Plan Review Details - Permit 09010345
Plan Review Stops For Permit 09010345
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2010-04-28 Cont ID  
Sent By lmartine Date 2010-04-28 Time 16:06 Rev Time 0.00
Received By lmartine Date 2010-04-28 Time 16:06 Sent To  
Notes
2010-04-28 16:08:10REVIEW NOT REQUIRED UNDER THIS PLUMBING PERMIT. SEE
 #09090315 FOR BUILDING REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-10-31 Cont ID  
Sent By lmartine Date 2009-10-31 Time 12:36 Rev Time 0.00
Received By lmartine Date 2009-10-31 Time 12:36 Sent To  
Notes
2009-10-31 12:52:07BUILDING REVIEW COMMENTS
  
  
  
  
 THIS PERMIT APPLICATION IS FOR PLUMBING WORK ONLY. THE
 DRAWINGS SUBMITTED INCLUDE A CHANGE OF OCCUPANCY AS
 WELL AS ADDITIONAL CONSTUCTION NOT PERMITTED UNDER A
 PLUMBERS LICENSE SCOPE OF WORK.
  
 SEE PERMIT #09090315 FOR POSSIBLE RESOLVE OF CONFLICT.
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-03-03 Cont ID  
Sent By mjacobs Date 2009-03-03 Time 16:33 Rev Time 0.00
Received By mjacobs Date 2009-03-03 Time 16:33 Sent To  
Notes
2009-03-03 16:33:35 
 BUILDING PLAN REVIEW
 PERMIT: 090100345
 ADD: 724 BUNKER RD
 CONT: TROPICAL PLUMBING
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3) SUBMIT A PROPOSED AND AN EXISTING FLOOR PLAN OF THE
 SPACE. THESE DRAWING SHALL SHOW ALL AREAS WHERE WORK
 SHALL BE PERFORMED. PROVIDE A WALL LEGEND INDICATING
 THE TYPE OF WALL TO BE CONSTRUCTED AND WHICH ONES WILL
 BE DEMOED. 2004 FBC 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 4) NOTE: THE FLOOR PLANS SUBMITTED DO NOT MATCH WHAT WE
 HAVE ON RECORD. THEREFORE, IF WORK WAS CARRIED OUT AT
 THIS LOCATION WITHOUT PERMITS A FEE MAY BE APPLIED TO
 THIS PERMIT APPLICATION. IF THE OWNER CAN PROVIDE
 INFORMATION FROM THIS BUILDING DEPARTMENT REGARDING THE
 INTERIOR REMODEL OF THE STRUCTURE, THERE WILL BE NO
 FEE.
  
 5) FBC 106: THE PLANS SUBMITTED SHALL BE OF DRAFTSMAN
 QUALITY AND SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE.
 SUBMIT TWO COMPLETE SETS OF PLANS PREPARED BY A DESIGN
 PROFESSIONAL THAT IS REGISTERED WITH THE STATE OF
 FLORIDA. PLANS PREPARED BY A DESIGN PROFESSIONAL SHALL
 BEAR THE DESIGNER OFFICIAL SEAL, SIGNATURE AND DATE ON
 EACH SHEET. FLORIDA STATUTES 471 AND 481.
  
 6) FBC 108.4 ANY PERSON WHO COMMENCES ANY WORK ON A
 BUILDING, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEM BEFORE OBTAINING THE BUILDING
 OFFICIAL???S APPROVAL OR THE NECESSARY PERMITS SHALL BE
 SUBJECT TO A PENALTY OF 300 PERCENT OF THE USUAL PERMIT
 FEE IN ADDITION TO THE REQUIRED PERMIT FEES.
  
 7) FBC 313: MORE INFORMATION IS REQUIRED TO SHOW THE
 TYPE OF DAY-CARE FACILITY AT THIS LOCATION. INDICATE
 THE NUMBER OF OCCUPANTS / CLIENTS WHO WILL RECEIVE
 CARE, MAINTENANCE AND SUPERVISION BY SOMEONE OTHER THAN
 THEIR RELATIVE OR LEGAL GUARDIAN. INDICATE THE OCCUPANT
 LOAD PER TABLE 1004, THE PROPOSE USE AND OCCUPANCY PER
 CHAPTER 3 AND THE TYPE OF CONSTRUCTION PER TABLE 601
 AND TABLE 503
  
 8) 2004 FBC (EXISTING) 301.5 A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. THIS INFORMATION SHALL BE SHOWN ON THE
 PLANS.
  
