Plan Review Stops For Permit 08120587 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2009-04-08 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2009-04-08 |
Time |
08:55 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2009-04-08 |
Time |
08:23 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2009-02-24 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2009-02-24 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2009-02-24 |
Time |
08:54 |
Sent To |
PC |
|
Notes |
2009-02-24 08:54:26 | BUILDING PLAN REVIEW | | PERMIT: 08120587 | | ADD: 401 CLEMATIS STREET | | CONT: MEISNER ELECTRIC | | TEL: (561)278-8362 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 2ND | | ACTION: DENIED | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) * NO RESPONSE NOT ADDRESSED:* PLANS SUBMITTED FOR | | PERMIT (FIRST TIME REVIEW) AFTER JULY 1ST, 2007 SHALL | | BE REVIEWED TO THE 2004 FBC BUILDING WITH THE 2007 | | SUPPLEMENTS. THIS INFORMATION SHALL BE INDICATED ON THE | | DRAWINGS. | | | | 3) PROVIDE THE STRUCTURAL CALCULATIONS WITH THE WIND | | LOAD INFORMATION PER 1603.1.4. AS STATED ON THE PLANS, | | THE BURIAL DEPTH, FOUNDATION REQUIREMENTS AND WIND LOAD | | INFORMATION SHALL BE PROVIDED BY A STRUCTURAL ENGINEER | | SIGN, SEAL AND DATED PER FAC 61G15-23.002. | | NOTE: TWO DIFFERENT CALCULATION REPORTS WERE SUBMITTED | | FOR TWO DIFFERENT POLES. IF TWO TYPES OF POLES WILL BE | | INSTALLED AT THE LOCATION PROVIDE TWO SETS OF REPORTS | | FOR EACH POLE. THE LIGHT POLE ON THE SITE PLAN IS | | DIFFERENT FROM THE LIGHT POLE SPECIFICATION PROVIDED. | | CLARIFY. | | | | 4) THE ORIGINAL DESIGNER SHALL APPROVE THE LIGHT POLE | | PRIOR TO THE INSTALLATION. THE SHOP DRAWING STAMP OF | | THE ORIGINAL DESIGN TEAM IS REQUIRED ON ALL SUBMITTALS | | DOCUMENTS. THE SIGNATURE ON ALL DOCUMENTS SUBMITTED FOR | | RECORD RETENTION SHALL CONTAIN THE ORIGINAL SIGNATURE | | OF THE PERSON SIGNING EACH DOCUMENT. 106.1.3* | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-01-12 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2009-01-12 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2009-01-12 |
Time |
08:53 |
Sent To |
PC |
|
Notes |
2009-01-12 08:53:30 | BUILDING PLAN REVIEW | | PERMIT: 08120587 | | ADD: 401 CLEMATIS STREET | | CONT: MEISNER ELECTRIC | | TEL: (561)278-8362 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 1ST | | ACTION: DENIED | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION | | SHALL BE INDICATED ON THE DRAWINGS. | | | | 3) PROVIDE THE STRUCTURAL CALCULATIONS WITH THE WIND | | LOAD INFORMATION PER 1603.1.4. AS STATED ON THE PLANS, | | THE BURIAL DEPTH, FOUNDATION REQUIREMENTS AND WIND LOAD | | INFORMATION SHALL BE PROVIDED BY A STRUCTURAL ENGINEER | | SIGN, SEAL AND DATED PER FAC 61G15-23.002. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2009-04-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-04-06 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-04-06 |
Time |
11:04 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2009-02-23 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-02-23 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-02-17 |
Time |
09:17 |
Sent To |
B |
|
Notes |
2009-02-17 09:25:05 | | | | | | | SENT TO ZONING, DID NOT GET A ZONING REVIEW FIRST TIME | | IN./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-01-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-01-06 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-01-06 |
Time |
13:25 |
Sent To |
B |
|
Notes |
2009-01-06 13:40:23 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | LUMINAIRES INTENDED TO BE INSTALLED. | | | | 2} A "RIGHT OF WAY" PERMIT FROM WEST PALM BEACH | | ENGINEERING DEPARTMENT IS REQUIRED PRIOR TO THE | | ELECTRICAL PERMIT BEING ISSUED. THE ENGINEERING OFFICE | | IS LOCATED @ 1000 45TH STREET, WEST PALM BEACH AND THE | | PHONE NUMBER IS561-494-1128. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2009-03-31 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-03-31 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-03-31 |
Time |
15:06 |
Sent To |
E |
|
Notes |
2009-03-31 15:06:56 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-02-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-02-12 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-02-12 |
Time |
15:53 |
Sent To |
E |
|
Notes |
2009-02-12 15:53:26 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2009-01-12 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-31 |
Time |
10:29 |
Sent To |
|
|
Notes |
2008-12-31 10:29:43 | TO "E" BOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2009-02-19 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2009-02-19 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2009-02-19 |
Time |
08:43 |
Sent To |
|
|
Notes |
2009-02-19 08:44:02 | ZONING REVIEW: NOT REQUIRED | | | | ** REVISED WIRING PLAN ONLY | | | | MATT FLIS - 822-1445 |
|
|