Plan Review Details - Permit 09010481
Plan Review Stops For Permit 09010481
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-10-19 Cont ID  
Sent By shill Date 2009-10-19 Time 09:36 Rev Time 0.00
Received By shill Date 2009-10-19 Time 09:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-09-09 Cont ID  
Sent By shill Date 2009-09-09 Time 11:44 Rev Time 0.00
Received By shill Date 2009-09-09 Time 11:44 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-24 Cont ID  
Sent By shill Date 2009-03-24 Time 10:36 Rev Time 0.00
Received By shill Date 2009-03-24 Time 10:36 Sent To P
Notes
2009-03-24 10:40:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENT FROM PREVIOUS LIST:
  
 1. FS471, THE ENGINEER'S SEAL IS TO BE LEGIBLE. PLEASE
 HAVE THE ENGINEER RE-SEAL THE SHEETS AS DISCUSSED.
  
 NEW COMMENTS:
  
 2. TWO COMPLETE SETS OF ORIGINAL DOCUMENTS REQUIRED FOR
 PERMIT ISSUANCE. NOTE THE FOLLOWING:
  
 A. ONLY ONE SET OF PLANS PREPARED BY DOUGLAS RUTH
 ASSOCIATES WAS SUBMITTED. THE ONE SET WAS NOT SIGNED
 AND SEALED. TWO ORIGINAL SIGNED, SEALED, DATED SETS
 REQUIRED.
  
 B. TWO ADDITIONAL SETS OF PLANS PREPARED BY JOHN HALEY,
 PE WERE SUBMITTED. PLEASE REMOVE FROM THE PACKAGE; KEEP
 THE TWO ORIGINALS IN THE PERMIT PACKAGE.
  
 3. INFORMATIONAL ONLY; THE DUMPSTER GATES CANNOT
 ENCROACH THE PROPERTY LINE FBC3202.2. THE PERMIT WILL
 BE ISSUED WITH PROVISO/REDLINE (NO CHANGE TO PLANS
 NECESSARY).
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-27 Cont ID  
Sent By shill Date 2009-02-27 Time 13:18 Rev Time 0.00
Received By shill Date 2009-02-27 Time 13:18 Sent To  
Notes
2009-02-27 13:20:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FS471, THE ENGINEER'S SEAL IS TO BE LEGIBLE. PLEASE
 HAVE THE ENGINEER RE-SEAL THE SHEETS AS DISCUSSED.
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2009-09-03 Cont ID  
Sent By mgonzale Date 2009-09-03 Time 08:26 Rev Time 6.00
Received By mgonzale Date 2009-09-03 Time 08:18 Sent To  
Notes
2009-09-03 08:25:5509/03/09 PASSED WITH PROVISOS
  
 REVIEW FOR STORMWATER ELEMENTS AT 233 WENNONAH PLACE
  
 #1 STORM CALCULATIONS DATED 09/02/09 HAVE BEEN RECEIVED
 AND APPROVED.
 CONTRACTOR SHALL BUILD THE PARKING AREA BASED ON THE
 CALCULATIONS SUPPLIED AND REVISE
 THE AS-BUILT PLAN ACCORDINGLY. (CALCS ARE ATTACHED TO
 THE PLAN)
  
 #2 SHEET ONE DOES NOT AGREE WITH THE PLAN SHOWN ON SHT
 2 A (NO HANDICAP PARKING SHOWN)
 ( CONTRACTOR NEEDS TO BUILD AS PER CITY APPROVED SITE
 PLAN.)
  