 9) FBC 11-4.3. INDICATE THE ACCESSIBLE ROUTE TO THE
 BUILDING, THE ACCESSIBLE ROUTE SHALL. TO THE MAXIMUM
 EXTENT FEASIBLE, COINCIDE WITH THE ROUTE FOR THE
 GENERAL PUBLIC. THE MAIN ENTRANCE TO THE BUILDING SHOWS
 AT LEAST TWO STEPS, WHICH WILL NOT MEET THE ACCESSIBLE
 REQUIREMENT; SEE SECTION 11-4.8 FOR RAMP REQUIREMENTS.
 IF PARKING SPACES ARE PROVIDED; THE ACCESSIBLE SPACE
 SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE
 ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE11-406.2.
  
 10) FBC (EXISTING) 812.4.1.1 WHEN A CHANGE OF OCCUPANCY
 GROUP IS MADE TO A HIGHER HAZARD CATEGORY (LOWER
 NUMBER) AS SHOWN IN TABLE 812.4.1, THE MEANS OF EGRESS
 SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 OF THE
 FBC. PROVIDE A LIFE SAFETY PLAN SHOWING THE MEANS OF
 EGRESS, EXIT ACCESS, EXIT, EXIT DISCHARGE AND THE DOORS
 WITH THE DIMENSIONS.
  
 NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW. FOR MORE INFORMATION SEE FBC (EXISTING)
 CHAPTER 8. A PLUMBING CONTRACTOR CANNOT DO THE INTERIOR
 REMODEL OF THE STRUCTURE. A BUILDING, RESIDENTIAL OR
 GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMODEL
 OF THE STRUCTURE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2010-04-29 Cont ID  
Sent By btrobaug Date 2010-04-12 Time 10:11 Rev Time 0.00
Received By btrobaug Date 2010-04-12 Time 10:01 Sent To  
Notes
2010-04-29 16:17:00SEE PERMIT #09090315
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-10-10 Cont ID  
Sent By dpalmer Date 2009-10-10 Time 08:38 Rev Time 0.00
Received By dpalmer Date 2009-10-10 Time 08:38 Sent To  
Notes
2009-10-10 08:38:40** DENIED**
  
 1) NOTE: PERMIT APPLICATION FOR CHANGE IN OCCUPANCY HAS
 STILL NOT BEEN APPLIED FOR AS REQUIRED PER CHAPTER 3 OF
 THE FBC. PLEASE ALSO SEE EXISTING BUILDING CODE CHAPTER
 9 FOR CHANGES IN OCCUPANCY.
  
 2) NOTE: PLEASE SEE FBC 108.3 AS THE APPLIED VALUE FOR
 THE COMPLETE SCOPE OF WORK SHALL INCLUDE ALL LABOR,
 EQUIPMENT, MATERIALS, DESIGN COST EVEN IF ANY OF THESE
 ARE OWNER SUPPLIED.
  
 3) NOTE: A MINIMUM OF TWO ORIGINAL SIGNED, DATED AND
 SEALED SETS OF PLANS ARE REQUIRED. BOTH SETS OF PLANS
 SUBMITTED ARE PHOTO-COPIES OF SIGNED AND SEALED PLANS
 WHICH ARE NOT PERMITTED. SEE FLORIDA STATUTES 471.025
 AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002.
 FBC 106.1,106.1.1,106.1.2, ETC
  
