Plan Review Details - Permit 09010310
Plan Review Stops For Permit 09010310
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-08-11 Cont ID  
Sent By jgomez Date 2009-08-11 Time 16:30 Rev Time 0.00
Received By jgomez Date 2009-08-11 Time 16:26 Sent To  
Notes
2009-08-11 16:31:34BUILDING REVIEW FOURTH CHECKLIST.
 2004 FBC WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK
 UP.
  
 2- WOMEN TOILET ROOM DOESN'T COMPLY WITH SEC. 11-4.22.
 TOILET ROOM PROVIDED DOESN'T PROVIDE THE UNOBSTRUCTED
 TURNING SPACE COMPLYING WITH SEC. 11-4.2.3.
  
 3- DOOR LEADING TO WOMEN TOILET ROOM DOESN'T COMPLY
 WITH SEC. 11-4.13.5. NEED MINIMUM CLEAR OPENING OF 32".
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-05-29 Cont ID  
Sent By jgomez Date 2009-05-29 Time 09:45 Rev Time 0.00
Received By jgomez Date 2009-05-29 Time 09:45 Sent To  
Notes
2009-05-29 10:03:20MOTOR VEHICLE SHOWROOM (B), BUILDING REVIEW THIRD
 CHECKLIST.
 REVIEW UNDER 2004 FBC WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- ORIGINAL COMMENT: MEN TOILET ROOM NEEDS TO COMPLY
 WITH CHAPTER 11 FBC 2004 SEC. 11-4.1.3(11). IF TOILETS
 ARE PROVIDED THEN BOTH MEN AND WOMEN NEED TO COMPLY.
 RESPONSE SAYING THAT HANDICAPPED TOILET ROOM FOR MEN IS
 ON ANOTHER AREA DOESN'T PROVIDE EQUALITY FOR EVERYBODY.
 CODE SECTION REQUIRES EACH TOILET ROOM TO COMPLY.
  
 *** ARCHITECT'S RESPONSE TO THIS COMMENT: "MEN'S TOILET
 HAS BEEN REMOVED AS PER BUILDING DEPARTMENT
 REQUIREMENT".
  
 CLARIFICATION: IT IS NOT THE BUILDING DEPARTMENT
 REQUIREMENT TO REMOVE THE MEN'S TOILET. IF TOILETS ARE
 PROVIDED, THEN BOTH NEED TO COMPLY WITH SEC.
 11-4.1.3(11) OF 2004 FBC. PLANS NOW SHOW ONLY TOILET
 ROOM FOR WOMEN. NEED TO PROVIDE TOILET ROOM FOR MEN
 ALSO AND BOTH NEED TO BE ADA COMPLIANT. ANOTHER
 SOLUTION MAY BE TO PROVIDE UNISEX TOILET. CHECK WITH
 THE PLUMBING CODE FOR REQUIRED NUMBER OF FIXTURES.
 REVISE PLANS AS REQUIRED.
  
 3- NEED TO PROVIDE TURNING AREA AT THE KITCHENETTE AREA
 TO COMPLY WITH SEC. 11-4.2.3 FBC 2004. T-SHAPED SPACE
 SHOWN IS OUTSIDE THE KITCHENETTE AREA. NEED TO PROVIDE
 TURNING AREA INSIDE THE KITCHENETTE AREA. OTHERWISE A
 PERSON USING A WHEELCHAIR NEEDS TO REVERSE TO GET OUT.
  
 REVISED PLAN STILL DOESN'T PROVIDE TURNING AREA.
 HANDICAPPED PERSON USING THE REFRIGERATOR STILL HAS TO
 BACK UP ALL THE WAY BACK. THERE IS NO TURNING AREA
 PROVIDED IN THIS AREA. TURNING AREA IS STILL PROVIDED
 OUTSIDE THE KITCHENETTE AREA, NOT INSIDE. REVISE PLANS
 AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-30 Cont ID  
Sent By jgomez Date 2009-03-30 Time 13:55 Rev Time 0.00
Received By jgomez Date 2009-03-30 Time 13:55 Sent To  
Notes
2009-03-30 15:30:46MOTOR VEHICLE SHOWROOM (B), BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2004 FBC WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- MEN TOILET ROOM NEEDS TO COMPLY WITH CHAPTER 11 FBC
 2004 SEC. 11-4.1.3(11). IF TOILETS ARE PROVIDED THEN
 BOTH MEN AND WOMEN NEED TO COMPLY. RESPONSE SAYING THAT
 HANDICAPPED TOILET ROOM FOR MEN IS ON ANOTHER AREA
 DOESN'T PROVIDE EQUALITY FOR EVERYBODY. CODE SECTION
 REQUIRES EACH TOILET ROOM TO COMPLY.
  