 CONTRACTOR SHALL BE RESPONSIBLE FOR THIS CORRECTION
 DURING CONSTRUCTION:
  
 #1 SHEET 2B PAVING AND DRAINAGE DETAILS:
 PRECAST INLET TYPE "C" (OPTION) DETAIL NEEDS TO SHOW OR
 STATE THAT ROCK UNDER STRUCTURE MUST BE WRAPPED IN
 FILTER FABRIC
 #2 SHEET 2B PAVING AND DRAINAGE DETAILS:
 EXFILTRATION TRENCH DETAIL (OPTION)
 REVISE NOTE #2 TO INCLUDE "BOTTOM" ALSO.
 #3 SHEET 2B PAVING AND DRAINAGE DETAILS:
 ADD TO 12"X12" SUMP A NOTE ADDING SS HARDWARE CLOTH
 (MESH) AT SUMP ENTRY POINT.
 #4 SHEET 2B PAVING AND DRAINAGE DETAILS:
 REVISE NOTE #2 TO INCLUDE "BOTTOM" ALSO.
  
 PLEASE FEEL FREE TO CONTACT ME IF ANY FURTHER QUESTIONS
 OR CONCERN.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2009-08-13 Cont ID  
Sent By mgonzale Date 2009-08-13 Time 09:14 Rev Time 4.00
Received By mgonzale Date 2009-08-13 Time 08:52 Sent To  
Notes
2009-08-13 09:14:15 
 ENGINEERING PREVIOUSLY LOOKED AT PLANS FOR RIGHT OF WAY
 ELEMENTS"
  
 08/12/09
 REVIEW FOR STORMWATER ELEMENTS AT 233 WENNONAH PLACE
 STORM WATER CALCULATION WHERE RECEIVED 08/06/09 VIA FAX
 FROM MR HALEY AS REQUESTED TO PROCEED WITH REVIEW.
 COMMENTS TO JOHN HALEY, ENGINEER OF RECORD
 #1 DISCHARGE FROM SITE BEGINS AT ELEV 9.50 (CALCS SHOW
 AT ELEV 10.61)
 #2 PROVIDE 100 YEAR STAGE VS BUILDING FINISH FLOOR
 ELEVATION.
 #3 PROVIDE PRE CONDITIONS VS POST CONDITION
 CALCULATIONS.
 #4 SHEET ONE DOES NOT AGREE WITH THE PLAN SHOWN ON SHT
 2 A (NO HANDICAP PARKING SHOWN)
 #5 SHEET 2B PAVING AND DRAINAGE DETAILS:
 PRECAST INLET TYPE "C" (OPTION) DETAIL NEEDS TO SHOW OR
 STATE THAT ROCK UNDER STRUCTURE MUST BE WRAPPED IN
 FILTER FABRIC
 #6 SHEET 2B PAVING AND DRAINAGE DETAILS:
 EXFILTRATION TRENCH DETAIL (OPTION)
 REVISE NOTE #2 TO INCLUDE "BOTTOM" ALSO.
 #7 SHEET 2B PAVING AND DRAINAGE DETAILS:
 ADD TO 12"X12" SUMP A NOTE ADDING SS HARDWARE CLOTH
 (MESH) AT SUMP ENTRY POINT.
 #8 SHEET 2B PAVING AND DRAINAGE DETAILS:
 REVISE NOTE #2 TO INCLUDE "BOTTOM" ALSO.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-02-27 Cont ID  
Sent By mgonzale Date 2009-02-27 Time   Rev Time 1.00
Received By mgonzale Date 2009-02-27 Time   Sent To  
Notes
2009-02-27 09:53:10**** PASSED ****
  
 ROW PERMIT IS REQUIRED.
 CONTACT CWPB ENGINEERING (561) 494-1040
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-10-13 Cont ID  
Sent By lmartine Date 2009-10-13 Time 14:21 Rev Time 0.00
Received By lmartine Date 2009-10-13 Time 14:21 Sent To  
Notes
2009-10-13 14:23:39LANDSCAPE RESUBMITTAL, PUT IN ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-07-24 Cont ID  
Sent By rregueir Date 2009-07-24 Time 16:34 Rev Time 0.00
Received By rregueir Date 2009-07-24 Time 16:34 Sent To  
Notes
2009-07-24 16:34:45TO Z INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-09 Cont ID  
Sent By adarroug Date 2009-03-09 Time 10:35 Rev Time 0.00
Received By adarroug Date 2009-03-09 Time 10:35 Sent To Z
Notes
2009-03-09 10:36:10TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-13 Cont ID  
Sent By adarroug Date 2009-02-13 Time 16:52 Rev Time 0.00
Received By adarroug Date 2009-02-13 Time 16:52 Sent To ENG
Notes
2009-02-13 16:52:39TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-02 Cont ID  
Sent By lmartine Date 2009-02-27 Time 16:19 Rev Time 0.00
Received By lmartine Date 2009-02-02 Time 10:42 Sent To  
Notes
2009-02-02 10:42:21TO "Z" BOX

