Plan Review Details - Permit 09020012
Plan Review Stops For Permit 09020012
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-03-05 Cont ID  
Sent By shill Date 2009-03-05 Time 13:49 Rev Time 0.00
Received By shill Date 2009-03-05 Time 13:49 Sent To  
Notes
2009-03-05 13:50:37REVISE SHEET 1 OF 1, FBC3101. (DESIGN CRITERIA STATES
 FABRIC TO BE REMOVED WHEN WINDS EXCEED 90 AND THE FRAME
 IS DESIGNED TO 75 - DOES NOT COMPLY WITH MINIMUM CODE.
 CALCULATIONS ARE FOR DESIGN TO 90MPH)
  
 **AT CONTRACTOR'S RISK**

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-02-25 Cont ID  
Sent By shill Date 2009-02-25 Time 15:37 Rev Time 0.00
Received By shill Date 2009-02-25 Time 15:37 Sent To  
Notes
2009-02-25 15:42:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. FBC3105.4, DESIGN CRITERIA FOR FABRIC REMOVAL DOES
 NOT MEET THE MINIMUM CODE REQUIREMENT. PLEASE REVISE.
  
 2ND REVIEW, THE SAME ENGINEERING DATED 10/13/08 WAS
 SUBMITTED. SEE SHEET 1 OF 1, GENERAL NOTE 4. FRAMES
 WITH FABRIC ARE TO BE DESIGNED TO WITHSTAND 90MPH AND
 FABRIC REMOVED WHEN WINDS EXCEED 75MPH, ALSO "NOTE TO
 OWNER" INCORRECT. ALSO SEE CALCULATIONS, DESIGN
 CRITERIA (SHEET 3) STATE SHADE COVERING TO BE REMOVED
 WHEN WINDS EXCEED 90; THIS DOES NOT COMPLY WITH
 FBC3105.4. PLEASE CHECK ALL SHEETS AND REVISE ALL
 SHEETS TO MEET MINIMUM REQUIREMENTS OF FBC3105.4.
  
 NEW COMMENT:
  
 2. ALL INFORMATION REQUIRED BY FAC61G15-23.002 REQUIRED
 ON EACH SHEET, SEE PAGE 1 OF 1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-17 Cont ID  
Sent By shill Date 2009-02-17 Time 15:40 Rev Time 0.00
Received By shill Date 2009-02-17 Time 15:40 Sent To  
Notes
2009-02-17 15:45:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FBC3105.4, DESIGN CRITERIA FOR FABRIC REMOVAL DOES
 NOT MEET THE MINIMUM CODE REQUIREMENT. PLEASE REVISE.
  
 2. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 3. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 15:54 Rev Time 0.00
Received By adarroug Date 2009-02-24 Time 15:54 Sent To Z
Notes
2009-02-24 15:54:45TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-17 Cont ID  
Sent By shill Date 2009-02-17 Time 15:45 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2009-02-02 16:57:09TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2009-02-13 Cont ID  
Sent By mcruz Date 2009-02-13 Time 11:38 Rev Time 0.00
Received By mcruz Date 2009-02-13 Time 11:33 Sent To B
Notes
***NONE***