Plan Review Details - Permit 09010267
Plan Review Stops For Permit 09010267
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-09 Cont ID  
Sent By shill Date 2009-02-09 Time 15:13 Rev Time 0.00
Received By shill Date 2009-02-09 Time 15:13 Sent To  
Notes
2009-02-09 15:45:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THIS WORK IS NOT WITHIN THE SCOPE OF AN ELECTRICAL
 CONTRACTOR'S LICENSE. FS 489.505 (12) "ELECTRICAL
 CONTRACTOR" OR "UNLIMITED ELECTRICAL CONTRACTOR" MEANS
 A PERSON WHO CONDUCTS BUSINESS IN THE ELECTRICAL TRADE
 FIELD AND WHO HAS THE EXPERIENCE, KNOWLEDGE, AND SKILL
 TO INSTALL, REPAIR, ALTER, ADD TO, OR DESIGN, IN
 COMPLIANCE WITH LAW, ELECTRICAL WIRING, FIXTURES,
 APPLIANCES, APPARATUS, RACEWAYS, CONDUIT, OR ANY PART
 THEREOF, WHICH GENERATES, TRANSMITS, TRANSFORMS, OR
 UTILIZES ELECTRICAL ENERGY IN ANY FORM, INCLUDING THE
 ELECTRICAL INSTALLATIONS AND SYSTEMS WITHIN PLANTS AND
 SUBSTATIONS, ALL IN COMPLIANCE WITH APPLICABLE PLANS,
 SPECIFICATIONS, CODES, LAWS, AND REGULATIONS. THE TERM
 MEANS ANY PERSON, FIRM, OR CORPORATION THAT ENGAGES IN
 THE BUSINESS OF ELECTRICAL CONTRACTING UNDER AN EXPRESS
 OR IMPLIED CONTRACT; OR THAT UNDERTAKES, OFFERS TO
 UNDERTAKE, PURPORTS TO HAVE THE CAPACITY TO UNDERTAKE,
 OR SUBMITS A BID TO ENGAGE IN THE BUSINESS OF
 ELECTRICAL CONTRACTING; OR THAT DOES ITSELF OR BY OR
 THROUGH OTHERS ENGAGE IN THE BUSINESS OF ELECTRICAL
 CONTRACTING.
  
 2. PLEASE INCLUDE WIND DESIGN CRITERIA FBC1609.
  
 3. PLEASE INCLUDE GOVERNING CODE INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 4. PLEASE SHOW COMPLIANCE WITH FBC 3105.1.1. NO SITE
 PLAN SHOWING PROPERTY LINES PROVIDED.
  
 5. NO STRUCTURAL INFORMATION PROVIDED TO SHOW
 COMPLIANCE WITH FBC3105.4. DESIGN CRITERIA NOT CLEAR.
  
 6. IF THIS IS TO BE REMOVABLE, REMOVAL INSTRUCTIONS
 REQUIRED TO SHOW COMPLIANCE WITH FBC3105.4.2.1.
  
 7. IF THIS IS TO BE REMOVABLE, . PER BUILDING OFFICIAL,
 WE ARE TO PUT ON THE PERMIT FILE A LETTER, OR
 CONTRACTORS FORM, SIGNED BY THE OWNER (NOT THE TENANT)
 TO ACKNOWLEDGE THEIR RESPONSIBILITY TO HAVE THE AWNING
 COVER REMOVED PRIOR TO ANY WIND EVENT WITH PROJECTED
 WIND SPEEDS OF 75 MPH OR GREATER. THE LETTER/FORM MUST
 BE SIGNED BY THE OWNER BUT IT NEED NOT BE NOTARIZED.
  
 8. SHOW COMPLIANCE WITH FBC3105.3.
  
 9. PROVIDE A STRUCTURAL DETAIL FOR THE EXISTING FRAME.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 10:22 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 10:22 Sent To B
Notes
2009-02-09 10:22:55TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-09 Cont ID  
Sent By shill Date 2009-02-09 Time 15:45 Rev Time 0.00
Received By shill Date 2009-01-22 Time 08:51 Sent To  
Notes
2009-01-22 08:51:42TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-05 Cont ID  
Sent By aaponte Date 2009-02-05 Time 14:42 Rev Time 0.00
Received By aaponte Date 2009-02-05 Time 14:42 Sent To  
Notes
2009-02-05 14:45:531. PERMIT IS FOR A NEW AWNING, NOT A REPLACEMENT.
 2.ACCORDING WITH THE DMP REGULATIONS, THE TYPE OF
 AWNING USED AND ITS FORM, MATERIALS AND COLOR SHALL BE
 CONSISTENT WITH THE DESIGN CHARACTER OF THE BUILDING TO
 WHICH IT IS ATTACHED. PROPOSED AWNING IS NOT CONSISTENT
 WITH EXISTING BUILDING.
 3. SAMPLE OF AWNING MATERIAL SHALL BE SUBMITTED WITH
 PERMIT APPLICATION.