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-10-15 Cont ID  
Sent By rkussner Date 2009-10-15 Time 09:54 Rev Time 0.00
Received By rkussner Date 2009-10-15 Time 09:54 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-08-03 Cont ID  
Sent By rkussner Date 2009-08-03 Time 12:03 Rev Time 0.00
Received By rkussner Date 2009-08-03 Time 12:03 Sent To  
Notes
2009-08-03 12:27:17***LANDSCAPE REVIEW FAILED***
  
 1. REPEAT COMMENT: PLEASE RESPOND TO ALL COMMENTS IN
 WRITTEN FORMAT.
  
 2. REPEAT COMMENT: THE SITE AND PAVING AND DRAINAGE
 PLAN ARE INCONSISTENT REGARDING THE NORTH END OF THE
 PARKING LOT, ADJACENT TO THE DUMPSTER ENCLOSURE. THE
 HANDICAP SPACE AND MANERUVERING ARE ARE DIFFERENT IN
 THIS SUBMITTAL, AS WELL. ALL PLANS MUST BE CONSISTENT.
  
 3. REPEAT COMMENT: THE PROPOSED DOUBLE SIDED CARSTOPS
 ARE NOT PERMITTED BY CITY CODE. THEY MUST BE ANGLED ON
 ONLY ONE SIDE.
  
 4. PLEASE PROVIDE STANDARD CITY APPROVED STRIPING
 DETAIL.
  
 5. ON THE LANDSCAPE PLAN, PLEASE SHOW ANY OVERHEAD
 LINES, UTIITIES, EASEMENTS OR ANYTHING ELSE THAT MAY
 INTERFERE WITH THE PROPOSED LANDSCAPING. THE APPLICANT
 SHALL ABIDE BY THE GUIDELINES SETFORTH BY FPL REGARDING
 TREE LOCATIONS IN CLOSE PROXIMITY TO OVERHEAD LINES.
 PLEASE REFER TO FPL'S 'PLANT THE RIGHT TREE IN THE
 RIGHT PLACE' FOR MORE INFORMATION.
  
 6. BASED UPON THE LANDSCAPE CALCULATIONS PROVIDED,
 THERE ARE LESS TREES PROVIDED AS COMPARED TO WHAT IS
 REQUIRED. PLEASE CLARFIY.
  
 7. IN KEEPING WITH XERISCAPE GUIDELINES, THE PROPOSED
 SABAL PALMS SHALL BE INCORPORATED INTO PLANT BEDS,
 INSTEAD OF SOD.
  
 8. THE SYMBOL 'PP' WAS USED ON THE PLAN, BUT THERE IS
 NO REFERENCE TO THAT SYMBOL ON THE PLANT LEGEND.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-03-19 Cont ID  
Sent By rkussner Date 2009-03-19 Time 10:22 Rev Time 0.00
Received By rkussner Date 2009-03-19 Time 09:48 Sent To  
Notes
2009-03-19 10:21:37***LANDSCAPE REVIEW FAILED***
  
 1. PLEASE RESPOND TO ALL COMMENTS IN WRITTEN FORMAT.
  
 2. THE SITE PLAN AND PAVING AND DRAINAGE PLAN ARE
 INCONSISTENT REGARDING THE NORTH END OF THE PARKING
 LOT, ADJACENT TO THE DUMPSTER ENCLOSURE. ALL PLANS MUST
 BE CONSISTENT.
  