 4) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR
 MINIMUM CODE COMPLIANCE PER EXISTING BUILDING CODE AND
 CHANGES IN OCCUPANCY PER 2007 EXISTING BUILDING CODE
 CHAPTER 9.
 PLEASE BE SURE TO SEE 2005 NEC AS ELECTRICAL IS ALL
 REQUIRED TO MEET CURRENT CODES.
 PLEASE INCLUDE ALL ELECTRICAL RECEPTACLES, CIRCUITING,
 LIGHTING, LIGHTING CONTROLS, SERVICE, DISCONNECTS,
 CONDUCTORS, OVER CURRENT PROTECTION, PANEL SCHEDULE(S)
 ETC
 230.2,230.70,230.71,230.72,240.4,310.16,408.4, 230.76,2
 30.79,215.5,250.50,250.122,250.66,220.14,220.12,220.42,
 220.44,220.60 ETC
 THERE ARE TOO MANY CODE SECTIONS TO LIST EVERYONE THAT
 APPLY TO THIS SCOPE OF WORK AND THE CHANGE IN
 OCCUPANCY.
 PLEASE BE SURE TO SEE NFPA-101 FOR MINIMUM LIFE SAFETY
 CODE REQUIREMENTS. THE CURRENT EDITION IS THE 2006
 NFPA-101 PER FAC 69A-60.004, 69A-3.012
 PLEASE BE SURE TO SEE FBC CHAPTER 13 FOR ENERGY CODE
 COMPLIANCE FOR PRESCRIPTIVE REQUIREMENTS. SEE
 13-415.AB.1.1,.1.2, .1.3 AND .1.4.
  
 ** AS NO ELECTRICAL PLANS WERE SUBMITTED FOR MINIMUM
 CODE COMPLIANCE REVIEW THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 **IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-03-06 Cont ID  
Sent By btrobaug Date 2009-03-06 Time 14:23 Rev Time 0.00
Received By btrobaug Date 2009-03-06 Time 13:57 Sent To  
Notes
2009-03-06 14:23:23 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} NO ELECTRICAL PLANS WHERE SUBMITTED FOR REVIEW.
 SUBMIT PLANS INDICATING THE SCOPE OF WORK INTENDED.
 106.1 FBC
  
 2} INDICATE WHAT THE USE AND OCCUPANCY OF THE BUILDING
 IS INTENDED TO BE PER CHAPTER 3 FBC.
  
 3} 301.5 EXISTING BUILDING CODE
 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. INDICATE SAME
 ON THE PLANS.
  
 4} 106.1.3 RESERVED. QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2009-10-14 Cont ID  
Sent By mawillia Date 2009-10-14 Time 14:36 Rev Time 0.00
Received By mawillia Date 2009-10-14 Time 14:26 Sent To  
Notes
2009-10-14 14:36:24*****NOT REQUIRED*****
  
 SINCE A CHANGE OF OCCUPANCY FOR THIS STRUCTURE HAS BEEN
 CONDUCTED UNDER PERMIT 09090315, NO FIRE REVIEW IS
 REQUIRED FOR THIS PLUMBING PERMIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-03-16 Cont ID  
Sent By mawillia Date 2009-03-16 Time 11:01 Rev Time 0.00
Received By mawillia Date 2009-03-16 Time 10:40 Sent To  
Notes
2009-03-16 11:00:42*****DENIED*****
  
  
 1. THE 2007 EDITION OF FLORIDA FIRE PREVENTION CODE
 WHICH IS BASED ON NFPA 101, LIFE SAFETY CODE, 2006
 EDITION AND NFPA 1, UNIFORM FIRE CODE, EDITION SHALL BE
 REFERENCED.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. IT APPEARS THAT THIS FORMERLY BUSINESS OCCUPANCY IS
 BEING CONVERTED TO ANOTHER OCCUPANCY TYPE. PLEASE
 SPECIFY THE NEW OCCUPANCY TYPE AND PERTINENT
 INFORMATION NEEDED TO CONDUCT A THOROUGH PLAN REVIEW
 BASED ON THE NEW OCCUPANCY TYPE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-04-09 Cont ID  
Sent By lmartine Date 2010-03-29 Time 15:45 Rev Time 0.00
Received By lmartine Date 2010-03-29 Time 15:45 Sent To  
Notes
2010-04-09 15:45:49B--7

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-17 Time 11:47 Rev Time 0.00
Received By lmartine Date 2009-09-17 Time 11:47 Sent To  
Notes
2009-09-22 11:50:02B-6, ROUTED ON 9/22, LM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 08:31 Rev Time 0.00
Received By adarroug Date 2009-02-24 Time 08:30 Sent To  
Notes
2009-02-24 08:31:47TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-20 Cont ID  
Sent By adarroug Date 2009-02-20 Time 11:19 Rev Time 0.00
Received By adarroug Date 2009-02-20 Time 11:19 Sent To P
Notes
2009-02-20 11:19:18TO "KSTEVENS" DESK/RESUB