 3- DOOR LEADING TO THE WOMEN TOILET ROOM DOESN'T COMPLY
 WITH MANEUVERING CLEARANCES AT DOORS AS REQUIRED BY
 SEC. 11-4.13.6 FBC 2004 AND FIGURE 25. PULL SIDE
 REQUIRES 60" MIN. REVISE AS REQUIRED.
  
 4- SHEET A-105. CLARIFY WHAT IS THE DOTTED LINE SHOWN
 ON SECTION-B OF HC SINK AT KITCHENETTE COUNTER DETAIL
 FOR.
  
 5- NEED TO PROVIDE TURNING AREA AT THE KITCHENETTE AREA
 TO COMPLY WITH SEC. 11-4.2.3 FBC 2004. T-SHAPED SPACE
 SHOWN IS OUTSIDE THE KITCHENETTE AREA. NEED TO PROVIDE
 TURNING AREA INSIDE THE KITCHENETTE AREA. OTHERWISE A
 PERSON USING A WHEELCHAIR NEEDS TO REVERSE TO GET OUT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-27 Cont ID  
Sent By jgomez Date 2009-01-27 Time 10:56 Rev Time 0.00
Received By jgomez Date 2009-01-27 Time 10:55 Sent To  
Notes
2009-01-27 11:00:07MOTOR VEHICLE SHOWROOM (B), BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FBC WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE. SEE ITEM #10 BELOW FOR
 CORRECT ADDRESS AND PARCEL ID NUMBER INFORMATION.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- CLEAR FLOOR SPACE OF WOMEN HANDICAPPED RESTROOM
 DOESN'T COMPLY WITH SEC. 11-4.22.3 FBC 2004. THERE IS
 NOT AN UNOBSTRUCTED TURNING SPACE COMPLYING WITH SEC.
 11-4.2.3.
  
 3- SPECIFY ALL DIMENSIONS ON WOMEN HANDICAPPED TOILET
 RESTROOM TO VERIFY COMPLIANCE WITH ALL MINIMUM
 CLEARANCES REQUIRED BY CHAPTER 11 FBC 2004.
  
 4- CLARIFY WHY THE MEN'S TOILET ROOM IS NOT DESIGNED TO
 COMPLY WITH CHAPTER 11 FBC 2004 SEC. 11-4.1.3(11).
  
 5- SPECIFY ALL DIMENSIONS FOR OFFICE NEXT TO THE
 KITCHENETTE TO VERIFY CLEARANCES BETWEEN COUNTERS. SEC.
 11-4.3 FBC 2004.
  
 6- SPECIFY ALL DIMENSIONS NEXT TO THE DOORS TO VERIFY
 COMPLIANCE WITH MANEUVERING CLEARANCES AT DOORS AS
 REQUIRED BY SEC. 11-4.13.6 FBC 2004. CHECK DOOR THAT
 PROVIDES ACCESS TO THE WOMENS TOILET ROOM. THERE IS NO
 ENOUGH ROOM. ALSO, CHECK DOOR IN OFFICE NEXT TO THE
 KITCHENETTE AREA.
  
 7- UPPER CABINETS SHOWN ON OFFICE NEXT TO THE
 KITCHENETTE AREA AND IN THE KITCHENETTE AREA NEED TO
 COMPLY WITH SEC. 11-4.25.3. FBC 2004.
  
