Plan Review Details - Permit 09010414
Plan Review Stops For Permit 09010414
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-02-11 Cont ID  
Sent By shill Date 2009-02-11 Time 16:08 Rev Time 0.00
Received By shill Date 2009-02-11 Time 16:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-30 Cont ID  
Sent By shill Date 2009-01-30 Time 11:26 Rev Time 0.00
Received By shill Date 2009-01-30 Time 11:26 Sent To  
Notes
2009-01-30 11:30:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE INSTALLATION SCHEDULE STATES THAT THE BUILDING
 IS 62' HIGH, BUT THE WIND LOAD CHART SUBMITTED STATES
 THIS BUILDING IS 25'. PLEASE REVISE. THIS APPEARS TO BE
 A TYPO.
  
 2. THE INSTALLATION SCHEDULE STATES THAT THE SUBSTRATE
 IS CONCRETE. 3320PSI CONCRETE REQUIRED, SEE SHEET 8 OF
 THE PRODUCT APPROVAL. THIS HOUSE WAS BUILT WITH A
 SPECIFICATION OF 3000PSI CONCRETE FOR FLOOR AND
 COLUMNS. PLEASE PROVIDE EVIDENCE THAT THE CONCRETE
 SUBSTRATE MEETS THE MINIMUM STRENGTH REQUIREMENT, OR
 USE THE HOLLOW BLOCK SPECIFICATION, OR A DIFFERENT
 ANCHOR.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-10 Cont ID  
Sent By adarroug Date 2009-02-10 Time 09:40 Rev Time 0.00
Received By adarroug Date 2009-02-10 Time 09:40 Sent To B
Notes
2009-02-10 09:41:12TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-30 Cont ID  
Sent By shill Date 2009-01-30 Time 11:30 Rev Time 0.00
Received By shill Date 2009-01-28 Time 10:48 Sent To  
Notes
2009-01-28 10:49:07TO "MISC"BOX#1