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2009-10-20 Cont ID  
Sent By rkussner Date 2009-10-20 Time 13:00 Rev Time 0.00
Received By rkussner Date 2009-10-20 Time 13:00 Sent To  
Notes
2009-10-20 13:02:16***LANDSCAPE REVIEW NOT REQUIRED***
  
 THIS IS A PLUMBING PERMIT. LANDSCAPING WAS REVIEWED
 UNDER PERMIT # 09-090315.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2010-05-17 Cont ID  
Sent By hmoser Date 2010-05-17 Time 14:55 Rev Time 0.00
Received By hmoser Date 2010-05-17 Time 14:55 Sent To  
Notes
2010-05-17 14:57:26REFER TO PERMOT # 09090315 FOR MECHANICAL REVIEW
 5/17/10 HM.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2010-04-14 Cont ID  
Sent By hmoser Date 2010-04-14 Time 13:49 Rev Time 0.00
Received By hmoser Date 2010-04-14 Time 13:49 Sent To  
Notes
2010-04-14 13:53:46PLAN DENIED
 FRESH AIR CALCULATIONS ON THE PLANS DO NOT MATCH ASHRAE
 62. 1-04 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-10-17 Cont ID  
Sent By rregueir Date 2009-10-17 Time 09:58 Rev Time 0.00
Received By rregueir Date 2009-10-17 Time 09:57 Sent To  
Notes
2009-10-17 10:05:16REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 **PREVIOUS REVIEW COMMENTS NOT ADDRESSED**
  
 BASED ON THE SCOPE OF WORK AND THE FLOOR PLAN SHOWN,
 THE USE OF THIS SPACE FOR CHILD CARE WOULD CONSTITUTE A
 CHANGE OF OCCUPANCY. A CHANGE OF OCCUPANCY IS DEFINED
 AS A CHANGE IN THE PURPOSE OR LEVEL OF ACTIVITY WITHIN
 A BUILDING THAT INVOLVES A CHANGE IN APPLICATION OF THE
 REQUIREMENTS OF THIS CODE IN ACCORDANCE WITH FBC-EB
 SECTION 202. THE PROPOSED USE WOULD BE A DAY-CARE
 OCCUPANCY IN ACCORDANCE WITH FBC-B SECTION 313.
  
 WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF
 AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED MECHANICAL
 VENTILATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL, THE INTENT OF THE RESPECTIVE
 FLORIDA BUILDING CODE, MECHANICAL PROVISIONS SHALL BE
 COMPLIED WITH FOR THE NEW OCCUPANCY IN ACCORDANCE WITH
 FBC-EB 809.1. PLEASE SHOW HOW THE VENTILATION
 REQUIREMENTS FOR THE PROPOSED NEW OCCUPANCY ARE TO BE
 MET IN ACCORDANCE WITH FBC-M 403.3.
  
 AS THIS BUILDING WAS PERMITTED PRIOR TO MARCH 15, 1979,
 IT SHALL MEET THE REQUIREMENTS FOR RENOVATIONS IN
 SECTION 101.1.3 FOR THOSE COMPONENTS WHICH ARE BEING
 RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B
 13-101.3.1. PLEASE DEMONSTRATE COMPLIANCE WITH THESE
 REQUIREMENTS AS APPROPRIATE.
  
 NOTE: THE SCOPE OF WORK AS STATED ON ORIGINAL PERMIT
 APPLICATION HAS EXPANDED TO INCLUDE ARCHITECTURAL AND
 EXTERIOR WORK. PERMIT APPLICATION SHALL BE UPDATED TO
 REFLECT THE ENTIRE PROPOSED SCOPE OF WORK. THE STATED
 VALUE ON PERMIT APPLICATION SHALL ALSO BE UPDATED TO
 REFLECT THE ACTUAL VALUE OF THE PROPOSED WORK.
  
