Plan Review Details - Permit 08120486
Plan Review Stops For Permit 08120486
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-23 Cont ID  
Sent By mjacobs Date 2009-01-23 Time 13:26 Rev Time 0.00
Received By mjacobs Date 2009-01-23 Time 13:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-12-29 Cont ID  
Sent By mjacobs Date 2008-12-29 Time 08:23 Rev Time 0.00
Received By mjacobs Date 2008-12-29 Time 08:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 13:03 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 13:03 Sent To  
Notes
2009-01-20 13:06:42TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-09 Cont ID  
Sent By kstevens Date 2009-01-09 Time 14:28 Rev Time 0.00
Received By kstevens Date 2008-12-23 Time 10:08 Sent To  
Notes
2008-12-23 10:10:23TO "BOB"#11

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 11:57 Rev Time 0.00
Received By kstevens Date 2009-01-27 Time 11:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-09 Cont ID  
Sent By kstevens Date 2009-01-09 Time 14:16 Rev Time 0.00
Received By kstevens Date 2009-01-09 Time 14:16 Sent To  
Notes
2009-01-09 14:28:18DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P-101 THE ENGINEERING FIRM AND THE ARCHITECTURAL
 FIRM SHALL INDICATE THE CERTIFICATE OF AUTHORIZATION
 NUMBER, (BUSINESS NUMBER), IN THE TITLE BLOCK. FAC
 61G15-23.002(2), 61G1-16.004(2) & FS 471.025, 481.219 &
 481.2055. PLEASE INDICATE BOTH NUMBERS IN TITLE BLOCK.
 (SEE ATTACHED SHEETS FROM FLORIDA STATE DBPR WEBSITE
 FOR CORRECT NUMBERS).
  
 2. SHT P-101 WITH THE LAVS BEING DELETED ON THE VENT
 STACK FOR THE WATER CLOSETS, A CLEANOUT IS REQUIRED ON
 THE VENT STACK. SECTION 708.3.4. PLEASE INDICATE A
 CLEANOUT ON THE VENT PIPE. THE SIZE OF THE CLEANOUT
 SHALL BE THE SAME NOMINAL SIZE AS THE PIPE THEY SERVE
 PER SECTION 708.7.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  