 3. THE PROPOSED DOUBLE SIDED CARSTOPS ARE NOT PERMITTED
 BY CITY CODE. THEY MUST BE ANGLED ON ONLY ONE SIDE.
  
 4. PLEASE PROVIDE SOD AND IRRIGATION IN THE
 RIGHT-OF-WAY ADJACENT TO WENONA PLACE.
  
 5. IN ADDITION TO THE TREES, ALL SHRUBS SHALL BE
 PLANTED AT OR SLIGHTLY ABOVE GRADE. MULCH SHALL BE
 APPLIED TO A DEPTH OF (3) INCHES OUTSIDE OF THE ROOT
 BALL WITH LESS THAN (1) INCH OF MULCH SHALL BE APPLIES
 OVER THE ROOTBALL.
  
 6. SILT FENCING IS SHOWN ON THE SITE PLAN. A FENCE IS
 SHOWN ON THE LANDSCAPE PLAN. UNLESS THIS IS A PERMANENT
 FENCE, IT SHOULD NOT BE SHOWN ON THE LANDSCAPE PLAN. IF
 IT IS A PERMANENT FENCE, PLEASE PROVIDE A DETAIL. IN
 ADDIITION, IT MUST BE PLACED ALONG THE INTERIOR
 PERIMETER OF THE LANDSCAPE SETBACK ACJACENT TO WENONAH
 PLACE.
  
 7. PLEASE PROVIDE THE TABULATION NECESSARY TO
 DEMONSTRATE COMPLIENCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, IINCLUDING THE
 XERISCAPE POINTS.
  
 8. PLEASE SHOW THE PLANT BED LINES FOR ALL PLANTING
 AREAS.
  
 9. THE HEDGE BETWEEN THE PARKING LOT AND BUILDING IS
 NOT REQUIRED. INSTEAD, TIERED PLANTING SHALL BE
 INSTALLED ALONG THE SIDEWALK THE PERIMETER HEDGE ALONG
 THE NORTH AND EAST SIDES OF THE PARKING LOT CAN BE
 PLANTED ALONG THE PROPERTY LINE.
  
 10. THE PERIMETER TREES SHALL BE REORIENTED IN ORDER TO
 PROVIDE A TREE AT THE TERMINUS OF EACH PARKING ROW (ALL
 FOUR CORNERS). ONE PROPOSED TREE IS SHOWN INSIDE OF THE
 DUMPSTER ENCLOSURE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-09-09 Cont ID  
Sent By kstevens Date 2009-09-09 Time 17:05 Rev Time 0.00
Received By kstevens Date 2009-09-09 Time 17:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-01 Cont ID  
Sent By kstevens Date 2009-04-01 Time 11:18 Rev Time 0.00
Received By kstevens Date 2009-03-31 Time 11:18 Sent To  
Notes
2009-04-01 11:59:08DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT IR-1 MINIMUM TWO SETS OF SIGNED/SEALED PLANS
 REQUIRED PER SECTION 106.1. PLEASE SUBMIT REQUIRED SETS
 OF PLANS WITH APPLICATION.
  
 2. SHT IR-1 SHALL BE SIGNED, SEALED AND DATED. THE
 SHEET HAS NOT BEEN SEALED AND THE SIGNATURE IS A PHOTO
 COPY OF AN ORIGINAL SIGNATURE. ORIGINAL "WET
 SIGNATURES" ARE REQUIRED ON EACH SET OF PLANS. SECTION
 106.1, FAC 61G1-16.004(2) & FS 481.306.
  
