Plan Review Details - Permit 09020126
Plan Review Stops For Permit 09020126
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-02 Cont ID  
Sent By shill Date 2009-03-02 Time 09:06 Rev Time 0.00
Received By shill Date 2009-03-02 Time 09:06 Sent To  
Notes
2009-03-02 09:13:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. ACCESSIBLE PARKING IS TO BE DISPERSED, FBC11-4.6.2.
 AN ADDITION IS SHOWN (NORTH, CENTER) BUT NO ACCESSIBLE
 PARKING SHOWN FOR THIS BUILDING. INDICATE LOCATION OF
 PROPOSED ACCESSIBLE ENTRANCE(S).
  
 2. DELCARE TOTAL NUMBER OF PARKING SPACES AND THE TOTAL
 NUMBER OF ACCESSIBLE SPACES, FBC11-4.1.2(5)(A).
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-24 Cont ID  
Sent By dpalmer Date 2009-02-24 Time 08:48 Rev Time 0.00
Received By dpalmer Date 2009-02-24 Time 08:48 Sent To  
Notes
2009-02-24 08:48:14** DENIED **
  
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON THE PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2006 NFPA-101
 THE 2006 LIFE SAFETY CODE CHANGED DECEMBER 31ST, 2008
 FAC69A-60.004
 2002 NFPA-72 (WHEN APPLICABLE).
  
 2) NOTE: PLEASE SUBMIT WORST CASE VOLTAGE DROP
 CALCULATIONS.
 13-413.1ABC.1
  
 3) NOTE: PLEASE SUBMIT AND MEET PRESCRIPTIVE
 REQUIREMENTS FOR LIGHTING PER CURRENT CODE 13-415.2,
 13-415.2.ABC.1.3.
 THE LIGHTING BEING PROPOSED GOES BEYOND THE PARKING
 STRUCTURE PERMIT APPLIED FOR IN 2007.
  
 4) NOTE: LIGHTING CONTROLS NEED TO MEET
 13-415.1.ABC.1.4. NOT ALL SHOWN DETAILS PHOTO-SENSOR OR
 ASTRONOMICAL TIME CLOCK WITH PROGRAMMING BACK UP. SEE
 CONTACTOR RISER ON E0.1.
  
 5) NOTE: PLANS DO NOT INDICATE ANY LIGHT POLES AND
 FIXTURE DETAILS. PLEASE BE SURE TO SEE COMMENTS FROM
 OTHER TRADES SUCH AS BUILDING WITH RESPECT TO MINIMUM
 WIND LOADS MEETING 1609 OF THE FBC WITH EFFECTIVE
 PROJECTED AREAS ETC.
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-03-05 Cont ID  
Sent By mgonzale Date 2009-03-05 Time 13:24 Rev Time 1.00
Received By mgonzale Date 2009-03-05 Time 13:24 Sent To  
Notes
2009-03-05 13:25:56***** APPROVED ****
  
 ENGINEERING HAS REVIEWED THE PLANS AND HAVE APPROVED.
 SOME OF THE WORK HAS STARTED AND IS BEING INSPECTED
 THRU ENGINEERING.
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-03-06 Cont ID  
Sent By mawillia Date 2009-03-06 Time 19:08 Rev Time 0.00
Received By mawillia Date 2009-03-06 Time 18:46 Sent To  
Notes
2009-03-06 19:07:42*****PROVISO*****
  
 THE APPROPIATE PLAN SHEETS (C4 & C5) TO BE FIRE STAMPED
 WHEN THE FOLLOWING COMMENTS AS WELL AS THE OTHER PLAN
 EXAMINER'S COMMENTS HAVE BEEN ADDRESSED:
  
 1. ON SHEET G0.0, AMEND FIRE CODE TO THE 2007 EDITION
 OF FLORIDA FIRE PREVENTION CODE AND THE LIFE SAFETY
 CODE TO THE 2006 EDITION OF NFPA 101. PLEASE BE ADVISED
 THAT NFPA 70 AND NFPA 241 ARE NOT LIFE SAFETY CODES.
  
 2. ON SHEET C5 OF 5, ADD TO NOTES AND/OR DISPLAY IN THE
 PICTORIAL THAT THE BACKFLOW DEVICE SHALL BE EQUIPPED
 WITH A CHAIN AND LOCK.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-06 Cont ID  
Sent By mawillia Date 2009-03-06 Time 19:09 Rev Time 0.00
Received By mawillia Date 2009-02-06 Time 16:16 Sent To  
Notes
2009-02-06 16:20:48TO "COMM" BD#10

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-18 Cont ID  
Sent By eschneid Date 2009-02-18 Time 11:48 Rev Time 0.50
Received By eschneid Date 2009-02-18 Time 11:48 Sent To  
Notes
2009-02-18 11:51:50FAILED
  
 1) THE CIVIL AND BASE DRAWINGS DO NOT MATCH THE PLANS
 APPROVED BY THE ZONING DIVISION.
  
 2) THE CIVIL PLANS DO NOT MATCH THE "AS-BUILT"
 CONDITIONS IN A FEW LOCATIONS.
  
 NOTE: URBAN DESIGN KILDAY STUDIOS IS IN THE PROCESS OF
 AMENDING THE SITE AND LANDSCAPE PLANS. ALL PLANS SHALL
 SHOW SAME CONDITIONS AND THE FINAL INSTALLATION SHALL
 MATCH THE APPROVED PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.