 OPTIONS 3 AND 4 ARE TO BE INSTALLED WHEN THE HOUSE WALL
 IS USED AS A PART OF THE BARRIER, BUT THE PRIMARY
 BARRIER NOT NOTED. PLEASE REVISE NOTE TO COMPLY.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-03-24 Cont ID  
Sent By btrobaug Date 2009-03-24 Time 14:13 Rev Time 0.00
Received By btrobaug Date 2009-03-24 Time 14:00 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-18 Cont ID  
Sent By btrobaug Date 2009-02-18 Time 10:15 Rev Time 0.00
Received By btrobaug Date 2009-02-18 Time 09:42 Sent To P
Notes
2009-02-18 10:15:19 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE FOLLOWING ARE NONCOMPLIANT WITH 106.1.1 FBC AS
 AMENDED:"CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5)."
  
 1} THE POOL SPECIFICATIONS DO NOT INCLUDE THE HEAT PUMP
 FOR WHICH SPECIFICATIONS WERE SUBMITTED.
  
 2} THE HEAT PUMP IS NOT SHOWN IN THE ELECTRICAL
 DIAGRAM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2009-02-26 Cont ID  
Sent By kstevens Date 2009-02-26 Time 14:49 Rev Time 0.00
Received By kstevens Date 2009-02-26 Time 14:49 Sent To  
Notes
2009-02-26 14:50:18NO GAS PIPING OR GAS APPLIANCE INDICATED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-04-09 Cont ID  
Sent By adarroug Date 2009-04-09 Time 09:38 Rev Time 0.00
Received By adarroug Date 2009-04-09 Time 09:38 Sent To Z
Notes
2009-04-09 09:39:07TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-10 Cont ID  
Sent By adarroug Date 2009-03-10 Time 09:11 Rev Time 0.00
Received By adarroug Date 2009-03-10 Time 09:11 Sent To Z
Notes
2009-03-10 09:12:05TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-17 Cont ID  
Sent By adarroug Date 2009-02-17 Time 09:37 Rev Time 0.00
Received By adarroug Date 2009-02-17 Time 09:37 Sent To E
Notes
2009-02-17 09:37:51TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-05 Cont ID  
Sent By shill Date 2009-03-05 Time 10:42 Rev Time 0.00
Received By shill Date 2009-02-06 Time 08:50 Sent To  
Notes
2009-02-06 08:50:27TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-04-03 Cont ID  
Sent By kstevens Date 2009-04-03 Time 13:23 Rev Time 0.00
Received By kstevens Date 2009-04-03 Time 13:23 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-02-26 Cont ID  
Sent By kstevens Date 2009-02-26 Time 14:50 Rev Time 0.00
Received By kstevens Date 2009-02-26 Time 14:50 Sent To B1
Notes
2009-02-26 15:16:23DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL CODE
 FBC-2004 CHAPTER 1
  
 1. THE PLANS SHOW DETAILS THAT ARE NOT CLEAR OR
 LEGIBLE. (SEE VENT DETAIL, MAIN DRAIN DETAIL,
 ATMOSPHERIC VENT DETAIL ETC). SECTION 106.1.1
 CONSTRUCTION DOCUMENTS.
  
 2. A TIME CLOCK IS REQUIRED FOR RESIDENTIAL POOLS PER
 SECTION 13-612.1.ABC.2.3.3 AND A POOL COVER IS REQUIRED
 PER SECTION 13-612.1.ABC.2.3.2. PLEASE INDICATE THESE
 REQUIREMENTS ON THE PLANS.
  
 3. THE POOL PIPING SCHEMATIC DOES NOT REFLECT THE POOL
 PLAN. THE SCHEMATIC SHOWS SPA MAIN DRAINS AND SPA INLET
 BUT NO SPA IS INDICATED ON THE POOL LAYOUT. PLEASE
 CORRELATE. SECTION 106.1.1
  
 4. THE POOL PIPING SCHEMATIC DOES NOT SHOW A POOL
 HEATER, BUT THERE IS A POOL HEATER MANUFACTURE
 SPECIFICATION SHEET SUBMITTED. PLEASE CLARIFY. SECTION
 106.1.1.
  
 5. FBC-2004 424.2.6.6.2, OR FBCR-2004
 SEC R4101.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES).
  
 6. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES).
  
 7. FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (ADD TO NOTES).
  
 8. FBC-2004 SEC. 424.2.13.2, OR
 FBCR-2004 SEC.R4101.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES).
  
 9. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF. (MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT). -- NOT SHOWN ON MANUF.
 SHEETS.
  
 10. FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-04-20 Cont ID  
Sent By mcruz Date 2009-04-20 Time 12:44 Rev Time 0.00
Received By mcruz Date 2009-04-20 Time 12:32 Sent To B
Notes
2009-04-20 12:56:53SENT TO SHILL

Review Stop Z ZONING
Rev No 2 Status F Date 2009-03-17 Cont ID  
Sent By mcruz Date 2009-03-17 Time 19:20 Rev Time 0.00
Received By mcruz Date 2009-03-17 Time 19:04 Sent To E
Notes
2009-03-17 19:20:07PLANNING AND ZONING DEPT: ***ZONING FAILED - 1ST
 RESUB***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-304(D)(2)(B-E):
  
 B. EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
  
 C. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 D. IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT TO OR
 SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN AWAY
 FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
 E. FOR A DOUBLE FRONTAGE LOT, A SWIMMING POOL MAY BE
 LOCATED ALONG THAT STREET FRONTAGE THAT IS THE
 PREDOMINANT LOCATION OF SWIMMING POOLS ALONG THAT SAME
 STREET. THE MINIMUM SETBACK FOR THE WATER'S EDGE,
 SCREEN ENCLOSURES AND APPURTENANCES FROM THE PROPERTY
 LINE SHALL BE FIVE FEET. A LANDSCAPE BUFFER ALONG THE
 POOL'S STREET FRONTAGE IS REQUIRED THAT IS CONSISTENT
 WITH SUBSECTION C. ABOVE.
  
 PROVIDE A DETAIL OF THE LANDSCAPE BUFFER AS DESCRIBED
 IN SUBSECTION C. ABOVE. BASED ON THE AERIAL, SCREENING
 MAY ALREADY EXIST ON THE PROPERTY, IF APPLICABLE,
 PLEASE PROVIDE A DETAIL OF EXISTING SCREENING ALREADY
 IN PLACE.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-13 Cont ID  
Sent By mcruz Date 2009-02-13 Time 14:01 Rev Time 0.00
Received By mcruz Date 2009-02-13 Time 13:58 Sent To I
Notes
2009-02-13 14:00:59PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO AN
 REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  