 3. SHT IR-1 THE METER, PVB, RAIN SENSOR & THE
 CONTROLLER LOCATIONS ARE TO BE INDICATED ON THE PLANS.
 SECTION 106.1.1 & APPENDIX "F" (J) & FS 373.62.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-08-04 Cont ID  
Sent By mcruz Date 2009-08-04 Time 11:46 Rev Time 0.00
Received By mcruz Date 2009-08-02 Time 21:20 Sent To ENG
Notes
2009-08-04 11:46:05PASSED WITH PROVISO: COMMENTS FROM LANDSCAPE PLANNER
 AND ENGINEERING SHALL BE RESOLVED PRIOR TO FINAL
 APPROVAL.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2009-03-17 Cont ID  
Sent By mcruz Date 2009-03-17 Time 18:24 Rev Time 0.00
Received By mcruz Date 2009-03-17 Time 17:39 Sent To L
Notes
2009-03-17 17:40:09PLANNING AND ZONING DEPT: ***ZONING FAILED - 1ST
 RESUB***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 REPEAT COMMENT:
 2. PLEASE PROVIDE EXISTING NUMBER OF PARKING SPACES
 VERSES PROPOSED. FOR YOUR REFERENCE, PROVIDED ATTACHED
 IS A COPY OF THE GREEN CARD FOR THE SUBJECT PROPERTY.
 CROSS REFERENCE THE NUMBER OF REQUIRED PARKING SPACES
 FOR EACH TYPE OF UNIT LOCATED ONSITE. THE NUMBER OF
 REQUIRED PARKING SPACES CAN BE FOUND IN THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-486.
 SPECIFIC PARKING REQUIREMENTS; LOADING SPACE
 REQUIREMENTS FOR INDIVIDUAL USES. TABLE XV-6, CITYWIDE
 PARKING REQUIREMENTS, LINE ITEM 131.
  
 NEW COMMENTS:
 3. AS NOTED BY THE ENGINEERING PLAN REVIEWER, PLEASE
 PROVIDE A RIGHT-OF-WAY PERMIT FOR THE PROPOSED APPROACH
 EXTENSION FROM THE CITY'S ENGINEERING DEPARTMENT
 (561.494.1040).
  
 4. THE LOCATION OF THE PROPOSED DUMPSTER ENCLOSURE
 CONFLICTS WITH THE PROPOSED PARKING SPACE AND DOES NOT
 PROVIDE ENOUGH MANEUVERING FOR A VEHICLE TO SAFELY BACK
 OUT FROM THE ADJACENT PARKING SPACE. RECONFIGURE THE
 DESIGN IN ORDER TO ALLOW FOR ADEQUATE MANEUVERING
 CAPABILITY. NOTE: REFER TO THE ZLDR, SECTION 94-485,
 FIGURE XV-2, GENERAL PARKING DIMENSIONS, FOR MINIMUM
 WIDTH REQUIREMENTS.
  
 5. IN ACCORDANCE WITH THE ZLDR, SECTION 94-304, MINIMUM
 SETBACKS FOR ACCESSORY STRUCTURES: THE DUMPSTER
 ENCLOSURE SHALL BE SETBACK A MINIMUM OF FIVE (5) FEET
 FROM THE REAR PROPERTY LINE.
  