 NOTE: PLANS WHICH ARE PREPARED BY A DESIGN PROFESSIONAL
 SHALL BEAR THE ORIGINAL SIGNATRE AND SEAL OF THE DESIGN
 PROFESSIONAL IN ACCORDANCE WITH FBC-B 106.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-03-13 Cont ID  
Sent By rregueir Date 2009-03-13 Time 16:15 Rev Time 0.00
Received By rregueir Date 2009-03-13 Time 15:46 Sent To FIRE
Notes
2009-03-13 16:15:15REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 BASED ON THE SCOPE OF WORK AND THE FLOOR PLAN SHOWN,
 THE USE OF THIS SPACE FOR CHILD CARE WOULD CONSTITUTE A
 CHANGE OF OCCUPANCY. A CHANGE OF OCCUPANCY IS DEFINED
 AS A CHANGE IN THE PURPOSE OR LEVEL OF ACTIVITY WITHIN
 A BUILDING THAT INVOLVES A CHANGE IN APPLICATION OF THE
 REQUIREMENTS OF THIS CODE IN ACCORDANCE WITH FBC-EB
 SECTION 202. THE PROPOSED USE WOULD BE A DAY-CARE
 OCCUPANCY IN ACCORDANCE WITH FBC-B SECTION 313.
  
 WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF
 AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED MECHANICAL
 VENTILATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL, THE INTENT OF THE RESPECTIVE
 FLORIDA BUILDING CODE, MECHANICAL PROVISIONS SHALL BE
 COMPLIED WITH FOR THE NEW OCCUPANCY IN ACCORDANCE WITH
 FBC-EB 809.1. PLEASE SHOW HOW THE VENTILATION
 REQUIREMENTS FOR THE PROPOSED NEW OCCUPANCY ARE TO BE
 MET IN ACCORDANCE WITH FBC-M 403.3.
  
 AS THIS BUILDING WAS PERMITTED PRIOR TO MARCH 15, 1979,
 IT SHALL MEET THE REQUIREMENTS FOR RENOVATIONS IN
 SECTION 101.1.3 FOR THOSE COMPONENTS WHICH ARE BEING
 RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B
 13-101.3.1. PLEASE DEMONSTRATE COMPLIANCE WITH THESE
 REQUIREMENTS AS APPROPRIATE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2010-06-02 Cont ID  
Sent By lwagner Date 2010-06-02 Time 10:08 Rev Time 0.00
Received By lwagner Date 2010-06-02 Time 10:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2010-04-13 Cont ID  
Sent By lwagner Date 2010-04-13 Time 11:00 Rev Time 0.00
Received By lwagner Date 2010-04-12 Time 14:01 Sent To M
Notes
2010-04-12 14:08:20DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
  
 ****UPDATE*****
 PLUMBING ISOMETRIC REQUIRED FOR ISSUANCE OF PERMIT
  
  
  
 1. THERE APPEAR TO BE 6 SINKS ON A 2" COMBINATION DRAIN
 AND VENT ON THE EAST SIDE OF THE HOUSE. P3111.3 SIZE -
 12 FIXTURE UNITS REQUIRE 3" PIPE. IF NOT A COMBINATION
 WASTE AND VENT, 4 OF THE SINKS ARE MISSING VENTS.
  
 2. A MINIMUM OF ONE VENT STACK THROUGH THE ROOF IS
 REQUIRED.
 P3102.1 STACK REQUIRED.
 EVERY BUILDING SHALL HAVE A VENT STACK OR A STACK VENT.
 SUCH VENT SHALL RUN UNDIMINISHED IN SIZE AND AS
 DIRECTLY AS POSSIBLE FROM THE BUILDING DRAIN THROUGH TO
 THE OPEN AIR ABOVE THE ROOF.
  
 3. THE 2 SINKS CONNECTED TO THE WATER CLOSET ARE NOT
 PERMITTED TO BE CONNECTED WITH A HEEL OR SIDE INLET 1/4
 BEND. ALSO, SINKS ARE NOT PERMITTED TO BE PART OF A WET
 VENT. IF THE THREE WC;S ARE IN A CIRCUIT VENT, THEN A
 VERTICAL DRY VENT IS REQUIRED BETWEEN THE TWO WC'S.
 P3110.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS.
  