 8- SHEET A-103: PROPOSED OPENING DETAIL SPECIFIES THAT
 MAXIMUM OPENING TO BE 50", WHILE SHEET A-101 SPECIFIES
 OPENING TO BE 4'-6" X 7'-2". REVISE AS REQUIRED TO
 MATCH.
 ***NOTE: COORDINATE OPENING DIMENSIONS WITH REQUIRED
 CLEARANCE FOR DOOR MANEUVERING. SEE ITEM #5 ABOVE.
  
 9- SHEET A-105: KITCHENETTE SINK DIMENSIONS TO COMPLY
 WITH SEC. 11-4.24.3 (KNEE CLEARANCE), 11-4.24.4 (SINK
 DEPTH) AND SEC. 11-4.24.5 (CLEAR FLOOR SPACE UNDERNEATH
 THE SINK). REVISE AS REQUIRED.
  
 10- CLARIFY TYPE OF HARDWARE FOR ALL ACCESSIBLE DOORS
 TO REVIEW COMPLIANCE WITH SEC. 11-4.13.9 FBC 2004. DOOR
 TYPES SHOWN ON DOOR SCHEDULE ON SHEET A-106 DON'T SHOW
 APPROVED TYPE OF HARDWARE. THEY SHOW TWISTING HANDLES.
 REVISE/CLARIFY SPECIFICATIONS AND DRAWINGS AS REQUIRED.
  
 11- CLARIFY ADDRESS OF BUILDING. ACCORDING TO THE
 PROPERTY APPRAISAL WEBSITE, THERE ARE THREE DIFFERENT
 BUILDING WITH THREE DIFFERENT ADDRESSES THAT ARE OWNED
 BY THE SAME OWNER. BUILDING WHERE WORK IS TAKEN PLACE
 IS THE 901 S. DIXIE HWY, NOT 915 S. DIXIE HWY. SEE
 ATTACHED COPY OF PROPERTY APPRAISAL AERIAL VIEW. REVISE
 ADDRESS ON PLANS AND PERMIT APPLICATION AS REQUIRED.
 ***NOTE: PLEASE MAKE SURE CORRECT PARCEL ID NUMBER IS
 USED ON PERMIT APPLICATION TO AVOID ANY CONFLICTS OR
 DELAYS. ALSO, INFORMATION ON NOTICE OF COMMENCEMENT
 NEED TO MATCH ACCORDINGLY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2009-05-28 Time 09:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-15 Cont ID  
Sent By btrobaug Date 2009-04-15 Time 08:53 Rev Time 0.00
Received By btrobaug Date 2009-04-15 Time 08:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-02-06 Cont ID  
Sent By btrobaug Date 2009-02-06 Time 11:40 Rev Time 0.00
Received By btrobaug Date 2009-02-06 Time 07:15 Sent To I
Notes
2009-02-06 10:17:03 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE CIRCUIT NUMBERS SOR THE LIGHTING CIRCUITS
 SHOWN ON SHEET E-102. 106.3.5 FBC AS AMENDED.
  
 2} THE LPD OF 1.2 W/SQ.FT FOR THE CORRIDOR DENSITY IS
 INCORRECT PER 13-415.2.B WHICH LISTS CORRIDORS @ 0.5
 ALLOWED W/SQ.FT. SHEET E-102.
  
 3} PROVIDE A PANEL SCHEDULES FOR THE REMODEL AREA
 CIRCUITING PER 408.4 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-27 Cont ID  
Sent By mawillia Date 2009-05-27 Time 16:07 Rev Time 0.00
Received By mawillia Date 2009-05-27 Time 15:41 Sent To  
Notes
2009-05-27 16:00:59*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS A-101, A-102, E-101, &
 E-102 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-04-07 Cont ID  
Sent By mawillia Date 2009-04-07 Time 14:13 Rev Time 0.00
Received By mawillia Date 2009-04-07 Time 13:55 Sent To  
Notes
2009-04-07 14:02:09*****PROVISO*****
  
  
 1. ON SHEET A-101, AMEND INFORMATION (NEW INTERIOR WALL
 CEILING FINISH) TO REFLECT THAT THE 2006 EDITION OF
 NFPA 101- LIFE SAFETY CODE - IS REFERENCED. (BE ADVISED
 THAT THE CHANGE OF EDITIONS WENT INTO EFFECT AS OF
 12/31/2008.)
  