 6. THE PROPOSED LANDSCAPING DOES NOT MEET THE MINIMUM
 REQUIRED PER CODE. PURSUANT TO THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR),
 SECTION 94-443??(3): OFF-STREET PARKING LOTS.
 OFF-STREET PARKING LOTS CONTAINING AT LEAST 12 INTERIOR
 PARKING SPACES SHALL CONTAIN LANDSCAPE AREAS. THE TOTAL
 SIZE OF SUCH LANDSCAPED AREAS SHALL BE EQUAL TO TEN
 SQUARE FEET FOR EACH PARKING SPACE AND SHALL BE
 PROVIDED WITHIN THE INTERIOR OF AN OFF-STREET PARKING
 AREA. LANDSCAPED AREAS SHALL CONTAIN AT LEAST ONE SHADE
 OR FLOWERING TREE FOR EACH 100 SQUARE FEET OF REQUIRED
 LANDSCAPED AREA. A MINIMUM OF 75 PERCENT OF ALL TREES
 THAT ARE REQUIRED TO BE PLANTED WITHIN THE INTERIOR OF
 AN OFF-STREET PARKING AREA SHALL BE SHADE TREES. THE
 SHADE TREES SHALL BE LOCATED IN SUCH A MANNER TO
 PRODUCE MAXIMUM OVERHEAD CANOPY FOR THE VEHICLES. ALL
 PARKING LOT LANDSCAPED AREAS SHALL BE PLANTED WITH
 GRASS, GROUND COVER, SHRUBBERY, OR OTHER SUITABLE LIVE
 PLANT MATERIAL. PARKING LOT LANDSCAPED AREAS SHALL BE
 DESIGNED, PLANTED, AND MAINTAINED TO PERMIT CLEAR
 VISION BETWEEN THE HEIGHT OF TWO FEET AND EIGHT FEET
 ABOVE GRADE; HOWEVER, THIS REQUIREMENT SHALL NOT APPLY
 WHERE THE LACK OF CLEAR VISION IS NOT DEEMED TO BE A
 SAFETY HAZARD. TERMINAL ISLANDS, INTERIOR ISLANDS AND
 DIVIDER MEDIANS SHOULD BE DESIGNED TO RETAIN MAXIMUM
 WATER IN THE TURF AREAS AND ARE SUBJECT TO THE
 FOLLOWING REQUIREMENTS. FIGURE XIV-1 IS AN EXAMPLE OF
 THE LOCATION AND RELATIONSHIP BETWEEN THE PARKING LOT
 LANDSCAPE AREAS AND THE PROPERTY.
  
 7. ENSURE THE PARKING STALL DIMENSIONS MEET THE MINIMUM
 STANDARDS AS INDICATED IN THE ZLDR, SECTION 94-485 (SEE
 ATTACHED DETAIL).
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-12 Cont ID  
Sent By mcruz Date 2009-02-12 Time 13:43 Rev Time 0.00
Received By mcruz Date 2009-02-12 Time 13:21 Sent To I
Notes
2009-02-12 13:43:42PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. PURSUANT THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-444(B):
 OUTDOOR INCINERATORS, GARBAGE OR TRASH RECEPTACLES,
 FUEL OIL OR PROPANE TANKS, AND STORAGE RACKS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
  
 WALLS SHALL BE IRRIGATED AND LANDSCAPED WITH SHRUBS AND
 HEDGES PLANTED AT TWO (2) FEET INTERVALS. SHOW A DETAIL
 ON THE PLAN OF THE LANDSCAPING ALONG THE DUMPSTER
 ENCLOSURE.
  
 IS THERE EXISTING IRRIGATION ON SITE THAT WILL PROVIDE
 WATER TO PROPOSED LANDSCAPE SCREENING? IF SO, PLEASE
 INDICATE LOCATION OF EXISTING IRRIGATION ON PLANS AND
 DIRECTION OF WATER FLOW. IF NOT, IRRIGATION MUST BE
 INSTALLED AND SHOW LOCATION OF PROPOSED IRRIGATION ON
 PLANS.
  
 4. PLEASE PROVIDE EXISTING NUMBER OF PARKING SPACES
 VERSES PROPOSED.
  
 5. PURSUANT TO XIV-2 - DIMENSIONAL REQUIREMENTS AND
 SPECIFICATIONS FOR CURBS AND WHEEL STOPS, RODS FOR
 ANCORANGE SHALL BE #5 X 18". SEE ATTACHED DETAIL FOR
 SPECIFICATIONS.
  
 6. THE HANDICAP PARKING DETAIL ON SHEET 3 OF 3 IS
 MARKED OUT OF PLAN. PLEASE RESUBMIT A DETAIL OF THE
 HANDICAP PARKING SPACE IN ACCORDANCE WITH THE ATTACHED
 SPECIFICATIONS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  