 4.THE 2 LAVS SHOWN WITH THE SINGLE WC ARE DRAWN AS AN
 S-TRAP
  
 5. THE TWO DF STACKS REQUIRE VENTING.
  
 6. 3/4" WATER PIPE IS REQUIRED FOR 3 OR MORE FIXTURES.
 3/4" HOT WATER PIPE IS REQUIRED FOR 5 OR MORE FIXTURES.
 OR CALCULATIONS
 SHOWING THAT 1/2" WOULD BE ADEQUATE
 P2903.1 WATER SUPPLY SYSTEM DESIGN CRITERIA.
 THE WATER SERVICE AND WATER DISTRIBUTION SYSTEMS SHALL
 BE DESIGNED AND PIPE SIZES SHALL BE SELECTED SUCH THAT
 UNDER CONDITIONS OF PEAK DEMAND, THE CAPACITIES AT THE
 POINT OF OUTLET DISCHARGE SHALL NOT BE LESS THAN SHOWN
 IN TABLE P2903.1. TABLE P2903.2B SHALL BE PERMITTED TO
 BE USED TO SIZE THE WATER SERVICE OR WATER DISTRIBUTION
 SYSTEM.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-09-23 Cont ID  
Sent By kstevens Date 2009-09-23 Time 08:34 Rev Time 0.00
Received By kstevens Date 2009-09-22 Time 16:56 Sent To  
Notes
2009-09-23 09:31:03DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES.
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. SUBMIT A SANITARY RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, VENTS ETC. SECTION 106.3.5.1.3(4)(6)(13).
 SHOW THE POINT OF CONNECTION TO EXISTING BUILDING DRAIN
 OR STACK. TABLES 710.1(1) & 710.1(2).
 ****NO WRITTEN RESPONSE SUBMITTED. COMMENT NOT
 ADDRESSED. RISER DIAGRAM SHALL BE SUBMITTED IN
 ISOMETRIC FORM.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES,
 VALVES ETC. SHOW THE POINT OF CONNECTION. SECTIONS
 106.3.5.1.3(3)(10)(13) & 601.1.
 ****NO WRITTEN RESPONSE SUBMITTED. COMMENT NOT
 ADDRESSED. RISER DIAGRAM SHALL BE SUBMITTED IN
 ISOMETRIC FORM.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. OK
  
 4. ALL PLANS AND RISER DIAGRAMS IF NOT SIGNED AND
 SEALED BY A DESIGN PROFESSIONAL SHALL HAVE THE PRINTED
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DRAWING ON EACH SHEET. SECTION 104.2.1.
 ****NO WRITTEN RESPONSE SUBMITTED. COMMENT NOT
 ADDRESSED.
 ******PLANS NOW SUBMITTED ARE NOT SIGNED AND SEALED
 WITH AN IMPRESSION TYPE SEAL. SOME SHEETS WITH THE
 TITLE BLOCK FROM S.W. ENGINEERING ARE NOT SIGNED AND
 SEALED AT ALL. IF THE DESIGN PROFESSIONAL IS AN
 ENGINEER LEGALLY REGISTERED UNDE THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, THEN HEOR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS.
  
 *****************SINCE THIS IS A CHANGE OF OCCUPANCY
 ALL TRADES SHALL REVIEW********************
  
 ********NEW COMMENTS - NEW SHEETS********
  
 1B. THE APPLICATION PROJECT DESCRIPTION STATES "ADD 3
 SMALL CHILDRES'S TOILETS AND 3 LAV FOR CHILDREN". BUT
 THE PLANS SHOW 2 TOILETS AND 2 LAVS FOR THE CHILDREN.
 ALSO ON THE PLANS IS A NEW ADA TOILET ROOM, A NEW STAFF
 TOILET ROOM, A NEW 3 COMPARTMENT SINK & 2 NEW OTHER
 SINKS IN THE NEW DISPENSING AREA, A NEW MOP SINK, A
 RELOCATED WATER HEATER AND 2 NEW SINKS AT THE CHANGING
 TABLE. THE TOTAL VALUE OF ALL WORK SHALL BE INDICATED.
 SECTION 108.3.
  