 THE APPROPIATE PLAN SHEETS ( A-101, A-102, E-101, &
 E-102) TO BE FIRE-STAMPED WHEN THE ABOVE COMMENT AS
 WELL AS THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-02-02 Cont ID  
Sent By mawillia Date 2009-02-02 Time 15:35 Rev Time 0.00
Received By mawillia Date 2009-02-02 Time 15:14 Sent To  
Notes
2009-02-02 15:35:01*****UNSAT*****
  
  
 1. ON SHEETS A-100 AND A-101, AMEND INFORMATION TO
 REFLECT THAT THE 2006 EDITION OF NFPA 101- LIFE SAFETY
 CODE - IS REFERENCED. (BE ADVISED THAT THE CHANGE OF
 EDITIONS WENT INTO EFFECT AS OF 12/31/2008.)
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE ABOVE COMMENT AS WELL AS THE OTHER PLAN EXAMINERS'
 COMMENTS HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-07-22 Cont ID  
Sent By lmartine Date 2009-07-22 Time 14:08 Rev Time 0.00
Received By lmartine Date 2009-07-22 Time 13:54 Sent To  
Notes
2009-07-22 14:09:09C-1

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2009-05-28 Cont ID  
Sent By btrobaug Date 2009-05-28 Time 10:19 Rev Time 0.00
Received By btrobaug Date 2009-05-13 Time 10:10 Sent To  
Notes
2009-05-13 10:10:50INCOMING TO C-4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-12 Cont ID  
Sent By shill Date 2009-03-12 Time 09:32 Rev Time 0.00
Received By shill Date 2009-03-12 Time 09:32 Sent To  
Notes
2009-03-12 09:32:23TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-06 Cont ID  
Sent By btrobaug Date 2009-02-06 Time 11:40 Rev Time 0.00
Received By btrobaug Date 2009-01-23 Time 10:30 Sent To PC
Notes
2009-01-23 10:32:44TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-08-05 Cont ID  
Sent By rregueir Date 2009-08-05 Time 08:44 Rev Time 0.00
Received By rregueir Date 2009-08-05 Time 08:30 Sent To  
Notes
2009-08-05 08:44:41PREVIOUSLY PASSED PAGE M101 REPLACED BY REVISION DELTA
 5.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-02-05 Cont ID  
Sent By rregueir Date 2009-02-05 Time 20:14 Rev Time 0.00
Received By rregueir Date 2009-02-05 Time 20:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2009-08-13 Cont ID  
Sent By kstevens Date 2009-08-10 Time 14:00 Rev Time 0.00
Received By kstevens Date 2009-08-10 Time 14:00 Sent To  
Notes
2009-08-13 10:20:41DENIED
 REFERENCE:
 FBC-2004 CHAPTER 11
  
 1. PLANS AS SUBMITTED INDICATE 2 SEPARATE TOILET ROOMS.
 PER SECTION 11-4.1.3(11) EACH TOILET ROOM SHALL BE
 ACCESSIBLE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-05-22 Cont ID  
Sent By kstevens Date 2009-05-22 Time 09:13 Rev Time 0.00
Received By kstevens Date 2009-05-22 Time 09:13 Sent To  
Notes
2009-05-22 09:18:52DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
  
 2. SHT A-101 SUBMIT DETAILS/ELEVATIONS SHOWING
 COMPLIANCE WITH THE FOLLOWING:
  
 A. DRINKING FOUNTAIN
 1. 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ****RESPONSE NOTED, BUT COMMENT CONSERNING SECTION
 11-4.1.3(10)(A) NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMMENT CONSERNING SECTION
 11-4.1.3(10)(A) STILL NOT ADDRESSED.
  
 B. OK (DELETED)
  
 C. STALLS
 1. 11-4.17.3 SIZE & ARRANGEMENT EXCEPTION (1)(2) LAV
 REQUIRED IN STALL. (SEE FIGURE 30(E)).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PER
 SECTION 11-4.1.6(1)(B) IF EXISTING ELEMENTS, SPACES, OR
 COMMON AREAS ARE ALTERED, THEN EACH SUCH ALTERED
 ELEMENT, SPACE, FEATURE, OR AREA SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF SECTION 11-4.1.1 TO SECTION
 11-4.1.3, MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. AS
 SUCH THE LAV IS REQUIRED. THE COMMENT RESPONSE
 INDICATES THAT ON PERMIT NUMBERS 07080049 & 07110548 I
 HAD COMPLETED THE REVIEWS AND THAT I HAD VERIFIED WITH
 THE BUILDING OFFICIAL. PLAN REVIEWER MIKE PERSON
 FINISHED THE REVIEW FOR PERMIT 07080049 IN WHICH I HAD
 INDICATED THE REQUIRMENT FOR THE LAV. MIKE PERSON ALSO
 DID THE REVIEW FOR PERMIT 07110548. IF THERE IS AN
 EXCEPTION TO THE REQUIREMENT PLEASE SUBMIT THE
 EXCEPTION. THE E-MAIL WAS NOT FROM ME SO I AM NOT
 FAMILIAR WITH THE E-MAIL.
 ****RESPONSE NOTED, BUT COMMENT RESPONSE "MEN'S TOILET
 HAS BEEN REMOVED FROM THE PLANS AS PER BUILDING
 DEPARTMENT REQUIRMENT" DOES NOT ADDRESS THE COMMENT AND
 REMOVAL OF THE MEN'S TOILET ROOM HAS NEVER BEEN A
 REQUIREMENT. THE ONLY REQUIREMENT WAS THAT THE MEN'S
 TOILET ROOM BE ACCESSIBLE.
  
 D. OK
  
 F. TOILET ROOMS
 1. OK (DELETED)
 3. OK (DELETED)
 OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-04-01 Cont ID  
Sent By kstevens Date 2009-04-01 Time 14:54 Rev Time 0.00
Received By kstevens Date 2009-04-01 Time 14:54 Sent To  
Notes
2009-04-01 16:28:14DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A-101 SUBMIT DETAILS/ELEVATIONS SHOWING
 COMPLIANCE WITH THE FOLLOWING:
  
 A. DRINKING FOUNTAIN
 1. 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ****RESPONSE NOTED, BUT COMMENT CONSERNING SECTION
 11-4.1.3(10)(A) NOT ADDRESSED.
  
 B. W/C'S
 1. 11-4.16.4 GRAB BARS (NOT SHOWN IN MEN'S TOILET
 ROOM).
 ****RESPONSE NOTED, BUT THE DEMO SHEET DOES NOT SHOW
 THE MENS TOILET ROOM AS EXISTING SO THIS IS A NEW
 TOILET ROOM AND AS SUCH PER SECTION 11-4.1.3(11) IF
 TOILET ROOMS ARE PROVIDED, THEN EACH TOILET ROOM SHALL
 COMPLY WITH SECTION 11-4.22. SECTION 11-4.1.6((1)(B).
 COMMENT NOT ADDRESSED.
  
 C. STALLS
 1. 11-4.17.3 SIZE & ARRANGEMENT EXCEPTION (1)(2) LAV
 REQUIRED IN STALL. (SEE FIGURE 30(E)).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PER
 SECTION 11-4.1.6(1)(B) IF EXISTING ELEMENTS, SPACES, OR
 COMMON AREAS ARE ALTERED, THEN EACH SUCH ALTERED
 ELEMENT, SPACE, FEATURE, OR AREA SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF SECTION 11-4.1.1 TO SECTION
 11-4.1.3, MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. AS
 SUCH THE LAV IS REQUIRED. THE COMMENT RESPONSE
 INDICATES THAT ON PERMIT NUMBERS 07080049 & 07110548 I
 HAD COMPLETED THE REVIEWS AND THAT I HAD VERIFIED WITH
 THE BUILDING OFFICIAL. PLAN REVIEWER MIKE PERSON
 FINISHED THE REVIEW FOR PERMIT 07080049 IN WHICH I HAD
 INDICATED THE REQUIRMENT FOR THE LAV. MIKE PERSON ALSO
 DID THE REVIEW FOR PERMIT 07110548. IF THERE IS AN
 EXCEPTION TO THE REQUIREMENT PLEASE SUBMIT THE
 EXCEPTION. THE E-MAIL WAS NOT FROM ME SO I AM NOT
 FAMILIAR WITH THE E-MAIL.
  
 D. OK
  
 F. TOILET ROOMS
 1. 11-4.22.3 UNOBSTRUCTED TURNING AREA REQUIRED. (NOT
 SHOWN IN MEN'S TOILET ROOM).
 ****RESPONSE NOTED, BUT SINCE THIS IS A NEW TOILET ROOM
 IT SHALL BE ACCESSIBLE. SECTION 11-4.1.6(1)B).
  
 3. MEN'S TOILET ROOM SHALL BE ACCESSIBLE. SECTION
 11-4.1.6(1)(B).
 ****RESPONSE NOTED, BUT ALL TOILET ROOMS PROVIDED SHALL
 COMPLY WITH SECTION 11-4.22.
  
 4. A TURNING AREA IS REQUIRED AT THE KITCHENETTE.
 SECTION 11-4.2.3.
 ****RESPONSE NOTED, BUT THE TURNING AREA IS REQUIRED
 "IN" THE KITCHENETTE, NOT OUTSIDE THE KITCHENETTE.
  
 5. OK
 6. OK
 7. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-02-04 Cont ID  
Sent By kstevens Date 2009-02-04 Time 14:22 Rev Time 0.00
Received By kstevens Date 2009-02-04 Time 14:22 Sent To  
Notes
2009-02-04 14:43:50DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-101 REFERENCES DETAILED FIXTURE & ACCESSORIES
 ON SHEET A-104, BUT NO FIXTURES AND ACCESSORIES WERE
 FOUND. PLEASE CLARIFY & CORRELATE. SECTION 106.1.1 &
 CHAPTER 11.
  
 2. SHT A-101 SUBMIT DETAILS/ELEVATIONS SHOWING
 COMPLIANCE WITH THE FOLLOWING:
  
 A. DRINKING FOUNTAIN
 1. 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 B. W/C'S
 1. 11-4.16.4 GRAB BARS (NOT SHOWN IN MEN'S TOILET
 ROOM).
  
 C. STALLS
 1. 11-4.17.3 SIZE & ARRANGEMENT EXCEPTION (1)(2) LAV
 REQUIRED IN STALL. (SEE FIGURE 30(E)).
  
 D. LAV'S
 1. 11-4.19.2 CLEARANCE (29").
  
 F. TOILET ROOMS
 1. 11-4.22.3 UNOBSTRUCTED TURNING AREA REQUIRED. (NOT
 SHOWN IN MEN'S TOILET ROOM).
  
 3. MEN'S TOILET ROOM SHALL BE ACCESSIBLE. SECTION
 11-4.1.6(1)(B).
  
 4. A TURNING AREA IS REQUIRED AT THE KITCHENETTE.
 SECTION 11-4.2.3.
  
 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM REQUIRED BY
 SECTION 106.3.5.1.3(3)(5)(8)(10)(13). SHOW ALL PIPE
 SIZES, VALVES, WATER HEATER, THERMAL EXPANSION CONTROL,
 WATER HAMMER ARRESTORS & RPZV BACKFLOW PREVENTOR.
 SECTIONS 604.1, 604.9, 606.1, 606.2, 607.13.2 &
 608.13.2.
  
 6. SHT P-102 PLUMBING SPECIFICATIONS 2(A) CODES TO
 INCLUDE THE 2007 AMENDMENTS TO THE FBC-2004 PLUMBING
 CODE. THE STANDARD CODE IS NOT ADOPTED. PLEASE DELETE
 REFERENCE TO STANDARD CODE. SECTION 106.1.2
  
 7. SHT P-102 PLUMBING SPECIFICATIONS 5(F) AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE REFERENCE. SECTION
 604.9 AND PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  