2009-02-09 15:45:14 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. THIS WORK IS NOT WITHIN THE SCOPE OF AN ELECTRICAL |
| CONTRACTOR'S LICENSE. FS 489.505 (12) "ELECTRICAL |
| CONTRACTOR" OR "UNLIMITED ELECTRICAL CONTRACTOR" MEANS |
| A PERSON WHO CONDUCTS BUSINESS IN THE ELECTRICAL TRADE |
| FIELD AND WHO HAS THE EXPERIENCE, KNOWLEDGE, AND SKILL |
| TO INSTALL, REPAIR, ALTER, ADD TO, OR DESIGN, IN |
| COMPLIANCE WITH LAW, ELECTRICAL WIRING, FIXTURES, |
| APPLIANCES, APPARATUS, RACEWAYS, CONDUIT, OR ANY PART |
| THEREOF, WHICH GENERATES, TRANSMITS, TRANSFORMS, OR |
| UTILIZES ELECTRICAL ENERGY IN ANY FORM, INCLUDING THE |
| ELECTRICAL INSTALLATIONS AND SYSTEMS WITHIN PLANTS AND |
| SUBSTATIONS, ALL IN COMPLIANCE WITH APPLICABLE PLANS, |
| SPECIFICATIONS, CODES, LAWS, AND REGULATIONS. THE TERM |
| MEANS ANY PERSON, FIRM, OR CORPORATION THAT ENGAGES IN |
| THE BUSINESS OF ELECTRICAL CONTRACTING UNDER AN EXPRESS |
| OR IMPLIED CONTRACT; OR THAT UNDERTAKES, OFFERS TO |
| UNDERTAKE, PURPORTS TO HAVE THE CAPACITY TO UNDERTAKE, |
| OR SUBMITS A BID TO ENGAGE IN THE BUSINESS OF |
| ELECTRICAL CONTRACTING; OR THAT DOES ITSELF OR BY OR |
| THROUGH OTHERS ENGAGE IN THE BUSINESS OF ELECTRICAL |
| CONTRACTING. |
| |
| 2. PLEASE INCLUDE WIND DESIGN CRITERIA FBC1609. |
| |
| 3. PLEASE INCLUDE GOVERNING CODE INCLUDING 2007 |
| REVISIONS/SUPPLEMENTS. |
| |
| 4. PLEASE SHOW COMPLIANCE WITH FBC 3105.1.1. NO SITE |
| PLAN SHOWING PROPERTY LINES PROVIDED. |
| |
| 5. NO STRUCTURAL INFORMATION PROVIDED TO SHOW |
| COMPLIANCE WITH FBC3105.4. DESIGN CRITERIA NOT CLEAR. |
| |
| 6. IF THIS IS TO BE REMOVABLE, REMOVAL INSTRUCTIONS |
| REQUIRED TO SHOW COMPLIANCE WITH FBC3105.4.2.1. |
| |
| 7. IF THIS IS TO BE REMOVABLE, . PER BUILDING OFFICIAL, |
| WE ARE TO PUT ON THE PERMIT FILE A LETTER, OR |
| CONTRACTORS FORM, SIGNED BY THE OWNER (NOT THE TENANT) |
| TO ACKNOWLEDGE THEIR RESPONSIBILITY TO HAVE THE AWNING |
| COVER REMOVED PRIOR TO ANY WIND EVENT WITH PROJECTED |
| WIND SPEEDS OF 75 MPH OR GREATER. THE LETTER/FORM MUST |
| BE SIGNED BY THE OWNER BUT IT NEED NOT BE NOTARIZED. |
| |
| 8. SHOW COMPLIANCE WITH FBC3105.3. |
| |
| 9. PROVIDE A STRUCTURAL DETAIL FOR THE EXISTING FRAME. |
| |
| |
| |