 2B. SHTS 5.0 & 5.1. THE NEW STAFF TOILET ROOM, (107),
 SHALL BE ACCESSIBLE PER SECTION 11-4.1.3(11). TOILET
 ROOM SHALL COMPLY WITH SECTIONS 11-4.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 3B. SHTS 5.0 & 5.1. NEW ADA TOILET ROOM, (108). SHOW
 THE TURNING AREA REQUIRED BY SECTION 11-4.22.3. -- ALSO
 INDICATE THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE AS REQUIRED IN FIGURE 28.
  
 4B. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE SHOW THE LOCATION OF THE REQUIRED DRINKING
 FOUNTAIN AND SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.1.5 WITH ALL SUBSECTIONS AS WELL AS
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 5B. SHT 5.1 DETAIL 2/5.1 SHOW COMPLIANCE FOR THE
 FOLLOWING:
 ___FOR W/C:
 A. 11-4.16.3 HEIGHT (17" TO 19" REQUIRED, 19" TO 20"
 SHOWN)
 B. 11-4.16.6 DISPENSERS
 ___FOR LAV:
 A. 11-4.19.2 CLEARANCE SHALL BE 29" (28" SHOWN)
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 6B. THE NEW CHILDRENS TOILET ROOM SHALL BE ACCESSIBLE
 PER SECTIONS 11-4.16, 11-4.19 & 11-4.22. PLEASE SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH ALL SECTIONS AS WELL
 AS THE SUBSECTIONS. THERE ARE GUIDLINES FOR BUILDING
 ELEMENTS FOR CHILDREN: ADAAG AMENDMENTS AVAILABLE ON
 "THE ACCESS BOARD" THAT CAN BE REVIEWED. AS THESE ARE
 ONLY GUIDLINES AND CAN NOT BE ENFORCED AS CODE, THEY
 ARE RECOMMENDED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-02-23 Cont ID  
Sent By kstevens Date 2009-02-23 Time 14:18 Rev Time 0.00
Received By kstevens Date 2009-02-23 Time 14:18 Sent To  
Notes
2009-02-23 14:18:02DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. SUBMIT A SANITARY RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, VENTS ETC. SECTION 106.3.5.1.3(4)(6)(13).
 SHOW THE POINT OF CONNECTION TO EXISTING BUILDING DRAIN
 OR STACK. TABLES 710.1(1) & 710.1(2).
 ****NO WRITTEN RESPONSE SUBMITTED. COMMENT NOT
 ADDRESSED. RISER DIAGRAM SHALL BE SUBMITTED IN
 ISOMETRIC FORM.
  
 2. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES,
 VALVES ETC. SHOW THE POINT OF CONNECTION. SECTIONS
 106.3.5.1.3(3)(10)(13) & 601.1.
 ****NO WRITTEN RESPONSE SUBMITTED. COMMENT NOT
 ADDRESSED. RISER DIAGRAM SHALL BE SUBMITTED IN
 ISOMETRIC FORM.
  
 3. SUBMIT A DETAIL OF THE TOILET ROOM SHOWING THE
 SPACING OF THE FIXTURES AS REQUIRED IN SECTION 405.3.1
 AND FIGURE 405.3.1. A WATER CLOSET OR LAV SHALL NOT BE
 SET CLOSER THAN 15 INCHES FROM ITS CENTER TO ANY SIDE
 WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, OR CLOSER
 THAT 30 INCHES CENTER TO CENTER BETWEEN WATER CLOSETS
 OR ADJACENT FIXTURES. THERE SHALL BE AT LEAST A 21 INCH
 CLEARANCE IN FRONT OF THE W/C'S AND LAVS.
 ****NO WRITTEN RESPONSE SUBMITTED. COMMENT NOT
 ADDRESSED.
  
 4. ALL PLANS AND RISER DIAGRAMS IF NOT SIGNED AND
 SEALED BY A DESIGN PROFESSIONAL SHALL HAVE THE PRINTED
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DRAWING ON EACH SHEET. SECTION 104.2.1.
 ****NO WRITTEN RESPONSE SUBMITTED. COMMENT NOT
 ADDRESSED.
  
 *****************SINCE THIS IS A CHANGE OF OCCUPANCY
 ALL TRADES SHALL REVIEW********************
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 17:20 Rev Time 0.00
Received By kstevens Date 2009-01-27 Time 17:20 Sent To  
Notes
2009-01-27 17:39:50DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SUBMIT A SANITARY RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, VENTS ETC. SECTION 106.3.5.1.3(4)(6)(13).
 SHOW THE POINT OF CONNECTION TO EXISTING BUILDING DRAIN
 OR STACK. TABLES 710.1(1) & 710.1(2).
  
 2. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES,
 VALVES ETC. SHOW THE POINT OF CONNECTION. SECTIONS
 106.3.5.1.3(3)(10)(13) & 601.1.
  
 3. SUBMIT A DETAIL OF THE TOILET ROOM SHOWING THE
 SPACING OF THE FIXTURES AS REQUIRED IN SECTION 405.3.1
 AND FIGURE 405.3.1. A WATER CLOSET OR LAV SHALL NOT BE
 SET CLOSER THATN 15 INCHES FROM ITS CENTER TO ANY SIDE
 WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, OR CLOSER
 THAT 30 INCHES CENTER TO CENTER BETWEEN WATER CLOSETS
 OR ADJACENT FIXTURES. THERE SHALL BE AT LEAST A 21 INCH
 CLEARANCE IN FRONT OF THE W/C'S AND LAVS.
  
 4. ALL PLANS AND RISER DIAGRAMS IF NOT SIGNED AND
 SEALED BY A DESIGN PROFESSIONAL SHALL HAVE THE PRINTED
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DRAWING ON EACH SHEET. SECTION 104.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-10-05 Cont ID  
Sent By astelly Date 2009-10-05 Time 15:55 Rev Time 0.00
Received By astelly Date 2009-10-05 Time 15:55 Sent To  
Notes
2009-10-05 16:27:07AMY STELLY
 PLANNING & ZONING
 561.822.1442
  
  
 PROVISO
 SHARED PARKING AGREEMENT MUST BE EXECUTED PRIOR TO THE
 ISSUANCE OF THE FULL CO.
 THE AGREEMENT IS SLATED FOR CITY COMMISSION APPROVAL ON
 NOV. 16, 2009.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-03-18 Cont ID  
Sent By lfranco Date 2009-03-18 Time 11:12 Rev Time 0.00
Received By lfranco Date 2009-03-18 Time 11:12 Sent To FIRE
Notes
2009-03-18 11:31:26PLANNING AND ZONING: **** FAILED ****
  
 1. PLEASE RESPOND TO COMMENTS IN WRITING.
  
 2. THE PROPOSED DAYCARE IS A CHANGE OF USE THAT IS
 PERMITTED WITH PXRS (EXTRA REQUIREMENTS) PURSUANT TO
 THE ZONING AND LAND DEVELOPMENT REGULATIONS ("ZLDR"),
 ARTICLE IX, SECTION 94-272, (A)TABLE IX-1 (DAYCARE
 FACILITIES , AS PRINCIPAL USES, APPLICATIONS TO
 ESTABLISH CHILD DAY CARE CENTER SHALL COMPLY WITH THE
 REQUIREMENTS OF LAWS OF FLA. CH. 59 (1698), AS AMENDED.
 PROVIDE INFORMATION REGARDING HOW THE YOU ARE COMPLYING
 WITH STATE REQUIREMENTS, INCLUDING PLAYGROUND AREA FOR
 CHILDREN AND SQUARE FOOTAGE PER CHILD, ETC.
  
 3. ADDITIONALLY, THE BACK YARD (REAR) OF THE PROPERTY
 APPEARS TO BE COMPLETELY COVERED WITH ASPHALT/CONCRETE.
 WAS THERE A PERMIT SUBMITTED AND APPROVED FOR THIS
 WORK. HOW IS THIS IMPERVIOUS COVERAGE MEETING THE
 REQUIREMENTS OF THE ZLDR FOR IMPERVIOUS, OPEN SPACE AND
 LANDSCAPING REQUIREMENTS PURSUANT TO THE LANDSCAPING
 ARTICLE XIV?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved